23. ECODESIGN DATA TABLE

VEGA

350 E

700 E

1100 E

Declared typology

Unidirectional

Unidirectional

Unidirectional

Type of drive

Multi-speed

Multi-speed

Multi-speed

Type of HRS

N/A

N/A

N/A

Nominal NRVU flow rate

[ m

3

/s ]

0,14

0,2

0,29

Effective electric power input

[ kW ]

0,12

0,14

0,24

SFPint

[ W/(m

3

/s) ]

127

121

83

Face velocity

[ m/s ]

1,6

1,81

1,49

Normal external pressure

[ Pa ]

135

150

200

Internal pressure drop of ventilation components

[ Pa ]

37

45

34

Static efficiency of fans used in accordance with Regu

-

lation No 327/2011

[ % ]

29,2

37,2

47,4

Declared maximum external leakage

[ % ]

<1

<1

<1

Casing sound power level (Lwa)

[ dB(A) ]

45

56

56

Energy clasification of the filters

C

C

C

Filter Correction(F)

[Pa]

Description of visual filter warning

timer

timer

timer

ErP Compliance

2018

2018

2018

Internet address for disassembly instructions

www.salda.lt

VEGA

1100 W

Declared typology

Unidirectional

Type of drive

Multi-speed

Type of HRS

N/A

Thermal efficiency of heat recovery

[ % ]

N/A

Nominal NRVU flow rate

[ m

3

/s ]

0,27

Effective electric power input

[ kW ]

0,24

SFPint

[ W/(m

3

/s) ]

81

Face velocity

[ m/s ]

1,4

Normal external pressure

[ Pa ]

200

Internal pressure drop of ventilation components

[ Pa ]

31

Static efficiency of fans used in accordance with Regulation No 327/2011

[ % ]

38

Declared maximum external leakage

[ % ]

<1

Declared maximum internal leakage

[ % ]

-

Energy clasification of the filters

E

Description of visual filter warning

timer

Casing sound power level (Lwa)

[ dB(A) ]

67

ErP Compliance

2018

Internet address for disassembly instructions

www.salda.lt

Summary of Contents for VEGA Series

Page 1: ...VEGA EN MOUNTING AND INSTALLATION INSTRUCTION...

Page 2: ...IC CONTROL 16 19 1 ON OFF AIR SUPPLY UNIT 16 19 2 WEEKLY CALENDAR 16 19 3 FAN CONTROL 16 19 4 ELECTRIC HEATER CONTROL 16 19 5 OPERATION OF VEGA 1100 W WATER HEATER PROTECTION FUNCTION 17 19 6 INFORMAT...

Page 3: ...EN 3 VEGA v2019 06 22 IMPROPER OPERATION AND REPAIR 35 23 ECODESIGN DATA TABLE 36 24 DECLARATION OF CONFIMITY 37 25 WARRANTY 38 25 1 LIMITED WARRANTY COUPON 38...

Page 4: ...ge frequency Max current Max power consumption Protection class Weight xxx xx VAC Hz x xx A x xx kW IP xx xx kg Made in iauliai Lithuania AHU000000 BN xxxxxx 2019 01 01 SERIAL 2514523357 XXX GAMINIO P...

Page 5: ...Fumes Salda Antifrost system uses dis balancing of the air flow and it may cause negative pressure in premises Great care should be taken when using at the same time in premises as another heating app...

Page 6: ...762 protection class IP 44 Total power consumption power current kW A 6 28 16 2 9 28 14 2 15 28 22 85 Insulation of walls mm 30 Color RAL pilka 7040 Automatic control VEGA 1100 W Water heater power kW...

Page 7: ...and 40 C and relative humidity not exceeding 70 It is forbidden to use the units in potentially explosive environment Unit is designed for ventilation and conditioning systems to supply to a room onl...

Page 8: ...to make sure that it it has not been damaged during transportation The installation of damaged units is prohibited Verify that all ordered equipment are delivered before starting the installation Any...

Page 9: ...NG The protective film is intended to protect the unit during transportation It is recommended to remove the film because other wise oxidation signs may occur Before every heating season the condensat...

Page 10: ...omponent depends on model PS PS PS PS Figure 15 2 VEGA E Placement of the component depends on model M CO2 Figure 15 3 Indication for duct connection Figure 15 4 Ventilated premises ODA outdoor air SU...

Page 11: ...DATIONS Operation start up of the unit shall be performed only by trained and qualified personnel The assembly is ready for work after the voltage remote controller selected accessories are connected...

Page 12: ...and wires correspond to all applicable safety and functional requirements diameters etc earthing and protection systems are properly installed condition of all seals and sealing surfaces are proper 17...

Page 13: ...6 1 2 4 3 j d e f g h c a b i 1 2 3 4 5 6 1 2 4 3 j d e f g h c a b i 1 2 3 4 5 6 1 2 4 3 j d e f g h c a b i 1 2 3 4 5 6 1 2 4 3 j 18 3 FILTERS Change the supply air filter after the alert of the co...

Page 14: ...d Ensure that balancing weights of the impeller are in appropriate position Ensure that the casing does not block the impeller Allow the impeller to dry before mounting the fan Mount the fan back to t...

Page 15: ...ion pump to control box for water heater control Three anti frost protections of water heater are used outdoor air sensor return water temperature sensor air flow thermostat behind water heater 1 2 Fi...

Page 16: ...re are any other commands for that period When the remote control panel detects a command it sends speed and temperature settings to the controller Regardless calendar settings the user can manually w...

Page 17: ...plays an error A6 and stops the system 3 OUTPUT FOR EXTERNAL ALARM It is potential free normally closed contacts A1 GND in connection X1 Contacts are for the reception of the signal of an external ala...

Page 18: ...put 1 active 0 passive Fan overheat Coils R 3 0x03 Alarm from A4 input A4 1 active 0 passive LowPower Coils R 5 0x05 Low voltage alarm A7 1 active 0 passive T limit Coils R 8 0x08 Supply air temperatu...

Page 19: ...motor KE AE 150318 KE EE 150318 LED4 LED2 LED1 N L 0 10V Ain1 GND GND L Trafo A1 A6 GND A4 WARNING Thermo trafo N L Supply F1 0 315A 250V Filter GND 140Vac GND GND MOTOR A1 L1 G L1 A2 L2 G L2 A1 L2 N...

Page 20: ...failure Check sensors connections measure sensors resistance should be 10k at 25 C External fault signal Fault signal electric heater manual reset protection to 100 C is active contaminated filters ex...

Page 21: ...1 X24 A1 L1 RG1 EKR KEVer 1 4 Faston 6 3 mm su laikikliu 0 0336369 1 Kondensatorius prijungiamas Saldoje XC1 C1 1 2 XC1 F1 2A ATR1 TK1 TK2 Thermo Trafo RG1 EKR KEVer 1 4 01 2 2 1 2 3 4 5 6 X32 1 48070...

Page 22: ...X1 GND X1 A1 X1 GND X1 A6 X1 GND X1 GND X1 A4 X8 N X10 140VAC X9 170VAC X14 230VAC X16 N X17 L X12 RS485 RS485 RS485 24V RS485 24V X13 N X13 Supply X13 L X11 Motor X19 A2 L1 X20 G X21 A1 L1 X22 A2 L1...

Page 23: ...ting protection 710V13996 manual 100C EK1 heating elements 1200W 230V V1 semistor BTA26 20 3 EH 2 4 1F VEGA 350E DRAWN BY CHECKED BY SIGNATURE DUTIES NAME DATE UAB SALDA Drawi Book CHECKED BY 1 1 2 3...

Page 24: ...EK4 ildymo elemen V1 simistorius BTA26 K1 kontaktorius 20A AC 1 1 2 3 4 5 6 7 8 9 1 480706 0 X29 13 14 11 13 10 11 10 K1 A1 A2 400V AT1 1 2 1 L1 2 T1 3 L2 4 T2 5 L3 6 T3 13 14 K1 1 3 16 K1 1 L1 2 T1...

Page 25: ...ston 6 3 mm su laikikliu 0 0336369 1 Kondensatorius prijungiamas Saldoje XC1 C1 1 2 XC1 F1 2A ATR1 TK1 TK2 Thermo Trafo RG1 EKR KEVer 1 4 01 2 2 1 2 3 4 5 6 X32 1 480705 0 1 2 3 4 5 6 X29 7 8 9 1 4807...

Page 26: ...7 28 X1 0 10V X1 GND X1 Ain1 X1 GND X1 Filter X1 GND X1 A1 X1 GND X1 A6 X1 GND X1 GND X1 A4 X8 N X10 140VAC X9 170VAC X14 230VAC X16 N X17 L X12 RS485 RS485 RS485 24V RS485 24V X13 N X13 Supply X13 L...

Page 27: ...5 07 28 2015 07 28 1 2 3 4 5 6 7 8 9 1 480706 0 X29 1 2 3 4 X3 1 480702 0 1 X2 2 V1 A1 A2 G AT1 1 2 RT1 1 2 Components and cables indicated in dotted line should be connected by the manufacturer or by...

Page 28: ...A1 A2 G 63 22 14 4 3 10 22 21 21 11 1 1 14 EK3 A1 A2 5 3 EK4 A1 A2 5 10 X1 N PE L1 L2 L3 N Components and cables indicated in dotted line should be connected by the manufacturer or by the user EK1 A1...

Page 29: ...8 A1 EK1 A2 A1 EK2 A2 A1 EK3 A2 A1 EK6 A2 A1 EK5 A2 A1 EK4 A2 35 67 66 62 68 45 69 67 73 73 65 29 71 27 30 27 31 30 66 38 39 38 40 35 36 37 29 31 37 40 36 65 39 N L3 L2 L1 PE N X1 Components and cable...

Page 30: ...5 6 7 8 9 1 480706 0 X29 PE PE contact EK2 A1 A2 V2 A1 A2 G 10 18 17 2 4 5 18 15 16 1 1 17 EK3 A1 A2 3 4 EK4 A1 A2 3 6 X1 N PE L1 L2 L3 N Components and cables indicated in dotted line should be conn...

Page 31: ...3 4 5 6 13 14 K1 V 3 A1 A2 G 15 22 16 A1 EK1 A2 A1 EK2 A2 A1 EK3 A2 A1 EK6 A2 A1 EK5 A2 A1 EK4 A2 10 11 2 15 16 19 20 10 24 24 9 3 22 1 2 1 3 4 5 6 5 4 13 12 12 13 6 7 9 11 7 N L3 L2 L1 PE N X1 Compon...

Page 32: ...onents and cables indicated in dotted line should be connected by the manufacturer or by the user 3 4 1 2 3 4 5 6 7 8 9 1 480706 0 X29 1 2 3 4 X3 1 480702 0 L1 L1 L2 L3 X1 N PE N Black 1 Black 2 5 Bla...

Page 33: ...ikos gamintojo XC1 C1 5 uF 1 2 XC1 F1 2A ATR1 TK1 TK2 1 2 3 4 5 6 X32 1 480705 0 85 82 81 80 78 79 69 88 69 18 18 69 16 Components and cables indicated in dotted line should be connected by the manufa...

Page 34: ...RS485 RS485 RS485 24V RS485 24V X27 GND X27 DX24V X13 N X13 L X13 Supply RG1 EKR KW 1 4 119 119 125 124 124 93 93 92 92 X1 24VDC X1 0 10V2 X1 GND RG1 EKR KW 1 4 118 118 0 10 VDC 24VDC SV1 M PE1 107 X1...

Page 35: ...es off Check if voltage and current of the mains correspond to the requirements indicated in the product label Check for power availability to the unit Upon elimination of power supply faults switch o...

Page 36: ...he filters C C C Filter Correction F Pa Description of visual filter warning timer timer timer ErP Compliance 2018 2018 2018 Internet address for disassembly instructions www salda lt VEGA 1100 W Decl...

Page 37: ...T EN 60204 1 2006 Safety of machinery Electrical equipment of machines Part 1 General requirements LST EN 60335 1 2012 Household and similar electrical appliances Safety Part 1 General requirements LS...

Page 38: ...quipment to manufacturer Delivery costs should be covered by customer Manufacturer reserves the right to change this technical passport any time without prior notice if some typographic errors or inac...

Page 39: ...39 VEGA v2019 06...

Page 40: ...NANCE TABLE Product name LOT number Instalation Interval Datum Fan cleaning Once a year Heat exchanger cleaning Once a year Filter replacement Every 3 4 months Look at the product label At least NOTE...

Reviews: