background image

TABLE 2. 

MODEL NUMBER

HOLE DIAMETER

TORQUE SETTING

WFD20EN

31.8 mm +1.6 mm

1

1

/

4

 in +

1

/

16

 in

40.7 - 47.5 NT-M

30 - 35 FT-LBS

WFD25EN
WFD30EN

50.8 mm + 1.6 mm

2 in +

1

/

16

 in

61.6 - 67.8 MT-M

45 - 50 FT-LBS

WFD40EN
WFD60EN
WFD80EN

3.   Remove burrs and sharp edges from the hole. Clean and remove all  scale and 

foreign matter from the inside wall of pipe for a distance equal to the pipe di-

ameter on either side of the hole to ensure free movement of the vane. Clean the 

outside of the pipe to remove dirt, metal chips, and cutting lubricant.

4.   Seat the saddle gasket against the saddle and mount detector directly to pipe. 

Carefully roll the vane opposite the direction of flow and insert it through the 

hole (see Figure 4). Seat the saddle firmly against the pipe so that the locating 

boss goes into the hole.

5.   Install the U-bolt, tightening the nuts alternately to ensure a uniform seal (see 

Table 2 for torque values).

6.   Remove the cover with the tamper-proof wrench provided. Move the actuator 

lever back and forth to check for binding. If the vane binds, remove the detector 

and correct the cause before proceeding.

CAUTION

Be sure the direction-of-flow arrow and directional cover point in the correct direc-

tion, or else waterflow will go unreported. See Figure 4.

FIGURE 1. MOUNTING DIMENSIONS

8.9 CM

(3.5")

6.6 CM

(2.6")

PIPE DIAMETER

PLUS 12.7 CM

(5")

PIPE

VANE

OVERALL WIDTH = PIPE DI 6.4 CM (2.5")

U-BOLT

NUT

PIPE

SADDLE

U-BOLT

PIPE

W0384-00

FIGURE 2. LOCATION OF MOUNTING HOLE TOP VIEW 

WRONG

RIGHT

REMOVE BURRS FROM EDGE OF HOLE. CLEAN OUT SCALE

AND FOREIGN MATTER FROM INSIDE WALL OF PIPE.

W0106-00

PREOPERATION TESTING

1.   Fill the fire sprinkler system and check for leaks around the waterflow detector. 

If it leaks, first check for proper torque on U-bolt nuts. If leak persists, drain the 

system and remove the detector (refer to Maintenance). Check for dirt or for-

eign objects under the gasket, and make sure that the pipe surface is not dented. 

Reinstall the detector and check again for leaks. Do not proceed until all leaks 

have been stopped.

2.   Connect an ohmmeter or continuity tester across COM and B-NO switch ter-

minals. The ohmmeter should indicate an open circuit.

3.   Deflect the actuator lever and hold it until the pneumatic delay shaft releases the 

switch buttons. The ohmmeter or continuity tester should show a short circuit 

after the delay has elapsed. If there is no delay, check the setting of the delay 

adjustment dial.

FIELD WIRING

1.   All models have two SPDT switches. Switch contacts COM and B-NO are closed 

when water is flowing and open when water is not. Connect the switches as 

shown in Figure 7 depending on the application.

2.   When connected to a listed fire sprinkler/fire alarm control panel, the initiating 

circuit must be unable to be silenced.

3.   A ground screw is provided with all waterflow detectors. When grounding is 

required, clamp wire with screw in hole located between conduit entrance holes, 

see Figure 5.

4.     Use proper waterproof conduit fittings where required.

WARNING

High Voltage. Electrocution Hazard. Do not handle live AC wiring or work on a device to 

which AC power is applied. Doing so may result in severe injury or death.
When utilizing switches at voltages greater than 74VDC 

 or 

49VAC

~

means to provide all–pole disconnection must be incorporated in the field 

wiring, such as a circuit breaker.

MECHANICAL DELAY ADJUSTMENT

The pneumatic delay is preset at the factory to a dial setting of approximately 25 sec-

onds. To adjust the setting, turn the adjustment dial clockwise to increase the delay, 

counterclockwise to decrease it. Delay can be adjusted over a range from 0 to 30 sec-

onds maximum, see Figure 3.
NOTE: Set the delay to the minimum required to prevent false alarms due to flow 

surges.
Periodically test time delay as required by Authority Having Jurisdiction or code au-

thority. 

  

I56-4051-F 

 

 4/21