38 | SAMLEX AMERICA INC.
seCtIOn 9 |
Installation
when using the inverter in a building , connect a #8 Awg insulated stranded copper
wire from the above equipment grounding bolt to the earth ground connection (a con-
nection that connects to the ground rod or to the water pipe or to another connection
that is solidly bonded to the earth ground). The connections must be tight against bare
metal. use star washers to penetrate paint and corrosion.
when using the inverter in a mobile rV, connect a #8 Awg insulated stranded copper
wire from the above equipment grounding bolt to the appropriate ground bus of the
rV (usually the vehicle chassis or a dedicated dc ground bus). The connections must be
tight against bare metal. use star washers to penetrate paint and corrosion.
Grounding of PSe-12275A to earth or to other Designated Ground
Please see details regarding grounding under “Ac Power distribution and grounding”
on page 10. In case of hard wiring of the PSE-12275A to a building’s service entrance /
electrical breaker panel / load center, proper grounding and bonding have to be under-
taken as per the applicable national / local electrical codes. In such cases, the electrical
installation should be undertaken by a qualified electrician.
when the Ac output is fed through nEMA5-15r outlet, connect #8 Awg insulated
stranded copper wire from the equipment grounding bolt (j, fig 7.2) to the earth
ground connection (a connection that connects to the ground rod or to the water pipe
or to another connection that is solidly bonded to the earth ground). The connections
must be tight against bare metal. use star washers to penetrate paint and corrosion.
when using these inverters in a mobile rV, connect a #8 Awg insulated stranded copper
wire from the equipment grounding bolt (j, fig 7.2) to the appropriate ground bus of
the rV (usually the vehicle chassis or a dedicated dc ground bus). The connections must
be tight against bare metal. use star washers to penetrate paint and corrosion.