BURNER FLAME CONTROL

SERIES

page 3 di 6 

DOUBLE ELECTRODE FLAME DETECTION  
IN ACCORDANCE WITH STANDARD EN 298 

 

  COMMISSIONING                                     . 

 
1. Open the gas valve. 
2. Start the system. 
3. Give power to the 

4.  Press  the  power  button  (green  power 

LED lights up). 

5.  Switch  on  the  enable  terminal  to  start 

the ignition cycle. 

6. Waiting time at the start of about 5sec. 
7.  After  this  time  the 

  will  carry  out 

the  ignition  cycle.  The  gas  solenoid 
valve  will  be  commanded  and  the 
discharge  will  be  carried  out  at  the 
same  time  (yellow  discharge  LED  will 
light  up).  At  the  end  of  the  discharge 
the  presence  of  the  flame  will  be 
checked. 

8.  In  its  presence,  the  equipment  goes 

into  operation  by  turning  on  the  green 
detection  LED  and  continuing to  power 
the solenoid Gas valve. 

9. Otherwise 

 will go into lockout (the 

gas 

solenoid 

valve 

will 

be 

disconnected,  the  alarm  contact  will 
close  and  the  red  lock  LED  will  light 
up). To reset it and retry the boot it will 
be necessary to switch it off and switch 
it on again using the power button. 

 

 

N.B.  The  terminl  box                  should  never  be 
used.  This  clamp  has  remote  unlocking 
functionality  and  must  be  used  only  by 
authorized personnel, keeping the burner to be 
re-ignited under strict control.

 

 

   OPERATION CHECK                               . 

 
1. 

 

Remove the detection plug during 

operation

.

 

2. 

  will  attempt  to  restart  only  once, 

after  which  it  will  be  shut  down  due  to 
an  anomaly  (the  gas  solenoid  valve 
will be disconnected, the alarm contact 
will  close  and  the  red  LED  will  light 
up). 

3.  The burner flame must go out. 
4.  If  a  different  operation  should  occur 

check  the  wiring.  This  done  if  the 
problem  has  not  been  resolved 
disassemble  the 

  and  send  it  to 

the  manufacturer  for  a  complete 
overhaul. 

After replacing the safety device, check its 
operation: 
-  Close  the  general  gas  valve  and  check 

that  the  appliance,  after  a  few  attempts, 
does not start. 

If  the  safety  device  works  correctly  and 
the  wiring  is  in  order  but  the  equipment 
attempts to start the burner, send it to the 
manufacturer for a check. 
 

    OPERATING MODES GRAPHS           . 

 
Ta => 

waiting time before starting 

(pre-purge Time) 

 
 

Start without flame

 

 
 
 
 
 
 
 
 
 
 
 
 

Start with flame  

 
 
 
 
 
 
 
 
 
 
 
 

Re-start after flame faliure.

Summary of Contents for CF5Q Series

Page 1: ...Series Automatic burner control unit MONO DOUBLE ELECTRODE UV SENSOR FLAME DETECTION SAITEK srl www saitek it info saitek it Casalgrande RE ITALY Tel 39 0522 848211 Fax 39 0522 849070...

Page 2: ......

Page 3: ...modi cation use ormaintenancethey are not performed correctly they can occur injury or damage Please read the instructions rst to use the product to come installed according to regulations in force i...

Page 4: ...The burner is checked by an ionization electrode For grounded grids With a single restart due to flame put out can be applied directly to the burner in industrial thermal processes for metals glass ce...

Page 5: ...by pressure Dimensions 47 x 123 x 105 mm Prepared for pipe connection collars is not provided already wired otherwise perform the necessary connection on the back by the 16 position connector RECCOMEN...

Page 6: ...contact will close and the red lock LED will light up To reset it and retry the boot it will be necessary to switch it off and switch it on again using the power button N B The terminl box should nev...

Page 7: ...Pre Purge Time setting Pre Purge 5 sec Pre Purge 1 sec Pre Purge 8 sec Pre Purge 10 sec Pre Purge 20 sec Pre Purge 30 sec 1 2 ON 3 4 5 6 7 8 Pre Purge 50 sec 1 2 ON 3 4 5 6 7 8 Pre Purge 70 sec 1 2 ON...

Page 8: ...contents to third parties without authorization is forbidden Saitek Srl reserves the right to modify the present document at any moment without prior notice 04 2018 BURNER FLAME CONTROL SERIES page 5...

Page 9: ...valve outlet Check the wiring in case of short circuit in outlets eliminate it and change the inner fuse 2 5 A Or send the appliance to the manufacturer THERE IS THE FLAME BUT THE DETECTION LED IS OFF...

Page 10: ...contents to third parties without authorization is forbidden Saitek Srl reserves the right to modify the present document at any moment without prior notice AUTOMATIC BURNER CONTROL UNIT SERIES MONO D...

Page 11: ......

Page 12: ...installation up to a maximum of 18 months from the date of their original purchase by a consumer provided that the appliances are properly used in accordance with their operating instructions and app...

Reviews: