The DC input circuit is required to handle very large DC currents and hence, the size of
the cables and connectors should be selected to ensure minimum voltage drop between the
battery and the inverter. Thinner cables and loose connections will result in poor inverter
performance and will produce abnormal heating leading to risk of insulation melt down
and fire.

Use oil resistant, multi-stranded copper wire cables rated at 90 º C minimum. Do not use
aluminium cable as it has higher resistance per unit length. Cables can be bought at a
marine / welding supply store

The cables from the battery to the inverter should be protected by a suitable, very fast
acting DC fuse. Use a DC fuse of the appropriate capacity in line with the positive cable.
The fuse should be within 18” from the battery. 

Type ANN fuses with Fuse Block 4164 made

by Bussmann are recommended.

The following size of cables and fuses are recommended. The distance shown is the
distance between the battery and the inverter. The recommended size of the cables will
limit the voltage drop to approximately 2% ( The length of the cable for calculating the
voltage drop has been taken as 2 times the distance between the inverter and the battery
assuming that two ( one positive and one negative)cables are used for the connection )

Distance up to 4'

Distance up to 6’

Ampere rating of battery fuse

PST-150S-12A        AWG # 1/0

AWG # 2/0

300A (ANN 300)

PST-150S-24A        AWG # 3

AWG # 2

150 A (ANN 150)

CAUTION!

The input section of the inverter has large value capacitors connected across
the input terminals. As soon as the DC input connection loop ( B

Y

Y

Y

Y

Y

fuse 

Y

Y

Y

Y

Y

 in

 Y

 Y

 Y

 Y

 Y

inverter - 

Y

Y

Y

Y

Y

battery negative) is completed, these

capacitors will start charging and will momentarily draw very heavy current
that will produce sparking on the last contact in the input loop even when the
on / off switch on the inverter is in the off position. Ensure that the fuse is
inserted only after all the connections in the loop have been completed so that
the sparking is limited to the fuse area.

Using proper DC cable termination

The battery end and the inverter end of the cables should have proper terminals that will
ensure a firm and tight connection.

DC input terminals

The DC input terminals have a tubular hole with a set screw. A suitable pin type of copper
terminal should, therefore, be used on the cable end. 

Do not insert the stranded bare end of

the cable directly into the tubular hole as the set screw will not pinch all the strands and will
thus make only a partial and loose contact

For thicker cables, a suitable adapter with pin

type of termination should be used.

 

There should be no stray wire strands protruding from

the terminals as these may produce a short circuit due to the close vicinity of the plus and
minus terminals.

A pair of pin type of terminal has been provided. Crimp these terminals on the inverter end
of the cable. The terminal can accept up to AWG # 1/0

Summary of Contents for PST-150S-12A

Page 1: ...Owner s Manual Please read this manual before operating your Inverter DC AC Inverters PST 150S 12A PST 150S 24A...

Page 2: ...ion and Grounding 9 10 11 Limiting Electromagnetic Interference EMI 11 Powering direct embedded SMPS 12 Principle of Operation 13 Layout 13 Specifying Batteries Chargers and Alternators 14 15 16 17 18...

Page 3: ...s To ensure proper ventilation do not install in a low clearance compartment Preventing fire and explosion hazards Working with the inverter may produce arcs or sparks Thus the inverter should not be...

Page 4: ...transformer isolated or auto transformer of suitable wattage rating 25 more than the wattage rating of the inverter with primary of 120 VAC and secondary of 120 240 VAC Two 120 VAC split phases 180 d...

Page 5: ...ble for use in buildings including homes for recreational vehicles boats and portable applications Will it be connected to the utility grid in some way Electrical conventions and safety standards diff...

Page 6: ...ter will further limit its ability to start a motor A battery bank that is undersized in poor condition or has corroded connections can be a weak link in the power chain The inverter cables and the ba...

Page 7: ...VAC To obtain 240 VAC from a 120 VAC inverter use a 120 VAC to 240 VAC transformer If you do not already have a pump installed you can get a 120 volt pump if you don t need more than 1 2 HP Idle powe...

Page 8: ...for resistive type of loads that have unity 1 Power Factor In a reactive type of load like electric motor driven loads fluorescent lights computers audio video equipment etc the phase of the sine wav...

Page 9: ...wave form is a sine wave with very low harmonic distortion and clean power like utility supplied electricity Inductive loads like microwaves and motors run faster quieter and cooler Reduces audible an...

Page 10: ...ted to earth Examples are the neutral conductor in AC wiring and the negative conductor in many DC systems A grounded system is a system in which one of the current carrying conductors is grounded An...

Page 11: ...to the AC power source The plug of the power cord has three pins two flat pins also called poles that are connected to the two current carrying conductors and a round pin which is connected to a non...

Page 12: ...be tight against bare metal Use star washers to penetrate paint and corrosion The inverter contains internal switching devices which generate conducted and radiated electromagnetic interference EMI T...

Page 13: ...f up to 4 This will mean that for a particular rated RMS current applicable for a linear load the general purpose SMPS will draw much larger peak currents approx up to 4 times more than its rated RMS...

Page 14: ...again using PWM technique This is done by using a special wave shaping technique where the high voltage DC is switched at a high frequency and the pulse width of this switching is modulated with resp...

Page 15: ...of deep cycle lead acid batteries wet and sealed A wet cell battery has a high tolerance to overcharg ing However it will release hydrogen gas when charging that must be properly vented and the water...

Page 16: ...is not linear but is more or less according to the table below Table 1 Battery Capacity versus Rate of Discharge Hours of Discharge Usable Capacity 20 100 10 87 8 83 6 75 5 70 3 60 2 50 1 40 Using th...

Page 17: ...l connection of batteries When two or more batteries are connected in series their voltages add up but their AH capacity remains the same For example when two 12 V 105 AH batteries are connected in se...

Page 18: ...by multiplying 120 VAC by the AC current in Amperes The next step is to derive the DC current in Amperes A from the AC watts as per formulae 2 above An example of this calculation for a 12V inverter i...

Page 19: ...LI and the auxiliary deep cycle batteries the output from the alternator should be fed to these two sets of batteries through a battery isolator of appropriate capacity The battery isolator is a solid...

Page 20: ...dry environment Do not expose to moisture rain snow or liquids of any type To reduce the risk of overheating and fire do not obstruct the suction and discharge openings of the cooling fans To ensure p...

Page 21: ...Please observe the following precautions Ensure that the maximum charging voltage of the battery charger alternator solar charge controller is below 16 5 VDC for PST 150S 12A or 33 VDC for PST 150S 24...

Page 22: ...2A AWG 1 0 AWG 2 0 300A ANN 300 PST 150S 24A AWG 3 AWG 2 150 A ANN 150 CAUTION The input section of the inverter has large value capacitors connected across the input terminals As soon as the DC input...

Page 23: ...rter and this panel is also required to be powered from additional alternate AC sources the AC power from all the AC sources like the utility generator inverter should first be fed to a manual selecto...

Page 24: ...njured burned severely shocked or electrocuted A GFCI protects people from electric shock by detecting leakage and cutting off the AC source The AC output to the 3 NEMA 5 15R receptacles is fed throug...

Page 25: ...ircuit will still be alive even when the switch is in the off position Hence disconnect the DC and AC sides before working on any circuits connected to the inverter When the inverter is switched on th...

Page 26: ...provided with protections detailed below Low DC input voltage warning alarm The voltage at the DC input terminals will be lower than the voltage at the battery terminals due to the voltage drop in th...

Page 27: ...ature inside the unit will increase The temperature of a critical hot spot inside the inverter is monitored and at a particular upper limit the AC output of the inverter is shut down temporarily The r...

Page 28: ...3 Check that all connections in the battery input circuit are tight Visibly check the fuse element if it is blown The fuses are soldered and are not easily replaceable CallTechnical Support for repair...

Page 29: ...e load completely the unit has become defective Call Technical support 1 Check for ground fault in the load circuit A ground fault will cause a minor shock on touching Note In both the cases the unit...

Page 30: ...be delivered to such type of loads will reduce by this factor See page 7 for details Low Input Voltage Warning Alarm 10 7 V 21 4 V Low Input Voltage Shut down 10 V 20 V High Input Voltage Shut down 1...

Page 31: ...attempt to remedy the defect by anyone other than the Warrantor shall render this warranty void There shall be no warranty for defects or damages caused by faulty installation or hook up abuse or mis...

Page 32: ...110 17 Fawcett Rd Coquitlam B C Canada V3K 6V2 T 604 525 3836 F 604 525 5221 e mail samlex samlexamerica com website www samlexamerica com Version PST 150S 12A_24A July2005...

Reviews: