EN |
5
RIS 400-700 P EKO 3.0 v2019.06
Automatic control integrated
+
+
+
+
Thermal efficiency
90%
90%
90%
90%
Insulation of walls
[mm]
30
30
30
30
Cross-section of the power supply cabl
[mm²]
3x1,5
3x1,5
3x2,5
3x1,5
Circuit breaker*
Poles
1
1
1
1
I [A]
B6
B10
C16
Fuse 5A
RIS EKO 3.0
700PE 1.2
700PE 3.0
700PE 4.5
700PW
Heater
- phase/voltage
[50 Hz/VAC]
~1, 230
~1, 230
~3, 400
AVS 250
- power consumption
[kW]
1,2
3,0
4,5
Fans
- phase/voltage
[50 Hz/VAC]
~1, 230
~1, 230
~1, 230
~1, 230
exhaust
- power/current
[kW/A]
0,168/1.4
0,168/1.4
0,168/1.4
0,168/1.4
- speed
[min
-1
]
3230
3230
3230
3230
supply
- power/current
[kW/A]
0,168/1,4
0,168/1,4
0,168/1,4
0,168/1,4
- speed
[min
-1
]
3230
3230
3230
3230
- control input
[VDC]
0-10
0-10
0-10
0-10
- protection class
IP-54
IP-54
IP-54
IP-54
Total power consumption
- power/current
[kW/A]
1,54/8,34
3,34/15,84
4,84/9,34
0,34/2,84
Automatic control integrated
+
+
+
+
Thermal efficiency
90%
90%
90%
90%
Insulation of walls
[mm]
30
30
30
30
Cross-section of the power supply cabl
[mm²]
3x1,5
3x2,5
5x1,5
3x1,5
Circuit breaker*
Poles
1
1
3
1
I [A]
B6
B16
B10
Fuse 5A
6. CONSTRUCTION
10
1 - Plate heat exchanger; 2 - Supply fan; 3 - Exhaust fan; 4 - By-pass
damper
; 5 - Electrical/water heater/pre-heater; 6 - Control board; 7 - Ex-
tract air filters (panel/pocket); 8 - Supply air filter (panel/pocket).