The LED will indicate a fault. The BGW will turn on 
again after 1 minute.

Remote off

A switch can be installed between the OFF input and 
the minus (–) to manually disable the BGW output. 
The BGW will shut down immediately when the 
connection is made. The BGW will turn on when  
the connection has been disconnected.

LED

The LED has two functions. One is to indicate the 
BGW’s status. The different stages are explaned in 
the LED STATUS below. The other is to configure/
programme the BGW. This operation is described in 
the section “CONFIGURE/Programming”.

LED STATUS

STAGE EXPLAINED

Led is on.

BGW has enabled 
(switched on) the output.

Two short blinks (then off 
for a longer period).

BGW is disabled because 
the remote off has been 
activated.

One blink (1 second on 
and 1 second off).

Undervoltage or 
overvoltage detected.

Three short blinks (then off 
for a longer period).

BGW has been shut down 
for one minute due to one 
of the following causes: 
Ground loss, temperature 
protection, current 
protection, low output 
voltage.

LED is off.

BGW has been shut down 
due to undervoltage.

CONFIGURE/PROGRAMMING

To enter the configure/programming mode, a 
connection has be made between the CONFIG  
input and the Minus (–). The LED will blink one 
time when the connection has been made for 
approx. 2 seconds. Once this is done, the  
connection has to be disconnected.

The same connection can be made briefly (short) again 
to set the correct position from the programming 
table. The LED will light up as feedback.
At that point, program position #1 is selected.  

The user can briefly (short) make the connection 
again to select programme position #2, etc., etc..

If no connection is made for approx. 4 seconds,  
the LED will display the set state again.  
(Example: programme position #4 is set by a user, 
the LED will blink 4 times)

Two types of settings are available. Positions 1 
through 10 set the undervoltage threshold and reset 
values. Positions 11 and 12 set the overvoltage 
threshold and reset values. These settings must be 
selected individually.

The programmed positions are also retained when 
the battery voltage is disconnected.

PROGRAMMING TABLE

12V

24V

UNDERVOLTAGE (V)

Position

Thres-

hold

Reset

Thres-

hold

Reset

1*

10.5

12

21

24

2

10

11.5

20

23

3

9.5

11.5

19

23

4

11.25

13.25

22.5

26.5

5

11.5

13.8

23

27.6

6

10.5

12.8

21

25.6

7

11.5

12.8

23

25.6

8

11.8

12.8

23.6

25.6

9

12

13

24

26

10

10

13.2

20

26.4

OVERVOLTAGE (V)

Position

Thres-

hold

Reset

Thres-

hold

Reset

11*

16

15.8

32

31.6

12

15.4

15.2

30.8

31.4

* Factory default

Summary of Contents for BGW-200

Page 1: ...Overcurrent protection The current through the BGW is constantly monitored If an excessive current flows through the BGW for too long the BGW will shut down to prevent damage to both the BGW and the c...

Page 2: ...has be made between the CONFIG input and the Minus The LED will blink one time when the connection has been made for approx 2 seconds Once this is done the connection has to be disconnected The same c...

Page 3: ...de De plus la sortie d alarme STATUS indique la pr sence de surtension une fr quence de 1 Hz Cette information est galement communiqu e par la LED Protection contre la surcharge L lectricit qui passe...

Page 4: ...e de programmation il faut tablir un contact entre l entr e de CONFIG et la borne n gative La LED 1 se met clignoter d s qu un contact a t tabli pendant 2 secondes D s que cela se produit le contact d...

Page 5: ...US tambi n indicar con una frecuencia de 1Hz que se ha detectado una sobretensi n Esta informaci n tambi n se indicar por medio del LED Control de sobrecorriente Se mide constantemente la corriente qu...

Page 6: ...GURAR PROGRAMACI N Para iniciar el modo de configurar programaci n debe establecerse una conexi n entre la entrada de CONFIG y el min Una vez se haya establecido la conexi n durante 2 segundos el LED...

Page 7: ...ONS Minimum wire diameter 1 5 mm2 Faston plug 6 3 mm MECHANICAL Mounting hole 4 5 mm Distance between mounting holes centre to centre 1 mm 100 mm Weight 295 g Dimensions H W L 1 mm 39 76 111 mm IP Cod...

Page 8: ...anual 11004 BGW 40 60 1222 Battery Guard Models BGW 40 BGW 60 Please read this manual BEFORE operating the units Owner s Manual 11004 BGW 200 xx23 LOAD BATTERY REMOTE OFF CONFIG FUSE 5A STATUS ALARM F...

Reviews: