4.3. TECHNICAL DATA
RIS PE 3.0
400
700
1000
1500
Exhaust air fan
phase/voltage
[50 Hz/VAC]
~1, 230
~1, 230
~1, 230
~1, 230
power/current
[kW/A]
0,225/1,1
0,255/1,12
0,286/1,25
0,359/1,57
speed
[min
-1
]
1850
2000
2250
2750
protection class
IP-44
IP-44
IP-44
IP-44
Supply air fan
phase/voltage
[50 Hz/VAC]
~1, 230
~1, 230
~1, 230
~1, 230
power/current
[kW/A]
0,225/1,1
0,225/1,12
0,312/1,36
0,373/1,63
speed
[min
-1
]
1850
2000
2250
2750
protection class
IP-44
IP-44
IP-44
IP-44
Total power consumption
power/current
[kW/A]
3,35/15,24
4,68/20,50
6,6/11,27
9,73/16,19
Heater
phase/voltage
[50 Hz/VAC]
~1, 230
~1, 230
~3, 400
~3, 400
power consumption
[kW]
2,0
3,0
6,0
9,0
Pre-heater for heat exchanger power consumption
[kW]
1,0
1,2
-
-
Automatic control integrated
+
+
+
+
Thermal efficiency
75%
57%
51%
62%
Insulation of walls
[mm]
30
30
50
50
According to EN 13141-7 standard.
4.4. OPERATING CONDITIONS
Maximum extract air temperature
+40°C
Maximum extract air humidity
60%
Minimum supply air temperature
-20%
Maximum supply air humidity
90%
Operating ambient temperature
0...+30°C, humidity 60%