Input
R
0
0x00
Supply air temperature sensor value
Real =(value*10)
Speed
Input
R
1
0x01
Actual fan speed
0,1,2,3
T set
Input
R
2
0x02
Actual temperature setting
0-30’C
Heater output Input
R
4
0x04
Heater output
0-100%
(4x....) Holdings Read – 03h, Write – 06h, 10h ( Present value, Unsigned Word )
Speed
Holding_Register R/W
0
0x00
Fan speed setting
0,1,2,3 (0*)
T set
Holding_Register R/W
1
0x01
Supply air temperature set
0-30’C (18*)
time off
Holding_Register
8
0x08
Time to stop ventilator
30-120min.(50*)
SAF Low
Holding_Register R/W
280
0x118
Analog output 0-10V = ( 1speed /10)V
20-SAF Midd (30*)
SAF Midd
Holding_Register R/W
281
0x119
Analog output 0-10V = ( 2speed /10)V
SAF Low – SAF High (60*)
SAF High
Holding_Register R/W
282
0x11A
Analog output 0-10V = ( 3speed /10)V
SAF Midd -100 (100*)
MB addres
Holding_Register R/W
301
0x12D
Active ModBus addres on plate
0-247 (1*)
HeatPI:Kp
Holding_Register R/W
310
0x136
Heating proportional coef.
1-100 (30*) (Kp=X/10)
HeatPI:Ki
Holding_Register R/W
311
0x137
Heating integral coef.
1-200 (6*) (Ki=X/100)
Report SlaveID – 11h ( Present value, Unsigned Char )
R
KE-AE/002/Ver.1.6(ACmotor) KE-EE/002/Ver.1.6
(EC motor)
KE-AE:150318 KE-
EE:150318
LED4
LED2
LED1
N
L
0-10V
Ain
1
GND
GND
L
Tr
af
o
A1
A6
GND
A4
WARNING
The
rm
o traf
o
N
L
Supply
F1
0.
31
5A
25
0V
Filt
er
GN
D
~140Vac
GND
GND
MOTOR
A1(L1) G(L1)
A2(L2)
G(L2) A1(L2)
N
~180Vac
A2(L1)
HIGH VOLTAGE
EKR_KRE_015
X20
X21
X19
LED7
LED6
X22
X23
X24
LED5
TR1
K3
K2
K4
K1
X11
X10
X9
X14
X13
X17
C1
8
X1
C17
C16
X12
X16
X8
F3
LED3
Figure 19.11.1.
LED indications of the controller
RG1 (VEGA E)
Figure 19.11.2.
LED indications of the controller
RG1 (VEGA W)
LED1
Fan speed 1
LED5
Circulation pump On (only VEGA 1100W)
LED2
Fan speed 2
LED5 + LED 6
Electric heater On (only versions with electric heater)
LED3
Fan speed 3
LED7
If flashes 1 time per sec, the device operates er
-
ror-free. If flashes 2 times a sec, error A2 occurred. If
flashes 3times a sec, error A3 occurred, etc.
LED4
Unit On, air damper opening/opened
19.12. LABELING, CHARACTERISTICS OF THE CONTROLLER RG1 AND THE SYSTEM COMPONENTS
Labeling
Description
Output
Characteristics
M2
Supply air damper actuator.
X13: N, L, Supply
Power Supply: 230V AC; Type: ON/OFF.
EAS
External alarm signal (fire).
X1: A1, GND
Signal type: NC - inactive.
TL
Fresh (ambient) air temperature sensor.
X1:
Sensitive element: NTC; Type: duct.
PV
Supply air fan.
Control: 140, 170, 230V.
K1
Fan 1 speed rely
K2
Fan 2 speed rely
K3
Fan 3 speed rely
K4
Air damper control rely
F1
Controller protection
315mA