Space for door opening
L, [mm]
2000
outdoor air
supply air
extract air
exhaust air
H1-R
H1-L
H2-R
H2-L
HV1-R
HV1-L
HV2-R
HV2-L
HV3-R
HV3-L
HV4-R
HV4-L
HV5-R
HV5-L
HV6-R
HV6-L
5.6. CONNECTION OF AIR DUCTS
•
Connected air ducts must be straight and have their own fixing.
• Make sure that the fans can not be accessed through air duct heads. If it is possible to access the fan, protective grid should be installed. You
can choose it in our website.
• Do not reduce the diameter of the piping near air inlet or exhaust ducts. If you want to reduce the speed of air in the system, drop of pressure
and noise level, you can increase the diameter.
• In order to reduce the level of the noise in the air supply system, install silencers (see chapter on their installation).