background image

12 

| EN

RIRS 1200-5500 V EKO 3.0 v2019.06

The manufacturer does not assume any liability for personal injuries and property damage due to nonconformance with the 

provided instructions.

17. START-UP RECOMMENDATIONS

17.1.  RECOMMENDATIONS BEFORE THE START OF THE UNIT (BEFORE THE FINAL USER)

Prior to start-up the system must be thoroughly cleaned. Check whether: 

• operation systems and unit elements as well as automation and automation devices were not damaged during installation, 

• all electrical devices are connected to power supply and fit for service, 

• all necessary automation elements are installed and connected to power supply and terminal blocks, 

• cable connection to terminal blocks comply with the existing power connection diagrams, 

• all electrical equipment protection elements are properly connected (if they are additionally used), 

• cables and wires correspond to all applicable safety and functional requirements, diameters, etc., 

• earthing and protection systems are properly installed, 

• condition of all seals and sealing surfaces are proper.

17.2.  POSSIBLE FAULTS AND TROUBLESHOOTING

FAILURE

CAUSE

EXPLANATION / CORRECTIVE ACTIONS

Unit is not operating

No supply voltage

Check whether the device is connected to the

power network

Protection device is off or a current

leakage relay is active (if installed by the 

installer)

Switch on only if the unit condition has been 

evaluated by a qualified electrician. If the sys

-

tem failed, the failure MUST BE rectified prior 

to switching it on.

Air supply heater or pre-heater is not operat-

ing or malfunctioning (if installed)

Too low air flow in air ducts activates auto

-

matic

protection

Check if air filters are not clogged

Check if fans are rotating

Manual protection is activated

Possible heater or unit failure. MUST contact

the servicing staff for failure detection and its

elimination.

Too low air flow at rated fan speed

Clogged supply and/or extract air filter(s)

Filter replacement needed

Filters are clogged and no message is shown

on the remote control

Wrong time in filter timers or their switch is 

broken, or its pressure is set improperly.

Shorten filter timer time till the message of

clogged filters or replace the pressure switch 

of the filters, or set their proper pressure.

18. MAINTENANCE 

Unplug unit from mains first and wait for 2 minutes (till fans fully stop) before opening the covers.

18.1.  FILTERS

Dirt increases air resistance in the filter, therefore less air is supplied into the premises.

- It is advisable to change the filters every 3-4 months, or in accordance with the readings of filter contamination sensor. (Sensor PS 600 is inte

-

grated in the unit).

18.2.  FAN

- Maintenance and repair should only be performed by experienced and trained staff.

- The fan should be inspected and cleaned if needed at least once a year.

- Be sure the fan is disconnected from power source before performing any maintenance or repair.

- Proceed to maintenance and repair after any rotation in the fan stopped.

- Observe staff safety regulations during maintenance and repair.

- The motor is of heavy duty ball bearing construction. The motor is completely sealed and requires no lubrication for the life of the motor.

- Detach fan from the unit (1-2-3).

- Impeller should be specially checked for buil-up material or dirt which may cause an imbalance.  Excessive imbalance can lead to accelerated 

wear on motor bearings and vibration.

- Clean impeller and inside housing with mild detergent, water and damp, soft cloth.

- Do not use high pressure cleaner, abrasives, sharp instruments or caustic solvents that may scratch or damage housing and impeller.

- Do not plunge impeller into any fluid.

- Make sure, that impeller’s balance weights are not moved.

- Make sure the impeller is not hindered.

- Mount the fan back into the unit. Replace fan guards and connect the fan to power supply source (3-2-1).

- If after maintenance or repair the fan does not start either thermal protection contact activates automatically, contact the manufacturer.

- During the maintenance do not hold the fan by the impeller, it might cause disbalance of impeller or damage it. Hold the fan by the casing.

Summary of Contents for RIRS ECO 3.0 Series

Page 1: ...RIRS 1200 5500 V EKO 3 0 EN MOUNTING AND INSTALLATION INSTRUCTION...

Page 2: ...OF THE HVAC UNIT 17 19 5 SYSTEM ADJUSTMENT GUIDELINES 17 20 CONTROL BOARD RG1 19 20 1 LABELING CHARACTERISTICS OF THE CONTROLLER AND THE SYSTEM COMPONENTS 20 20 2 REGULAR SYSTEM CHECK UP 21 21 ELECTRI...

Page 3: ...quency Max current Max power consumption Protection class Weight xxx xx VAC Hz x xx A x xx kW IP xx xx kg Made in iauliai Lithuania AHU000000 BN xxxxxx 2019 01 01 SERIAL 2514523357 XXX GAMINIO PAVADIN...

Page 4: ...ked check the grounding make sure that all components and accessories are connected in accordance with the project or provided instructions Danger Fumes Salda Antifrost system uses dis balancing of th...

Page 5: ...m 50 50 50 50 Cross section of the power supply cable mm 4x2 5 4x2 5 3x1 5 3x1 5 Circuit breaker Poles 2 2 1 1 I A B16 B16 B10 B10 Filter class and dimensions exhaust mm 745x350x46 745x350x46 745x350x...

