4
| EN
RIS 400-700 P EKO 3.0 v2019.06
Warning!
• If the device is installed in a cold environment, make sure that all connections and tubes are properly isolated. Intake and discharge air
ducts should be isolated in all cases.
• Openings of the ducts should be covered during transportation and installation.
• Make sure not to damage the heater when connecting the piping of the water heater. For tightening up, use a wrench/spanner.
Before starting the equipment
• make sure, that there are no strange objects inside;
• manually check whether fans are not stuck or blocked;
• if rotary heat exchanger is installed in the device, make sure that it is not stuck or blocked;
• check the grounding;
• make sure that all components and accessories are connected in accordance with the project or provided instructions.
Danger: Fumes
Salda Antifrost
system uses dis-balancing of the air flow and it may cause negative pressure in premises. Great care should be taken
when using at the same time in premises as another heating appliance what depend on the air in premises. Such appliances include
gas, oil, wood or coal-fired boilers and heaters, fireplaces, continuous flow or other water heaters, gas hobs, cookers or ovens which
draw air in from the room and duct exhaust gases out through a chimney or extraction ducting. The heating appliance can be starved
of oxygen, impairing combustion. In exceptional cases harmful gases could be drawn out of the chimney or extraction ducting back
into the room. In this case we strictly recommend to turn off
Salda Antifrost
and use an external preheater for heat exchanger anti-frost
protection (see
Salda Antifrost
function on the Remote controller manual).
4. DIMENSIONS AND WEIGHT
L
W
H
D/D1*
d
W1*
W2
d*
L1
L2
H1
L3
D1*
D
L4*
RIS P EKO 3.0
L
L1
L2
L3
L4*
H
H1
W
W1*
W2
øD
øD1*
ød*
ød
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
[mm]
[mm] [mm] [mm] [mm]
400
670
183
183
99
330
148
1300
-
1361
200
-
-
16
700
970
242
242
485
104
358
160
1380
-
1461
250
-
-
16
RIS EKO 3.0
400PE 0.9
400PE 1.6
400PE 3.0
400PW
700PE 1.2
700PE 3.0
700PE 4.5
700PW
[kg]
74
74
74
73
103,5
104
104,5
103
5. ELECTRICAL DATA
RIS EKO 3.0
400PE 0.9
400PE 1.6
400PE 3.0
400PW
Heater
- phase/voltage
[50 Hz/VAC]
~1
~1
~1
AVS 200
- power consumption
[kW]
0,9
1,6
3,0
Fans
- phase/voltage
[50 Hz/VAC]
~1
~1
~1
~1
exhaust
- power/current
[kW/A]
0,085/0,73
0,085/0,73
0,085/0,73
0,085/0,73
- speed
[min
-1
]
3200
3200
3200
3200
supply
- power/current
[kW/A]
0,085/0,73
0,085/0,73
0,085/0,73
0,085/0,73
- speed
[min
-1
]
3200
3200
3200
3200
- control input
[VDC]
0-10
0-10
0-10
0-10
- protection class
IP54
IP54
IP54
IP54
Total power consumption
- power/current
[kW/A]
1,07/5,5
1,77/8,5
3,17/14,5
0,17/1,5