Salicru SLC TWIN PRO2 User Manual Download Page 17

17

accordance with the Regulations or standards of the 

country, in order to avoid dropping voltages.

 

ˆ

In the own documentation and for each configuration, 

it is available the information for «N» equipments in 

parallel, as well as the features of the «Backfeed pro-

tection».

 

In parallel systems, the length and cross cable sec-

tion that connect the switchgear or manual bypass 

panel with each UPS must be the same for all of them, with 

no exception.

 

The cross cable section must be always according to the size 

of the own terminals of the switches, in such way that the 

wire is embraced properly, in order to guarantee an optimal 

contact between both parts.

 

The data in the nameplate of the equipment states the 

nominal current only, as the safety standard EN-IEC 

62040-1 states. To calculate the input current, it has been 

considered the power factor and the own efficiency of the 

equipment.

The overload conditions are considered as a non-perma-

nent and exceptional operating mode, so it will not be kept 

in mind when sizing the protections. Do not connect devices 

to the UPS terminals or outlets that could overload it, like 

motors.

 

TWIN/3 PRO2 models (three phase input and single 

phase output), the input current of R phase and Neutral 

is higher than the other two lines/phases when the UPS 

works on bypass mode (loads supplied from mains directly). Pay 

attention to the nameplate data to size the two corresponding 

cables.

 

In case of adding peripheral parts at the UPS or parallel 

system input or output, like transformers or autotrans-

formers, the stated currents in their own nameplates 

must be also considered, in order to use the suitable cross 

cable section, by respecting the Local and/or National Low 

Voltage Electrotechnical Regulation.

 

When a UPS or parallel system, as standard, as an option 

or installed by yourself, at the input line or at the output or 

in both, include a galvanic isolation transformer, a Residual 

Current Device must be installed at its output, in order to 

protect against electrical shocks and indirect contacts,  be-

cause its intrinsic feature of isolation will prevent the trip-

ping of the protections fitted in the primary winding of  the 

transformer.

 

As a reminder, all the isolation transformers installed or 

supplied from factory has the output neutral connected to 

the protective earth by means of a cable bridge between 

the neutral and PE terminals. In case of requiring an iso-

lated output neutral, remove this cable bridge, by taking 

the stated cautions in the local and/or national low voltage 

regulations.

 

This equipment is ready to be installed in grids with 

power distribution systems TT, TN-S, TN-C or IT, 

keeping in mind the particular features of each neutral re-

gime and the electrical regulations of the destination 

country.

 

The switches, RCD and circuit breaker of a three phase input 

equipment connected to an IT power distribution system 

must break the NEUTRAL apart from the three phases.

 

TWIN PRO2 has a terminal strip to install an external emer-

gency power off button -EPO-. Only one device has to be 

fitted in, in order to break the energy to the loads in any 

operating mode.

5.1.5.5.  Preliminary considerations for batteries and their 

protections before connecting the equipment.

 

All the standard UPSs include batteries in the same enclo-

sure, less those models called B0 and B1. For the standard 

UPSs, the battery protection is done by internal fuses and 

they are not accessible by the end-user.

Also, the battery modules have protection and in this case they 

are doubled. Once are internal by means of fuses and not ac-

cessible by the end-user and the second ones by means of a 

two poles circuit breaker or fuses.

 

IMPORTANT FOR THE SAFETY: In case of installing the 

batteries by yourself, the battery set must have a two 

poles circuit breaker or fuses switch, with the size stated in 

Tab. 2.

 

Inside the battery module there are DANGEROUS VOLT-

AGES with the risk of electrical shock it involves, so it is 

classified as RESTRICTED ACCESS AREA.

 

Do not handle the battery fuse holder or circuit breaker 

switch when the equipment is turned ON. These 

switches 

cannot be  turned ON/OFF with load

.

 

When the power supply to the equipment or parallel 

system is broken and it is foreseen an out of service of 

the equipment for long time, the equipment must be shutdown 

completely.

 

The battery circuit is not isolated from the input 

voltage. So, dangerous voltages can be found be-

tween the battery terminals and the earth. Check that there 

is not any kind of voltage, before doing any action over the 

terminals.

5.1.5.6.  Connection parts.

 

Any electrical connection of the equipment is done through 

the rear side of the equipment:

 

ˆ

Input and output connection terminals. Remove the 

fixing screws of the protection cover and the own cover,  

to have access to the terminals.

 

ˆ

Connect the UPS with the battery modules. Depending 

on the power rate of the UPS, it has a connector or ter-

minals.

 

Equipment and battery module with connector. Re-

move the screws and the «BATTERY CONNECTOR» 

cover. These covers will not be put back again,  

keep them.

 

Equipment with battery terminals. They are beside 

the AC power terminals.

 

Battery module with terminals. Remove the screws 

and protection cover.

 

ˆ

Communication connectors:

 

DB9 type for RS232.

 

USB type for communication as a peripheral.

 

Digital input and output.

 

Terminal strip for external EPO button.

