OTHER CODES
CODE DATA COMMENTS
Outputs.
*88* - #
0 = Standard (Default)
• Relay 1 will be activated when set time reached.
• Relay 1 will be deactivated when emergency call ends.
• Relay 2 will be activated when the battery test has failed.
• Relay 2 will be deactivated by pressing the reset button.
1 = EN81-28 Pictograms
• Relay 1 will be activated when the emergency button in pressed
(yellow pictogram).
• Relay 1 will be deactivated when the reset button is pressed or if
alarm centre presses “5”.
• Relay 2 will be activated when the call is acknowledged (green
pictogram).
• Relay 2 will be deactivated when the call is disconnected.
2 = DTMF-controlled
The relays can be activated remotely for 5 seconds.
• Relay 1 will be activated for 5 seconds when DTMF “8” is pressed.
• Relay 2 will be activated for 5 seconds when DTMF “9” is pressed.
3 = Manual - ECF (Emergency Call Fail)
• Relay 1 will be activated when set delay reached.
• Relay 1 will be deactivated when the reset button is pressed.
Change password *91* - - - - # Change password (default=0000)
Simulate an
alarm event
*94* - #
Triggers an alarm event after programming is terminated.
1 = Emergency call
2 = Test alarm
3 = Battery failure
4 = Microphone/Loudspeaker failure
5 = Emergency call
6 = Maintenance
7 = Main unit power failure