S A G E M E T E R I N G , I N C .
O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
56
REV. 10-SIX/SRX
16 (0x10) WRITE REGISTERS
Writes the binary contents of the specified register
into the meter. Sage Rio values are typically 32 bits
wide (4 bytes) and contain a single IEEE754 floating
point value. Modbus registers are 16 bits wide (2
bytes) so a minimum of 2 Modbus registers are
required to transfer all floating point bits into the
meter. See section titled
Sage Floating Point Format.
Query
The query message specifies the starting register
address and the quantity of registers to be written.
16 (0x10) WRITE MULTIPLE REGISTERS
–QUERY–
–RESPONSE–
SA – SLAVE ADRESS
SA
0x10 – FUNC CODE
0x10 – 16 FUNC CODE
RH – REG ADDR HI
RH – REG ADDR HI
RL – REG ADDR LO
RL – REG ADDR LO
00 – # OF REGS HI
00 – # REGS HI
CT – # OF REGS LO
CT – # REGS LO
BC – BYTES COUNT
CH – CRC MSB
DATA0
CL – CRC LSB
DATA1
DATAn
CH – CRC MSB
CL – CRC LSB
REG ADDR HI (RH) is set to:
01 for INTEGER access of integral values
02 for IEEE754 floating point
03 for Scaled (x1000) long integer of floating point value
REG ADDR LO (RL) is the starting address index into the register
structure. See section titled Sage Register Index Values.
CT is the register count needed to transfer data. Typically this byte is
set to 02 to request 1 full IEEE754 floating point value.
BC is the actual number of bytes that follow.
DATA0-DATAn are bytes in binary format transmitted to the slave
device representing the contents of the selected register(s).
Summary of Contents for RIO SIX
Page 2: ......
Page 6: ......
Page 7: ...Section GETTING STARTED A ...
Page 8: ......
Page 25: ...Section STYLES AND FEATURES B ...
Page 26: ......
Page 39: ...Section DIAGNOSTICS D ...
Page 40: ......
Page 45: ...Section WARRANTIES AND SERVICE WORK E ...
Page 46: ......
Page 51: ...Section MODBUS F ...
Page 52: ......
Page 61: ...Section HART G ...
Page 62: ......
Page 71: ...G Section APPENDIX H ...
Page 72: ......