SECTION 8 |
Installation
36
8.4.5 Recommended Sizes of Battery Cables and Fuses
Sizes of cables and fuses are shown in table 8.2. Sizing is based on safety
considerations in UL-458, NEC-2014 and ISo -10133. Please refer to “Notes for table
8.2” for details.
TABLE 8.2 RECOMMENDED SIZING OF BATTERY CABLES AND EXTERNAL BATTERY SIDE FUSE
Model No.
Max. cont. DC
input current
A
Max. External
Battery Fuse
Size
Fuse (internal
fuse rating)
Min. Cable
size mm
2
<1.5 meter
Min. Cable
size mm
2
>1.6 - 3 meter
PSI 1000-12
120
150
40A * 4
35
50
PSI 1000-24
60
80
40A * 2
16
25
PSI 1500-12
180
200
30A * 8
50
70
PSI 1500-24
90
100
30A * 4
25
35
PSI 2000-12
240
300
35A * 10
70
95
PSI 2000-24
120
150
35A * 5
35
50
PSI 3000-12
360
400
30A * 16
95
2 * 70
PSI 3000-24
180
200
30A * 8
50
70
8.4.6 DC Input Connection
The DC input terminals for battery connection are M8 threaded rods with nuts.
Use the correct cable size (Table 8.2) and cable lugs.
8.4.7 Reducing RF Interference
Please comply with recommendations given in Section 3 - “Limiting Electromagnetic
Interference”.
8.5 AC SIDE CONNECTIONS
WARNING! Preventing Paralleling of the AC Output
1. The AC output of the inverter cannot be synchronized with another AC
source and hence, it is not suitable for paralleling. The AC output of the
inverter should never be connected directly to an electrical Panelboard
/ Load Center which is also fed from the utility power/ generator. Such a
connection will result in parallel operation and AC power from the utility
/ generator will be fed back into the inverter which will instantly damage
the output section of the inverter and may also pose a fire and safety
hazard. If an electrical Panelboard / Load Center is being fed from the
utility power / generator and the inverter is required to feed this panel