![Samson 4765 Mounting And Operating Instructions Download Page 8](http://html1.mh-extra.com/html/samson/4765/4765_mounting-and-operating-instructions_3922426008.webp)
2
Attachment
To attach the positioner to valves with cast
yokes, mounting parts (order no.
1400-5745) are used. For valves with
rod-type yokes (pillars), the mounting kit (or-
der no. 1400-5745) and additionally the
mounting kit (order no. 1400-5342) are
necessary (see also Table 2 on page 19).
Since the positioner can be attached on ei-
ther side of the valve, the physical location
(left or right attachment) should be deter-
mined before actual attachment (see corre-
sponding Figs. 6 to 9 in section 4.1).
2.1 Attachment to valves with
cast yokes
1. Fasten the plate (20) to the stem connec-
tor clamps (22) of the valve using the
screws (21).
2. Unscrew the positioner cover, and secure
the device to the valve yoke using the
mounting screw (15). The O-ring in-
cluded in the mounting kit is not required
for this device. Make sure that the pin (2)
is routed inside the wire strap and there-
fore clamped against the plate (20).
8
EB 8359-1 EN
Attachment
Legend for Figs. 4 and 5
1
Lever
2
Pin
2.1
Nut
15
Mounting screw
20
Plate
21
Screw
22
Stem connector
23
Plug stem
24
Travel indicator
26
Clamping plate
27
Valve rod (pillar)
28
Support
15
1
20
2
2.1
21
22 23
Fig. 4 · Attachment to valves with cast yokes (NAMUR rib)