21
Ÿ
Testing Procedures with the TL305
1. Please wait for 10 seconds after power is connected. Check if Yellow LED is
blinking
2. Turn on the TL305 and point it at the front of the SafeFlame. The recommended
distance between the test lamp and the detector is within 16ft(5m)
3. If the Red LED is on, the fire is detected
4. If the product is set to reset manually, cycle power to the detector
5. If the Red LED does not turn on, please reduce the testing distance and try
again. If that same problem persists, check the test lamp for functionality. If
working properly, contact the manufacturer.
Note: If bulb No. 1 is blinking and the radiation intensity is weak, or if the No. 2 bulb is
not functioning, please re-charge the test lamp. If neither the No. 1 or No. 2 bulbs
turn on, it means the test lamp is defective and require repair.
Detector Status During Testing
Operational or Output Status
Before Connecting Power
-Fault Relay signal Open (N.O.: De-Energized)
- All LEDs off
Common
Normal
Fire
After
Connecting
Power
-Fault Relay signal Closed (N.C.: Energized)
- After 7 seconds of self-diagnosis test, LED intersect for
3 seconds (Yellow Red Yellow etc) blinking
→
→
→
-All output, “Normal” signal (N.C.: Energized)
- Orange LED blinking (0.5Hz)
- All output “Fire” signal
Status
4.3 Testing
4.3.1
Built-in-Test
The detector will automatically perform a self-diagnostic test every 12 hours.
4.3.2
Test Lamp
The TL305 generates specific IR3 radiation which can be detected by the SafeFlame
detector series as a fire. It has an individual built-in internal power supply, making it
portable with up to a 30 minute charge.
[Figure 14] TL305 Test Lamp
Test Lamp for
IR3 Flame Detector
Model
SafeFlame Installation and Operation Manual
(Publication#: MA-SF200OM)