Faults
Causes
Remedy
Display shows a
current temperature
which is much higher
than the set minimum
temperature
The temperature on the
heat generator is too high
compared to the set minimum
temperature on the pump
Adjust the settings of the heat
generator and pump to match
The set minimum flow has
priority over the set minimum
temperature and is preventing
the pump from running more
slowly
Check the set minimum flow
Pump is not
maintaining the set
minimum flow
The piping is partially or
completely blocked
Open valves in the piping
Piping is undersized
Change piping design
Taps opened
Close taps and check if the pump
reaches the minimum flow then
Cold water flowing into the
circulation pipe
Install non-return valves
Pump not
detecting thermal
disinfection
The pump’s selflearning phase
(24 hours of uninterrupted
operation) was not observed
Activate thermal disinfection and
observe the self-learning phase