ENGLISH
36
1. PARAMETERS
Par.
Description
Units
Programming
Default
Min.
Max.
Wizard
0.5
FS
Notes
1.1
WORKING PRESSURE
Bar
Pressure you wish to maintain in the system.
Wizard
0
11
1.2
MOTOR CURRENT
Amp
Current of the motor in amperes. Taking into account
whether your motor is wired as three phase 230V or
three phase 400V.
0
1
1.3
ROTATION DIRECTION
You can change the rotation direction of the motor by
modifying this parameter from 0 to 1 or vice versa.
Wizard
0
99.9
1.4
STOP FREQUENCY
Hz
The system will stop when the frequency converter has
been working for a certain time (see parameter 5.06)
below this frequency.
0.5
0.3
3
1.5
START-UP DIFFERENTIAL
Bar
This is the differential that enables you to reduce the
pressure to start the pump using the value entered in
parameter 1.1.
2. DISPLAY
Par.
Description
Units
Notes
2.01 MODULE TEMPERATURE
ºC
This indicates the temperature the electronic module of the unit is at.
2.02 ANALOGUE SIGNAL
mA
This indicates the value in mA of the pressure transducer. This data will be 4 mA for 0 Bar
and 20 mA for the upper limit of the transducer connected.
2.03 VOLTAGE HOURS
Hours This indicates the total number of hours the unit has been connected to an electricity grid.
2.04 HOURS WORKED
Hours This indicates the total number of hours worked (providing an output voltage) of the frequency converter.
2.05 START-UP NUMBER
This indicates the total number of start-ups from zero that the unit has made.
2.06 DIGITAL INPUT 1
This indicates whether digital input 1 is ON or OFF.
2.07 DIGITAL INPUT 2
This indicates whether digital input 2 is ON or OFF.
2.08 RELAY 1 OUTPUT
This indicates whether the relay 1 output is ON or OFF.
2.09 RELAY 2 OUTPUT
This indicates whether the relay 2 output is ON or OFF.
2.10 SOFTWARE VERSION
Version of the unit software.
2.11 CONS. POWER OF PUMP
W
Instantaneous power consumed in output terminals toward pump.
2.12 CONS. POWER OF GROUP
W
Power consumed instantaneously by all of the pumps.
3. LOG
11. SETUP MENU
Wizard:
This parameter is the one entered or calculated in the start-up wizard.
FS:
Full-scale value of the transducer (entered in the start-up wizard).
3 . 0 1
A L A R M
F 0 4
V O L T A G E
1 0 / 0 2 / 1 6
-
1 2 : 1 9
E X I T
F1
When you access the log menu you will find a list in chronological order
of alarms that have been triggered in your unit, indicating the date
and the time they occurred
Use the arrows
and
to move forward or back to view the
different alarms that have been triggered.
Press F1 to exit this menu.
Manual Variador [e]-MOTION_SACI 12/07/16 20:06 Página 36