Samson Corporation-Swannanoa, NC 28778-
800.311.1047 www.samsoncorporation.com
hird, connect the wires using the following color codes for the pigtail (provided) of the DFC:
Spec
:
T
DFC Pigtail Cable Color Belden Cable Color Connection
ial Wiring Notes
Solid Black
Common Ground for all Fluid Solenoids and
Ready Lights
Green/Black Tracer
Light
Station #1 Solenoid and Ready
Orange/Black Tracer
Station #2 Solenoid and Ready Light
Station #3 Sol
Red/Black Tracer
Station #4 Solenoid and Ready Light
Blue/Black Tracer
Station #5 Solenoid and Ready Light
Solid Blue
Station #6 Solenoid and Ready Light
Solid White
Station #7 Solenoid and Ready Light
Solid Orange
Station #8 Solenoid and Ready Light
Solid Green
Station #9 Solenoid and Ready Light
Black/White Tracer
Station #10 Solenoid and Ready Light
Green/White Tracer
Optional Air Solenoid
Blue White Tracer
Optional Air Solenoid
Solid Red
Impulse Meter – Not Polarized
Red/White Tracer
Impulse Meter – Not Polarized
White/Black Tracer
enoid and Ready Light
The Belden (or equivalent) wire colors will probably not be the same as the wire colors in the
tail. Use the crossover chart above indicating which color DFC pigtail wire is
connected to a particular color wire in the Belden (or equivalent) cable to help connect the
wire
m the Fluid
he
o
nnect the solid green wire to the building ground and use the other two wires to connect
Spe
provided DFC pig
System during installation and also to help diagnose the System if there are any problems.
The wires connected to the Impulse Meter are not polarized. There are three spade terminals
located on the micro-switch mounted inside the Impulse Meter; connect the wires to the two
outside terminals, leaving the middle terminal blank. It does not matter which Impulse Meter
is connected to either of the two outside terminals, since they are not polarized.
Wire the Fluid Solenoid and the Ready Light in a
PARALLELL CIRCUIT.
Take one lead from the
Fluid Solenoid and one lead from the Ready Light and connect both wires to the Black (Fluid
Solenoid Ground) wire with a wire nut (three wires total). Take the other lead fro
Solenoid and the other lead from the Ready Light and connect them using a wire nut to the
appropriately colored station wire using the chart above and the previously prepared map of t
shop.
Connect the two wires indicated in the chart above to the optional Air Solenoid, if it is used. D
not connect the Air Solenoid to any other wires. If the Air Solenoid itself is equipped with three
wires, co
to the DFC.
Do not let any wires ground to the building or short to each other.
Double-check all wire connections for accuracy and tightness prior to powering up the System.
cial Plumbing Notes:
The Impulse Meter is located at the pump. The meter should be plumbed as indicated on the
luded with it; the flow path is into the base of the meter and out the side of
the meter. Impulse Meters are available in different units of measure (marked on the aluminum
-
located at the outlet of the Impulse
3 is for oil
inlet of the
by disabling the
r a
instruction sheet inc
housing of the meter). This System uses 10 Pulse per Unit Meters; the units of measure (1066
Liters, 1062-Pints, 1061-Quarts, 1059-Gallons) are determined by the model number of the meter
– use the correct meter for the units desired for the System.
Ì
CAUTION:
Do not use regular Impulse Meters on water-based fluid; contact the factory for
special internally coated meters for use with Windshield Wash Fluid and Anti-Freeze.
The Thermal Relief Valve (Adjustable Pressure Relief Valve) is
Meter. Use the instruction sheet included with the valve for correct installation.
Ì
CAUTION:
There are two different versions of the Thermal Relief Valve; Model 106
products (0-900PSI), and Model 1070 is for water base products (0-250PSI).
The optional Air Solenoid is installed between the Air /Filter Regulator and the air
pump. Use the instruction sheet included with the Model 1064 Air/Water Solenoid for correct
installation. The Air Solenoid is optional, it provides an added level of security
pump when there are no dispenses authorized. It also provides an added level of safety by
disabling the pump when dispenses are not authorized - in the event of a product line break o
component failure the pump will not empty the tank onto the floor.
Y-Strainers are located at each dispense point (Station) immediately upstream of the Fluid
Solenoid. Use the instruction sheet included with the Model 1069 Y-Strainer for correct
installation.
1060
4