- 24 -
8.5.- Cold start, without commercial mains.
• The cold start up procedure (without commercial mains), is the same as the normal one less for the mains absence, the optical
indications of the control panel, the acoustic ones and the indications of the
(LCD)
panel «BATTERY MODE» .
•
Due to the equipment is blocked by software against an accidental start up during transport, it is not possible to use the
cold start function to the reception of this.
Connect it to the mains and start it up for the first time according to the section 8.2.
8.6.- Complete UPS shutdown.
• Shutdown the loads and press the
(ON/OFF)
key during as minimum 3 seconds, the inverter will be shutdown.
• The
(LCD)
panel will show «SHUTDOWN» during some seconds, after them the
(LCD)
panel will only be lighted and with the
fans and battery charger are still ON.
• Switch «OFF» the outgoing protections, if you have them.
• Switch «OFF» the input
(M1)
and batteries
(M2)
circuit-breakers of the
UPS
. The equipment is completely shutdown.
• Cut the voltage supply to the equipment, by switching «OFF» protections of the distribution board of the input line of the UPS
(earth leakage breaker and circuit-breaker).