Parameter Name
Values (default in bold)
P02
Heat/Cool
Configuration
For 2 Pipe:
0 = Heat Only
1 = Cool Only
2 = Heat or Cool
Manual changeover
3 = Heat or Cool
Seasonal changeover
(Pipe sensor required)
4 = Heat or Cool with Auxiliary
Heat (Pipe sensor required)
For 4 Pipe:
2 = Heat or Cool
Manual changeover
3 = Heat, Cool or Auto
changeover
4 = Auto changeover only
P03
Pipe Valve
Type
0 = Normally open
1 = Normally closed
P12
External
Sensor Type
0 = External sensor
1 = Zigbee remote sensor
P13
Pipe Sensor
Type
0 = Analog input
1 = Normal open, default mode is Heat
2 = Normal open, default mode is Cool
3 = Normal close, default mode is Heat
4 = Normal close, default mode is Cool