Page 6: ...er class and dimensions exhaust mm 790x400x46 790x400x46 900x455x90 900x455x90 supply mm 790x400x46 790x400x46 900x455x90 900x455x90 RIS EKO 3 0 5500 VE 5500 VW Heater phase voltage 50 Hz VAC 3 SVS po...

Page 7: ...pocket 9 Rotor engine 7 OPERATING CONDITIONS 5 C o 40 C o 40 C o 40 C o 15 C o 40 C o 3 C o 40 C o 5 C o 40 C o 23 C o 40 C o 15 C o 40 C o 40 C 23 C o O 40 C 15 C O O RH 60 40 C 23 o C O Ex O O 40 C...

Page 8: ...the unit first unpack the accessories Remove the film from the unit Remove the bracing packaging tape which keeps the protective profiles Remove the protective profiles After unpacking the unit examin...

Page 9: ...1 5xL H Min distance to open the door 1 5xL Min distance to open control box door H 400 mm 13 MOUNTING The protective film is intended to protect the unit during transportation It is recommended to re...

Page 10: ...duct conection Figure 14 2 Rectangular air duct conection D2 dimensions depend on unit 15 CONNECTION DIAGRAM PS PS PS PS 2 2 2 2 Figure 15 1 RIRS 1200 1900 VE EKO 3 0 Placement of the component depen...

Page 11: ...ns speed switch BOOST Component posibility to connect it depends on model For more information please check the manual 16 CONNECTION OF THE UNIT TO ELECTRIC NETWORK Supply voltage to the unit must be...

Page 12: ...ters are clogged and no message is shown on the remote control Wrong time in filter timers or their switch is broken or its pressure is set improperly Shorten filter timer time till the message of clo...

Page 13: ...can harm the heat exchanger It is NECESSARY to protect the motor of the heat exchanger from the moisture and liquid while cleaning the heat exchanger CAUTION It is forbidden to use the heat exchanger...

Page 14: ...using the START STOP feature STOP is displayed at the remote control panel FLEX In START mode the recuperator operates based on the latest settings of the panel FanFail and FanRun features It provides...

Page 15: ...rotection is triggered fans operate in maximum capacity until the manual heater protection is reset by pressing the reset button and the device is restarted When heater fault is registered manual heat...

Page 16: ...Read_Coils 10 1 Return water temperature sensor alarm 1 a c t i v e o passive 11 ToutDoor 01h_Read_Coils 11 1 Outside air temperature sensor alarm controller continues to work in determining ToutDoor...

Page 17: ...ted place Install the supplied connection cable FLEX controller between the control panel and the HVAC unit It is recommended to install the control panel separately from the power cables Note If cabl...

Page 18: ...rm input damper actuator damper actuator Extract air Supply air L L control N L control ON OFF ON OFF 230V AC 230V AC 15 20 16 L L N N L 18 17 M3 M2 X16 5 19 L N 17 16 15 14 13 12 11 X16 6 22 21 temp...

Page 19: ...a LED2 Air damper close LED9 Medium fans speed LED2 LED3 Air damper open LED10 Minimal fans speed LED4 Water valve open LED11 Supply air fan speed reducing LED5 Water valve close LED12 Preheater LED6...

Page 20: ...X32 3 HIGH BOOST increase the flow of air I X32 4 COM COM X33 1 TIMER Stop DI X33 2 COM COM M5 Water cooler valve actuator X33 3 VAL Cooling valve opening PWM 24v 50hz AO X33 4 VAL Cooling valve closi...

Page 21: ...ture sensor AI X39 2 COM TE Exhaust air temperature sen sor X41 1 Exhaust air temperature sensor AI X41 2 COM PV Supply air fan X37 1 V1 Supply air fan 0 10V AO X37 2 COM COM IV Extract room s air fan...

Page 22: ...7 18 L N N L L 20 L supply 230V AC 230V AC ON OFF ON OFF L X37 TL N PE L1 1 3 4 2 LOW X32 1 COM X32 4 HIGH X32 2 TIMER X32 3 COM X33 1 MID X33 2 CHIL X33 9 COM X33 10 BOOST STOP NO START NC A2 A1 R1 8...

Page 23: ...3 X38 2 X38 1 28 27 26 X33 24 X33 23 COM T set 26 24V DC 27 intput 0 10V DC 28 GND Transmitter 2 24 VDC P 29 X16 7 30 31 1A 2 1 F3 N L M4 PE 1f 230V AC 32 X16 8 33 34 24VDC 0 10VDC M6 G Y 0 0 GND Y 0...

Page 24: ...24 EN RIRS 1200 5500 V EKO 3 0 v2019 06 21 3 RIRS 1900 VE EKO 3 0...

Page 25: ...EN 25 RIRS 1200 5500 V EKO 3 0 v2019 06 21 4 RIRS 1900 VW EKO 3 0...

Page 26: ...26 EN RIRS 1200 5500 V EKO 3 0 v2019 06 21 5 RIRS 2500 3500 VE V2 4 RHX 0K...

