Inverter Model
CIMR-P5U
2018 2022 2030 2037 2045 2055 2075
—
O
ut
pu
t C
ha
ra
ct
er
ist
ics
Motor Output (HP) * 30 40 50 60 75 100 125
Capacity (kVA) 30 37 50 61 70 85 110
Rated Output
Current (A) - VT **
80 104 130 160 192 248 312
Rated Output
Current (A) - CT **
64 83 104 128 154 198 250
Max. Voltage
3-Phase, 200/208/220/230V
(Proportional to input voltage)
Rated Output Frequency 0.1 to 400 Hz
Overload Capacity - VT ** 120% Rated Output Current / 1 minute
Overload Capacity - CT ** 150% Rated Output Current / 1 minute
Po
we
r S
up
pl
y
Input Current (A) 88 119 143 176 212 270 344
—
Rated Voltage &
Frequency
3-Phase
220 - 230V, 50/60Hz
Voltage Fluct10%, -15%
Frequency Fluctuation ±5%
CIMR-P5U 4018 4022 4030 4037 4045 4055 4075 4110 4160 4185 4220 4300
O
ut
pu
t C
ha
ra
ct
er
ist
ics
Motor Output (HP) * 30 40 50 60 75 100 150 200 250 300 400 500
Capacity (kVA) 31 40 50 61 73 98 130 170 230 260 340 460
Rated Output
Current (A) - VT **
41
52
65
80
96 128 180 240 302 380 506 675
Rated Output
Current (A) - CT **
32 42 52 64 77 102 144 182 242 304 404 540
Max. Voltage
#
3-Phase, 380/400/415/440/460V
(Proportional to input voltage)
Rated Output Frequency 0.1 to 400 Hz
Overload Capacity - VT ** 120% Rated Current / 1 minute
Overload Capacity - CT ** 150% Rated Current / 1 minute
Po
we
r S
up
pl
y
Input Current (A) 46 58 72 88 106 141 198 264 330 456 608 810
Rated Voltage &
Frequency
#
3-Phase
380 -440 - 460V, 50/60Hz
Voltage Fluct10%, -15%
Frequency Fluctuation ±5%
Chapter 1 - Receiving & Installation
Specifications
* HP ratings based on standard NEMA 4-pole motor data.
#
For 380V operation, the motor rated current must be less than or equal to the inverter
rated current.
** VT: Variable Torque rating (n116=1), CT: Constant Torque rating (n116=0)
Note: Shaded areas indicate factory settings.
efesotomasyon.com - Control Techniques,emerson,saftronics -ac drive-servo motor