48
EB 8012 EN
Malfunctions
8
Malfunctions
Depending on the operating conditions, check the valve at certain intervals to prevent possi-
ble failure before it can occur. Operators are responsible for drawing up a test plan.
Tip:
SAMSON's After‑sales Service department can support you to draw up an inspection
plan for your plant.
8.1
Troubleshooting
Malfunction
Possible reasons
Recommended action
Actuator or plug stem does not
move on demand.
Actuator is blocked.
Check attachment.
Unblock the actuator.
Signal pressure too low
Check the signal pressure.
Check the signal pressure line for
leakage.
Actuator or plug stem does not
move through the whole range.
Signal pressure too low
Check the signal pressure.
Check the signal pressure line for
leakage.
The valve leaks to the atmo-
sphere (fugitive emissions).
The packing is defective.
Replace packing (see sec-
tion 7.2) or contact SAMSON's
After-sales Service department.
Version with adjustable pack-
ing
1)
: packing not tightened cor-
rectly.
See section 5.3, “Adjustable
packing”. Contact SAMSON's
After-sales Service department
when it continues to leak.
Version with bellows seal: the
metal bellows seal is defective.
Contact SAMSON's After-sales
Service department.
Flange joint loose or gasket
worn out.
Check the flange joint.
Replace gasket at the flanged
joint (see section 7.1 or contact
SAMSON's After-sales Service
department).
Summary of Contents for 3241
Page 11: ...EB 8012 EN 11 Safety instructions and measures...
Page 37: ...EB 8012 EN 37 Operation...
Page 58: ...58 EB 8012 EN Appendix...
Page 62: ...62 EB 8012 EN...
Page 63: ...EB 8012 EN 63...