Page 27: ...EN 27 RIRS 1200 5500 V EKO 3 0 v2019 06...

Page 28: ...28 EN RIRS 1200 5500 V EKO 3 0 v2019 06 ModBus RTU...

Page 29: ...EN 29 RIRS 1200 5500 V EKO 3 0 v2019 06 21 6 RIRS 5500 VE V2 4 RHX 0K...

Page 30: ...30 EN RIRS 1200 5500 V EKO 3 0 v2019 06...

Page 31: ...EN 31 RIRS 1200 5500 V EKO 3 0 v2019 06 ModBus RTU...

Page 32: ...32 EN RIRS 1200 5500 V EKO 3 0 v2019 06 21 7 SVR 2500VE 9 3F V2 4 2K...

Page 33: ...EN 33 RIRS 1200 5500 V EKO 3 0 v2019 06 21 8 SVR 3500VE 9 ESKM 0K 3X230...

Page 34: ...34 EN RIRS 1200 5500 V EKO 3 0 v2019 06 21 9 SVR 5500VE 18 3F ESKM 0K...

Page 35: ...EN 35 RIRS 1200 5500 V EKO 3 0 v2019 06 21 10 RIRS 2500VE V2 4 RHX 0K...

Page 36: ...36 EN RIRS 1200 5500 V EKO 3 0 v2019 06...

Page 37: ...EN 37 RIRS 1200 5500 V EKO 3 0 v2019 06 21 11 RIRS 3500VE V2 4 0K RHX 3X230...

Page 38: ...38 EN RIRS 1200 5500 V EKO 3 0 v2019 06...

Page 39: ...EN 39 RIRS 1200 5500 V EKO 3 0 v2019 06 21 12 RIRS 5500VE V2 4 RHX 0K...

Page 40: ...40 EN RIRS 1200 5500 V EKO 3 0 v2019 06...

Page 41: ...EN 41 RIRS 1200 5500 V EKO 3 0 v2019 06 21 13 RIRS 2500 3500 VW V2 4 RHX 0K...

Page 42: ...42 EN RIRS 1200 5500 V EKO 3 0 v2019 06...

Page 43: ...EN 43 RIRS 1200 5500 V EKO 3 0 v2019 06 ModBus RTU...

Page 44: ...44 EN RIRS 1200 5500 V EKO 3 0 v2019 06...

Page 45: ...EN 45 RIRS 1200 5500 V EKO 3 0 v2019 06 21 14 RIRS 5500 VW V2 4 RHX 0K...

Page 46: ...46 EN RIRS 1200 5500 V EKO 3 0 v2019 06...

Page 47: ...EN 47 RIRS 1200 5500 V EKO 3 0 v2019 06 ModBus RTU...

Page 48: ...48 EN RIRS 1200 5500 V EKO 3 0 v2019 06 21 15 RIRS 2500 VW V2 4 RHX 0K...

Page 49: ...EN 49 RIRS 1200 5500 V EKO 3 0 v2019 06...

Page 50: ...50 EN RIRS 1200 5500 V EKO 3 0 v2019 06 21 16 RIRS 3500 VW V2 4 RHX 0K...

Page 51: ...EN 51 RIRS 1200 5500 V EKO 3 0 v2019 06...

Page 52: ...52 EN RIRS 1200 5500 V EKO 3 0 v2019 06 21 17 RIRS 5500 VW V2 4 RHX 0K...

Page 53: ...EN 53 RIRS 1200 5500 V EKO 3 0 v2019 06 21 18 RIRS 2500 VW R3G280 AU06 B1...

Page 54: ...54 EN RIRS 1200 5500 V EKO 3 0 v2019 06 21 19 RIRS 3500 VW RH35C ZID DC 1R 21 20 RIRS 5500 VW R3G 400 AY87 01...

Page 55: ...nerative regenerative regenerative Thermal efficiency of heat recovery 73 73 73 73 Nominal NRVU flow rate m3 s 0 41 0 41 0 41 0 41 Effective electric power input kW 0 83 0 83 0 83 0 83 SFPint W m3 s 7...

Page 56: ...40 2 40 2 42 8 42 8 50 3 50 3 Declared maximum external leakage 1 1 1 1 1 1 Declared maximum internal leakage 3 3 3 3 3 3 Energy clasification of the filters E E E E E E Description of visual filter...

Page 57: ...sk reduction LST EN 60204 1 2006 Safety of machinery Electrical equipment of machines Part 1 General requirements LST EN 60335 1 2012 Household and similar electrical appliances Safety Part 1 General...

Page 58: ...iver the equipment to manufacturer Delivery costs should be covered by customer Manufacturer reserves the right to change this technical passport any time without prior notice if some typographic erro...

Page 59: ...59 RIRS 1200 5500 V EKO 3 0 v2019 06...

Page 60: ...NANCE TABLE Product name LOT number Instalation Interval Datum Fan cleaning Once a year Heat exchanger cleaning Once a year Filter replacement Every 3 4 months Look at the product label At least NOTE...

Reviews: