6
| EN
KF T120_KF T120 EC v2019.04
* Only transmitter Stouch is supported by a pressure transducer S - 1141
KF T120
160-4 L3
180-4 L3
200-4L3
225-4L3
250-4L3
280-4L3
315-4 L3
355-4 L3
400-4 L3
KF T120
TGRT
Frequency Converters
3X400 V
160-4L3
1
ACS380-042S-01A8-4 Pn: 0,55kW, In: 1,8A IP20
180-4L3
2
ACS380-042S-01A8-4 Pn: 0,55kW, In: 1,8A IP20
200-4L3
3
ACS380-042S-01A8-4 Pn: 0,55kW, In: 1,8A IP20
225-4L3
*
1
-
ACS380-042S-03A3-4 Pn: 1,1kW, In: 3,3A IP20
250-4L3
*
1
-
ACS380-042S-05A6-4 Pn: 2,2kW, In: 5,6A IP20
280-4L3
-
ACS380-042S-07A2-4 Pn: 3kW, In: 7,2A IP20
315-4L3
1
ACS380-042S-01A8-4 Pn: 0,55kW, In: 1,8A IP20
355-4L3
2
ACS380-042S-01A8-4 Pn: 0,55kW, In: 1,8A IP20
400-4L3
3
ACS380-042S-01A8-4 Pn: 0,55kW, In: 1,8A IP20
Frequency converter output voltage 3 ~ 400V. With these frequency converters can not ve connected fans with 3 ~ 230V connection.
*
1
Performance operating area is limited. Do not exceed the normal current, additional overload protection is required.
INSTALLATION
TRANSPORTATION AND STORAGE
• All units are packed in the factory to withstand regular conditions of transportation.
• Upon unpacking, check the unit for any damages caused during transportation. It is forbidden to install damaged units!!!
• The package is only for protection purpose!
• While unloading and storing the units, use suitable lifting equipment to avoid damages and injuries. Do not lift units by holding on power supply
cables, connection boxes, air extract or exhaust flanges. Avoid hits and shock overloads. Before installation units must be stored in a dry room
with the relative air humidity not exceeding 70% (at +20 °C) and with the average ambient temperature ranging b5 °C and +30 °C. The
place of storage must be protected against dirt and water.
• The units must be transported to the storage or installation site using forklifts.
• The storage is not recommended for a period longer than one year. In case of storage longer than one year, before the installation it is necessary
to verify whether the bearings of fans and motor rotate easily (turn the impeller by hand) and if the electric circuit insulation is not damaged or the
moisture is accumulated.
• unpacking wear protective gloves.