SH6- HEATER CONTROLLER SERIES
-
Check DIP Switch selected is installed and is the correct
value. Note failure to do this can result in damage to the
controller.
-
Set REF INP to ZERO
-
Apply power to the drive.
-
Check POWER ON LED and PHASE ROT LED on PC550
are ON.
-
Press start button.
-
Check RUN LED on PC550 is on.
-
Check that the drive can be stopped by pressing the
stop button.
-
Check RUN LED on PC550 will extinguish.
-
Restart the drive.
-
Slowly increase REF INP (Max 10V).
-
Adjust ACCEL pot to give desired ramp time.
-
Measure the current drawn by the load with a clip on
ammeter.
-
Adjust MAX CURR pot clockwise until the desired
current limit setting is reached.
-
Check that the elements are drawing desired current
once acceleration is complete and there is a 10VDC
reference.
-
The controller is now set for operation.