![Sabiana Ocean ECM Instructions For Installation, Use And Maintenance Manual Download Page 56](http://html.mh-extra.com/html/sabiana/ocean-ecm/ocean-ecm_instructions-for-installation-use-and-maintenance-manual_794854056.webp)
56
EN
Electrical connections
Upstream of the unit, a disconnection switch must
be provided and shall have a contact separation in all
poles, providing full disconnection under overvolt-
age category III condition.
Before establishing the electric connections with the
motor please make sure that the main switch of the
appliance is in the OFF position.
Please make sure that the earthing is all right.
The maximum power consumption of the motors is
the following:
230 V 50-60 Hz
Model
1
2
3
4
5
Motor absorption
W
186
380
550
530
1045
Current absorbed
A
1,3
1,7
2,4
2,3
4,7
For electrical connections see p. 141
Controls
All the units can be controlled by:
• WM-AU and T-MB elctronic controls to be used
with UPO-AU power unit
• QCV-MB control panel to which TM-B control,
PSM-DI multifunction control panel, T-DI Touch
screen multifunction control panel, Web gateway
for Sabiana Cloud and Sabianet can be connected
for connecting the QCV-MB to the unit and the var-
ious controls/panels, please refer to the dedicated
manuals.
WM-AU control
Code 9066632
To be used with UPO-AU only
Control panel with electronic room thermostat for
2-4 tube installations and electric heater:
• manual/automatic 3 speed switch
• controllo termostatico del ventilatore o di 1-2 val-
vole
• manual/automatic Summer/Winter switch
• optional low temperature cut-out thermostat NTC
For the versions with electric heater, there is the pos-
sibility of thermostatic control (ON-OFF) of a cold wa-
ter valve and an electric heating element.
For wiring diagrams see WM-AU control manual.
T-MB control
Code 9066331E
To be used with UPO-AU or with QCV-MB control
panel only
Control panel with display and with electronic room
thermostat for 2-4 tube installations and electric
heater:
• manual/automatic 3 speed switch
• controllo termostatico del ventilatore o di 1-2 val-
vole
• manual/automatic Summer/Winter switch
• optional low temperature cut-out thermostat NTC
• weekly ON/OFF program
For the versions with electric heater, there is the pos-
sibility of thermostatic control (ON-OFF) of a cold wa-
ter valve and an electric heating element.
For wiring diagrams see T-MB control manual.
Summary of Contents for Ocean ECM
Page 2: ...2 IT da p 5 EN from p 39 FR à partir de la p 73 DE von S 108 ...
Page 53: ...53 EN Valve water flow rate chart Dp pressure drop Qw water flow rate ...
Page 87: ...87 FR Schéma débit d eau des vannes Dp perte de charge Qw débit d eau ...
Page 122: ...122 DE Diagramm Wasserdurchflussmenge Ventile Dp DruckverlusteWasser Qw Wasserdurchsatz ...