BURNER FLAME CONTROL

 

 

SERIES

                 

page 6 di 6 

DOUBLE ELECTRODE FLAME DETECTION  
IN ACCORDANCE WITH STANDARD EN 298 

 

  RETIFICATION OF FAULTS                   .

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

  
?           < TROUBLE> 

 !            <CAUSE > 
 *            <REMEDY> 

 
? THE IGNITION SPARK DOES NOT 
APPEAR. 
! The distance between the electrode and 
the burner body is too great. 
* Set a distance of max. 2 mm. 
! The igniter cable does not make contact 
with the pipe. 
* re-screw the pipe tightly. 
! The igniter cable has a leakage on the 
earth. 
* Check the laying of the cable, clean the 
ignition electrode. 
! The ignition voltage is too low. 
* use an ignition transformer with power > 
5 KV 
! The ignition cable is too long. 
* Shorten its length to 1 m. (max. 5 m.) 
! The igniter cable does not make contact.  
* Screw it tightly on the ignition 
transformer. 
? THE GAS DOES NOT REACH IT 
! The gas solenoid valve does not open 
* Check the solenoid valve connection. 
! There is still presence of air in the gas 
hosepipe. 
* Make many ignition attempts in order to 
fill completely the gas hosepipe. 

? THE GAS DOES NOT REACH IT 
AND THE IGNITION SPARK DOES 
NOT APPEAR, THE 

  DOES NOT 

START. 
! Short circuit in the ignition or in the 
solenoid valve outlet. 
* Check the wiring 
-  in case of short circuit in outlets 
eliminate it and change the inner fuse 
(2,5 A). Or send the appliance to the 
manufacturer. 
? THERE IS THE FLAME BUT THE 
DETECTION LED IS OFF. 
! The detection electrode is in short 
circuit because of dirt, soot or damp. 
! The detection electrode is not in a 
correct position as to the flame. 
! The combustion air/gas ratio is 
incorrect. 
! The flame makes no contact with the 
burner body because air and/or gas 
pressure is too high. 
! The burner or 

  are not earthed 

correctly. 
! Short circuit or detection cable 
interruption. 
! Phase and neutral wire inverted. 
* Eliminate the defect. 
? THE APPLIANCE DOES NOT 
PERFORM THE IGNITION CYCLE 
AND GOES IMMEDIATELY 

IN 

DETECTION. 
! Anomaly on the detection  (flame 
simulation) 
* Eliminate the cause of the flame 
anomaly. 
! Anomaly of the flame detection circuit. 
* Send the appliance to the 
manufacturer for its replacement. 
? THE APPLIANCE DOES NOT 
START EVEN IF ALL THE TROUBLES 
HAVE BEEN ELIMINATED AND THE 
MAIN SWITCH HAS BEEN PRESSED. 
* Send the appliance to the 
manufacturer for the functional 
inspection. 

CAUTION!!! 
 
Danger of death due to shocks! 
Before intervening on the appliance cut 
off the tension to any cable. 
 
The elimination of breakdowns can be 
carried out by authorized personnel 
only. 
 
In case of improper repairs or incorrect 
electrical connections, the good 
running of the appliance is not granted. 
 

The release at distance can be carried 
out only by authorized personnel 
keeping under strict control the burner 
to be lighted

 

 

Summary of Contents for CF5Q Series

Page 1: ...Series Automatic burner control unit MONO DOUBLE ELECTRODE UV SENSOR FLAME DETECTION SAITEK srl www saitek it info saitek it Casalgrande RE ITALY Tel 39 0522 848211 Fax 39 0522 849070...

Page 2: ......

Page 3: ...modi cation use ormaintenancethey are not performed correctly they can occur injury or damage Please read the instructions rst to use the product to come installed according to regulations in force i...

Page 4: ...The burner is checked by an ionization electrode For grounded grids With a single restart due to flame put out can be applied directly to the burner in industrial thermal processes for metals glass ce...

Page 5: ...by pressure Dimensions 47 x 123 x 105 mm Prepared for pipe connection collars is not provided already wired otherwise perform the necessary connection on the back by the 16 position connector RECCOMEN...

Page 6: ...contact will close and the red lock LED will light up To reset it and retry the boot it will be necessary to switch it off and switch it on again using the power button N B The terminl box should nev...

Page 7: ...Pre Purge Time setting Pre Purge 5 sec Pre Purge 1 sec Pre Purge 8 sec Pre Purge 10 sec Pre Purge 20 sec Pre Purge 30 sec 1 2 ON 3 4 5 6 7 8 Pre Purge 50 sec 1 2 ON 3 4 5 6 7 8 Pre Purge 70 sec 1 2 ON...

Page 8: ...contents to third parties without authorization is forbidden Saitek Srl reserves the right to modify the present document at any moment without prior notice 04 2018 BURNER FLAME CONTROL SERIES page 5...

Page 9: ...valve outlet Check the wiring in case of short circuit in outlets eliminate it and change the inner fuse 2 5 A Or send the appliance to the manufacturer THERE IS THE FLAME BUT THE DETECTION LED IS OFF...

Page 10: ...contents to third parties without authorization is forbidden Saitek Srl reserves the right to modify the present document at any moment without prior notice AUTOMATIC BURNER CONTROL UNIT SERIES MONO D...

Page 11: ......

Page 12: ...installation up to a maximum of 18 months from the date of their original purchase by a consumer provided that the appliances are properly used in accordance with their operating instructions and app...

Reviews: