42 | SAMLEX AMERICA INC.
SCC-30AB is very rugged and designed for the most extreme operating conditions.
Most PV system problems will be caused by connections,Voltage drops, and loads.
Troubleshooting the SCC-30AB controller is simple. Some basic troubleshooting
procedures are listed below.
DISPLAY
FAULT
LED
DESCRIPTION
CAUSE OF FAULT / REMEDY
Alarm: OC
Over Current
Steady
Red
Over
Current
Input current exceeds 150% of the rated
current of 30A i.e. 45A
Alarm: OT
Blinking
Red
Heat Sink over
Temperature
Heat sink temperature exceeds 90ºC
Auto-reset at 70
°
C
Alarm: CPF00
Link Master Error
Steady
Red
Display Panel
Error
The CPU is not able to exchange data
with the Display Panel
Alarm: CPF00
Link Master Error
Display is dim or
OFF
OFF
Display Panel
Error
1. The CPU is not able to exchange
data with the Display Panel.
2. Battery voltage is below 7V
±
0.2V
Auto-reset at 10V and above.
Alarm: CPF04
DC / DC
Low Volt
Steady
Red
Low
Voltage
1. Low Battery Voltage:
< 9V for 12V Battery
< 18V for 24V Battery
2. If this symptom is for a 12V Battery
System, check & ensure that DIP
Switch 1 at the back of the unit is
selected for 12V battery and not
for 24V battery.
Auto-reset at 10V and above
Alarm: CPF09
Heat Sink SR
Open
Steady
Red
Low Operating
Temperature
Operating temperature is below -20ºC
(-4ºF). Ensure operating temperature is
above -20ºC (-4ºF).
Table 7.1. Fault Indications & Remedies
SYMPTOM 1. BATTERY IS NOT CHARGING
• Check the Status LED. This should be ON if it is daytime.
• Check that proper Battery Charging Algorithm (Program) has been selected by
DIP Switches 2, 3, 4 (Table 6.3).
• Check that all wire connections in the system are correct and tight. Check the
polarity (+ and –) of the connections.
SECTION 7 |
Troubleshooting