34
English
»
Features for service
> 3 sec.
This menu allows checking some
control parameters (probe value,
window contact status, any alarms).
With the control set on “OFF”, press the “+”
and “-” buttons simultaneously for 3 seconds.
Select the desired parameter to be modified
pressing the “+” or “-” buttons and confirm
using the “M” button.
Once the parameter is selected, the value will
be displayed.
To exit the menu, press the “M” button for more
than 5 seconds.
FUNCTION
DESCRIPTION
STATUS
P1
View probe T1 value
diS
= Probe not connected
P2
/
/
P3
View probe T3 value
diS
= Probe not connected
FF1
View window contact status
C
= Closed
O
= Open
ALL
View any alarms
---
= No alarm
AL1
= Faulty T1 probe
AL3
= Faulty T3 probe
AL4
= Wrong Master dip configuration
AL5
= Wrong T-MB dip configuration
AL6
= Faulty RS485 transmission
AL7
= Faulty TTL transmission (T-MB/Slave)
Usc1
View voltage value sent to the inverter by the master
Parameters Table
Summary of Contents for WM-UH-ECM
Page 2: ...ITALIANO 3 19 ENGLISH 20 36 DEUTSCH 37 53 FRANÇAIS 54 70 ESPAÑOL 71 87 ...
Page 4: ...4 Italiano 235 mm 185 mm 118 mm 198 mm 135 mm 99 mm M6 x3 A B MONTAGGIO DIMENSIONI ...
Page 5: ...5 Italiano C D E ...
Page 21: ...21 English 235 mm 185 mm 118 mm 198 mm 135 mm 99 mm M6 x3 A B INSTALLATION DIMENSIONS ...
Page 22: ...22 English C D E ...
Page 38: ...38 Deutsch 235 mm 185 mm 118 mm 198 mm 135 mm 99 mm M6 x3 A B MONTAGE ABMESSUNGEN ...
Page 39: ...39 Deutsch C D E ...
Page 55: ...55 Français 235 mm 185 mm 118 mm 198 mm 135 mm 99 mm M6 x3 A B MONTAGE DIMENSIONS ...
Page 56: ...56 Français C D E ...
Page 72: ...72 Español 235 mm 185 mm 118 mm 198 mm 135 mm 99 mm M6 x3 A B MONTAJE DIMENSIONES ...
Page 73: ...73 Español C D E ...
Page 91: ......
Page 92: ......