14
Fault Relay Output: Wiring Diagram
TB1
FLT_COM
Terminal
FLT_N.C.
Common
Normal (De-Energized)
Relay Status
Fault (Energized)
Common
Rating: 2A@28VDC, 4A@125VAC, 2A@250VAC
-FLT_N.C. is default. To disable Fault relay switch SW1-8 to ON
0-20mA Current Source: Wiring Diagram
Normally Open (N.O.)
Normally Closed (N.C.)
TB2
Terminal Block
Connection fault
Terminal
Detector Status
Current Output (mA)
0-20mA
0
Self diagnosis fault
Normal
Initializing Circuit fault
Self Diagnosis Test
Warning
Alarm
2
4
8
12
16
20
Non-Isolation Output: Common 24V-_IN(-Power)
Max Resistance:
400
Ω
SafeFlame Installation and Operation Manual
[Figure 10] Terminal wiring diagram at fire alarm relay
CONTROLLER
CONTROLLER
(Publication#: MA-SF200OM)