FIGURE 3. DELAY ADJUSTMENT DIAL 

NOTE: NUMBER ON DIAL IS APPROXIMATE TIME DELAY IN SECONDS. 

DELAY

ADJUSTMENT

DIAL

W0386-01

OPERATIONAL TESTING

Always notify the central station monitoring waterflow alarms before repairing, 

maintaining or testing waterflow alarm devices.
1.   Replace the cover and tighten the tamper-proof screws with the tamper-proof 

wrench. Store the wrench in a secure place.

2.   Open the inspector’s test valve and time how long it takes for the detector to 

indicate a flow condition. The detector should remain activated until the inspec-

tor’s test valve is closed. Air pockets in the sprinkler system may increase the 

apparent time delay.

MAINTENANCE

To prevent accidental water damage, control valves should be shut tight and the system 

completely drained before waterflow detectors are removed or replaced.
Inspect detectors in accordance with applicable codes and standards and/or the 

Authority Having Jurisdiction for leaks and replace if a leak occurs. Test detectors 

at least quarterly as described under Operational Testing to ensure proper operation. 

Test more often as required by applicable codes or standards.
Under normal conditions Safe Signal waterflow detectors should provide years of 

trouble-free service. If any part of the detector does not perform properly, replace 

the entire detector. Installation methods other than those listed in this installation 

manual may prevent the device from reporting the flow of water in the event the as-

sociated fire sprinkler system is activated by a fire. Safe Signal is not responsible for 

devices that have been improperly installed, tested, or maintained. 
Proceed as follows to remove a detector:
1.  Drain the pipe.
2.  Turn off electrical power to the detector, and then disconnect wiring.
3.  Loosen nuts and remove U-bolts.
4.   Gently lift the saddle far enough to get your fingers under it. With your fingers, 

roll the vane so it will fit through the hole while continuing to lift the waterflow 

detector saddle.

5.  Lift detector clear of pipe.

CAUTION

If a vane breaks off in a pipe, find and remove it. If it is not removed, the vane may 

restrict the proper flow of water to all or part of the fire sprinkler system.

FIGURE 4. ASSEMBLY DIAGRAM 

WATERFL

OW

U-BOLT

PIPE

SADDLE GASKET

REFER TO

 TABLE 1

U-BOLT

NUT

ELECTRICAL

CONDUIT

ENTRANCE

COVER

TAMPER PROOF

WRENCH

(P/N WFDW)

ROLL PADDLE

OPPOSITE OF

FLOW ARROW

WHILE INSERTING

PIPE SADDLE

MOUNTING PLATE

TIMER

(REPLACEMENT

P/N FS-RT)

COVER TAMPER

SWITCH

(OPTIONAL P/N CTS)

W0392-01

FIGURE 5. GROUND SCREW LOCATION 

GROUND 

GROUND 

SCREW

SCREW

W0383-01

  

I56-4051-F 

 

 4/21

Reviews: