18
SH6- HEATER CONTROLLER SERIES
4.1.1 SH6-100-X THROUGH SH6-800-X
Check that the switches and potentiometers on the
PC550/7 series control card are set as given in Table 4.1
for the specific heater controller.
SWITCHES
POSITION
SW1
Control Reference
SW1-1 ON –2 OFF
0-10Vdc input
SW1-1 OFF –2 ON
4-20mA input
SW2
Burden Resistor Selector
ON
4,7 Ohms
ON
10 Ohms
SW3
Burden Resistor Selector Switches
ON
33 Ohms
ON
56 Ohms
ON
100 Ohms
SW4
Soft Starter/ Phase controller Select
BOTH ON
Phase control
1 ON 2 OFF
Soft Starter
SW5
Bypass Activate Relay
BOTH ON
Activated
BOTH OFF
Deactivated
POTENTIOMETERS
POSITION
SH6-100 THRU -800
PHV
380v CCW
525v CW
BYP/TIME
MID RANGE
BIAS
FACTORY SET
MAX SPD
FULLY CCW
SPD STAB
FULLY CCW
GAIN
FACTORY SET
DECEL
FULLY CW
ACCEL
FULLY CW
CURR STAB
MID RANGE
MIN SPD
FULLY CCW
TORQ
FULLY CCW
MAX CURR
FULLY CCW
TABLE 4.1 - CONFIGURATION SETUP
4.2 START UP PROCEDURE
Summary of Contents for SH6 Series
Page 1: ...Saftronics SH6 Manual ...
Page 9: ...SH6 HEATER CONTROLLER SERIES 8 FIG 2 2 SH6 SERIES SIZE C OVERALL DIMENSIONS ...
Page 14: ...SH6 HEATER CONTROLLER SERIES FIG 3 4 SIZE E CONNECTION LAYOUT 3 1 PC550 CONTROL TERMINALS 13 ...
Page 15: ...SH6 HEATER CONTROLLER SERIES FIG 3 5 PC550 CONTROL TERMINALS 14 ...