 

Auxiliary contact for manual bypass switch.

 

ˆ

Control connections for parallel systems, by DB15 connec-

tors and analogical signal for current sharing. Remove the 

screws and the protection cover to have access to them.

SLC TWIN PRO2

 UNINTERRUPTIBLE POWER SUPPLY (UPS)

USER'S MANUAL        

Summary of Contents for SLC TWIN PRO2

Page 1: ...SLC TWIN PRO2 4 20 kVA UNINTERRUPTIBLE POWER SUPPLY UPS USER S MANUAL...

Page 2: ...nparts 5 2 CONNECTION 5 2 1 ConnectionoftheinputterminalstoACpowersupply 5 2 2 Connectionofload stotheoutputterminalsoroutput1 5 2 3 Connection of the load s to the output terminals 2 TWIN 3 PRO2from8...

Page 3: ...5 OPERATINGMODES STATUSDESCRIPTION 7 6 WARNINGCODES 7 7 ERROROFAULTCODES 7 8 WARNINGINDICATORS 8 MAINTENANCE WARRANTY AND SERVICE 8 1 BATTERYMAINTENANCE 8 1 1 Notestoreplaceandinstallthebatteries 8 2...

Page 4: ...sonnel exclusively Although we have made every effort to guarantee a com plete and accurate information in this user s manual we are not responsible for any errors or omissions that may exist The imag...

Page 5: ...er s manual allows the end user to make any operating of both installation and commissioning in an easy and ordered way without doubt Finally once the equipment is commissioned and in operation it is...

Page 6: ...ADVERTENCIA SLC TWIN PRO2 4 20 kVA This is a category C3 UPS product This is a product for commercial and industrial application in the second environment installation re strictions or additional mea...

Page 7: ...ent will always prevail In the nameplate of the equipment the most important parameters and features can be checked Proceed with the installation accordingly StandardandB1 from4to10kVA Singlephaseinpu...

Page 8: ...rent sharing signal under the cover Smart Slot Bat connector cover Battery connector StandardandB1 from8to10kVA Threephaseinputandsinglephaseoutput Digital input output RS232 USB EPO Manual bypass scr...

Page 9: ...protection Battery module size 1 with 3x20 batteries and 50 A protection Battery fuses Terminal cover IEC inlet for AC power supply Terminal cover Battery switch Protection breaker Battery module siz...

Page 10: ...10 SALICRU Battery switch Terminal cover Battery module size 2 with 4x20 batteries and 100 A protection Fig 3 Rear view of the battery module...

Page 11: ...ording to Salicru s code 3 Quantity of batteries in one string 2x Quantity of strings in parallel Omitted for only one 0 Battery module with no batteries but with the needed accessories to fit them in...

Page 12: ...to the worst conditions of input mains Wide input voltage range frequency range and wave shape so it is avoided the excessive use of the battery which has limited energy Available battery charger up...

Page 13: ...r which is ac cepted by the main manufacturers of software and hardware The connection of the UPS with the SNMP is internal mean while the connection between the SNMP and the IT network is done by mea...

Page 14: ...otect it against pos sible mechanical impacts dust dirt etc The equipment packaging has wooden pallet cardboard or wooden enclosure depending on the requirements ex panded polystyrene corners plastic...

Page 15: ...e distances as the same UPS enclosure It is recommended to leave 75 cm additional free in each side for the possible tasks of the T S S or the needed power cable length to facilitate the movement of t...

Page 16: ...hes which are only available in some models or equipments with extended back up times Ignore those operations related with your unit in case it does not have them Regarding the installation instructio...

Page 17: ...lectrical regulations of the destination country The switches RCD and circuit breaker of a three phase input equipment connected to an IT power distribution system must break the NEUTRAL apart from th...

Page 18: ...f the stated one in the UPS namopete 3 Relay for power contactor power supply 2 with 400V AC coil and NO contact type of 5A 1A minimum For parallel systems each equipment must have its own Backfeed pr...

Page 19: ...mportant to pay attention to the following consideration Bonding PE stud U output phase Output neutral Main PE stud Input neutral R phase input Bonding PE stud U phase output 1 Output neutral 1 U phas...

Page 20: ...lso the battery modules have protection and in this case they are doubled Once are internal by means of fuses and not ac cessible by the end user and the second ones by means of a two poles circuit br...

Page 21: ...lly closed NC so it will open the electrical circuit when pressing it By means of the communication software the inverse func tion can be set Less particular cases it is better to not use this type of...

Page 22: ...ructure N means the minimum quantity of equipments that the total load needs X means the quantity of redundant equipments that is to say the quantity of faulty UPSs that the system can allow at the sa...

Page 23: ...both ports RS232 and USB at the same time Tab 4 shows the pin out of the RS232 signal in the DB9 female connector The RS232 is a serial data port so an important amount of information can be sent thro...

Page 24: ...the risk of a long power outage for the first operating hours must be evaluated because the back up time of the UPS will be lower Do not start up the equipment and loads before section 6 states it Ne...

