10 Faults, causes and remedies
Only have faults rectified by qualified personnel! Follow the safety instructions in
9
• Observe the installation and operating instructions of the unit and the accessories!
• If the operating fault cannot be remedied, please contact your specialist technician or
Salmson Service or the closest Salmson representative.
1)
To remedy faults on parts which are under pressure, depressurise these first (vent the non-return valve and
drain the tank, with diaphragm hand pump if necessary).
2)
Further inquiry required
Faults
Identifier: Cause and remedy
The pump doesn't pump properly
1,6, 7, 8, 9, 10, 11, 15, 16, 17
Volume flow too low
1, 2, 3, 7, 8, 11, 12, 13
Current consumption too high
1, 2, 4, 5, 7, 13
Delivery head too small
1, 2, 3, 5, 8, 11, 12, 13, 16
Pump runs roughly/loud noise
1, 2, 3, 9, 12, 13, 14, 16
Cause
Remedy
1)
1
Pump inlet or impeller clogged
• Remove deposits in the pump and/or tank
2
Incorrect direction of rotation
• Exchange the 2 phases of the current feed
3
Wear of inner parts (impeller, bearing)
• Replace worn parts
4
Operating voltage too low
5
Running on two phases (only in the case of 3~ version)
• Exchange defective fuse
• Check line connections
6
Motor is not running since no voltage available
• Check the electric installation
7
Motor winding or electric line defective
2)
8
Non-return valve clogged
• Clean non-return valve
9
Water level dropped too low in the tank
• Check/exchange the level monitor
10
Level monitor defective
• Check the level monitor
11
Slide valve in the pressure pipe is not or insufficiently open
• Open the slide valve completely
12
Impermissible amount of air or gas in the fluid
2)
13
Radial bearing in the motor defective
2)
14
Unit-related vibrations
• Check pipes to make sure they have a flexible connection
15
Temperature monitor for winding monitoring switched off due to excessive winding temperature
• After cooling off, the motor switched back on automatically.
16
Pump ventilation clogged
• Clean the ventilation line
17
Thermal overcurrent monitor triggered
• Reset the overcurrent monitor in the switchgear