![Samson 42-37 Mounting And Operating Instructions Download Page 32](http://html1.mh-extra.com/html/samson/42-37/42-37_mounting-and-operating-instructions_3938907032.webp)
5-2
EB 3017 EN
Installation
Support or suspension
The plant engineering company is responsi-
ble for selecting and implementing a suitable
support or suspension of the installed regula-
tor and the pipeline.
Depending on the regulator version and
mounting position, the valve, actuator and
pipeline must be supported or suspended.
Do not attach supports directly to the valve
or actuator.
Note
NOTICE
!
Standard mounting position,
suspended
All versions.
Suitable for steam control and
for medium temperatures above
80 °C.
Alternative mounting
position, actuator on top
All versions, DN 15 to 80.
Maximum medium temperature
80 °C
Alternative mounting
position (as required)
Version with fixed plug
guide. Maximum medium
temperature 80 °C
Fig. 5-1:
Mounting position
Summary of Contents for 42-37
Page 54: ...8 4 EB 3017 EN...
Page 66: ...11 2 EB 3017 EN...
Page 68: ...12 2 EB 3017 EN...
Page 70: ...13 2 EB 3017 EN...
Page 74: ...14 4 EB 3017 EN...
Page 83: ......