4
SH6- HEATER CONTROLLER SERIES
1.3.1 SH6 INPUT DATA
NOTE:
The stack input voltage and the control circuit
supply must be synchronised i.e. R to R, S to S, T to T!!
STACK INPUT:
Voltage Type
SCR Voltage Rating
-
3 Phase Input
-
2,5 x line-line
AC
Voltage (min)
Type SH6-XX-3
-
420V Max Continuous
RMS voltage
Type SH6-XX-5
-
580V Max Continuous
RMS Voltage
Line Frequency
-
50Hz +2Hz
PC550 CONTROL SUPPLY
Voltage Type
- 3 Phase Input
Selectable 380/525V
Link at 380V Position
- 340v - 420v
Link at 525V Position
- 470v - 580v
Line Current
- Less that 25mA
Line Frequency
- 50Hz ± 2Hz
FAN SUPPLY
Type SH6 -100 to SH6-800 - AC220V, 50Hz, 0,5A
1.3.2 SH6 OUTPUT DATA
Unless otherwise specified, the currents listed below are
maximum at a maximum ambient temp of 40 DegºC and at an
altitude of 1500m max.
OUTPUT CURRENT
Type SH6 - 100
-
100 A Max. Cont. Current
Summary of Contents for SH6 Series
Page 1: ...Saftronics SH6 Manual ...
Page 9: ...SH6 HEATER CONTROLLER SERIES 8 FIG 2 2 SH6 SERIES SIZE C OVERALL DIMENSIONS ...
Page 14: ...SH6 HEATER CONTROLLER SERIES FIG 3 4 SIZE E CONNECTION LAYOUT 3 1 PC550 CONTROL TERMINALS 13 ...
Page 15: ...SH6 HEATER CONTROLLER SERIES FIG 3 5 PC550 CONTROL TERMINALS 14 ...