GRoUnDinG oF PSe-12275A to eARtH oR to otHeR DeSiGnAteD GRoUnD
In case of hard wiring of the PSE-12275A inverter to a building’s service entrance /electri-
cal breaker panel / load center, proper grounding and bonding have to be undertaken
as per the applicable national / local electrical codes. In such cases, the electrical installa-
tion should be undertaken by a qualified electrician.
when using PSE-12275A independently by connecting the provided plate with
nEMA 5-15r receptacle and breaker to their front panel, it should be grounded as in the
case of PSE-12125A and PSE-12175A i.e. connect an Awg #8 insulated stranded copper
wire from the equipment grounding bolt to the earth ground connection (a connection
that connects to the ground rod or to the water pipe or to another connection that is
solidly bonded to the earth ground). The connections must be tight against bare metal.
use star washers to penetrate paint and corrosion.
when using PSE-12275A in a mobile rV, connect a #8 Awg insulated stranded copper
wire from the equipment grounding bolt to the appropriate ground bus of the rV
(usually the vehicle chassis or a dedicated dc ground bus). The connections must be
tight against bare metal. use star washers to penetrate paint and corrosion.
seCtIOn 4 |
AC Power Distribution & Grounding