Page 25: ...After a few seconds the UPS will be on Battery mode so it has to be considered their charge level the remaining back up time and the risk that means to operate on this operating mode If the AC mains i...

Page 26: ...allel system again 6 4 PARALLEL SYSTEM OPERATING To operate with parallel systems in order to avoid prob lems check that the output 2 of each UPS is set to the same parameter in all of them The operat...

Page 27: ...ear panel to On Turn the input circuit breaker switches from each UPS to On Turn the internal manual bypass switch of each UPS to UPS position The output switches of each UPS from switchgear panel mus...

Page 28: ...erating mode as Frequency Converter With this operating mode the static bypass is disabled Tab 5 Control panel keypad functions The UPS has a control panel which has the following parts Four buttons w...

Page 29: ...onnected at the output in by means of four segments which are equivalent to the following proportion 0 25 26 50 51 75 and 76 100 Information of the programmable outputs P1 It indicates that the progra...

Page 30: ...e R R Phase R S S Phase S T T Phase T Tab 9 Abbreviations shown in the LCD 7 4 SETTINGS IN THE LCD CONTROL PANEL Parameter 1 Parameter 2 Parameter 3 Fig 28 Parameter layout in the LCD panel Parameter...

Page 31: ...MOD BAT setting YES Output voltage setting SI 18 Battery capacity and quantity of strings setting SI 19 Back up time setting SI Tab 10 Code list for parameter 1 Description and setting depending on th...

Page 32: ...Code 04 TWIN PRO2 TWIN 3 PRO2 Bypass frequency range Fig 33 Parameter 2 setting Minimum limit of the acceptable input frequency range When the nominal frequency is 50 Hz the setting range is from 46 t...

Page 33: ...fting Bypass shifting is understood as that one that the end users make it over the own UPS I e when pressing the OFF key at the front of the equipment when it is on normal mode then the load is shift...

Page 34: ...11 2 to 13 6 V If the battery voltage is lower than the entered figure the program mable output will be shutdown The preset factory figure is 11 2 V Code 12 TWIN PRO2 Hot standby function enable dis...

Page 35: ...e is from 0 to 9 9 V and the preset factory figure is 0 V Code 15 TWIN 3 PRO2 Inverter voltage setting Fig 49 Parameter 2 setting Select Add or Sub to set the inverter voltage Parameter 3 setting The...

Page 36: ...Parameter 2 setting It allows setting the battery capacity Parameter 3 setting It allows setting the MOD BAT quantity Code 19 TWIN 3 PRO2 Back up time setting Fig 54 Parameter 3 setting It allows sett...

Page 37: ...e inverter on or when shutdown it The UPS does not supply output voltage The acoustic alarm beeps every two minutes TWIN 3 TWIN AC mode Description If the input voltage is inside the range the UPS wil...

Page 38: ...me which will depend on their capacity also the acoustic alarm beeps every 4 sec TWIN 3 TWIN Bypass mode Description When the input voltage is inside the preset range and the bypass is enabled when th...

Page 39: ...n error or fault the inverter will be blocked And the fault code will be displayed in the LCD panel and the icon will light Table 13 shows the error or fault codes and their description TWIN 3 TWIN Ta...

Page 40: ...rvoltage 03 DC bus undervoltage 04 Unbalanced DC bus 06 Converter overcurrent 11 Inverter soft start fault 12 High inverter voltage 13 Low inverter voltage 14 Inverter output short circuited 1A Negati...

Page 41: ...layed in the LCD panel Try to solve the problems by following the steps described in table 15 If the problem persists consult with our Technical Ser vice and Support T S S When necessary contact with...

Page 42: ...rature is very high Check the fans and contact with the distributor Tab 15 Troubleshooting guide 8 3 WARRANTY CONDITIONS 8 3 1 Warranty terms The warranty conditions for this product can be found in o...

Page 43: ...1 Voltage THD with linear load 1 2 Voltage THD with non linear load 4 5 Frequency With mains synchronised with nominal input 46 54 56 64 Hz Freerunning batterymode50 60 0 1Hz Freerunning batterymode50...

Page 44: ...ticamente se trata de la uni n f sica entre la entrada de un dispositivo el ctrico con su salida DC La corriente continua CC en espa ol en ingl s DC de Direct Current es el flujo continuo de electrone...

Page 45: ...in terrumpir la corriente el ctrica de un circuito cuando sta sobrepasa ciertos valores m ximos Modo On Line En referencia a un equipo se dice que est en l nea cuando est conectado al sistema se en c...

Page 46: ...46 SALICRU...

Page 47: ...47 SLC TWIN PRO2 UNINTERRUPTIBLE POWER SUPPLY UPS USER S MANUAL...

Page 48: ...any salicru salicru_SA Product Range Uninterruptible Power Supplies UPS Lighting Flow Dimmer Stabilisers DC Power Systems Static Inverters Photovoltaic Inverters Voltage stabilisers The Technical Serv...

Reviews: