10
Salus
The heating and cooling set points may be set to a limited range to prevent over
heating or under cooling a space to save energy.
•
HEAT MAX SETPT does not appear if EQPT TYP is AC only
•
COOL MIN SETPT does not appear if set to Heat only
HEAT MAX SETPT
28.5
°
C/83
°
F
(default)
Max Heating Set point
20 - 30 ºC in 0.5 º steps
68 - 86 ºF in 1 º steps
COOL MIN SETPT
8
°
C /46
°
F
(default)
Min Cooling Set point
5 - 24ºC in 0.5º steps
41 - 75ºF in 1º steps
When EQPT TYP is HP, HP+EH and HT/AC you can set a DEAD BAND which determines
the number of degrees between where cooling turns Off and heating turns On and
vice-a-versa.
DEAD BAND 1.5
°
C /3
°
F
(default)
Dead band value is used for Auto mode.
1.5 - 5ºC in 0.5ºC steps
3 - 10ºF in 1º steps
The HEAT PROTECT set point creates a limit, above which the heating outputs will be
de-energized regardless of the system configuration. Not displayed if AC only.
HEAT PROTECT --
(default)
= Off
Heat Protect Setpoint
30 - 35ºC in 0.5 º steps
86 - 95 ºF in 1º steps