![Saab TankRadar G3 Service Manual Download Page 22](http://html1.mh-extra.com/html/saab/tankradar-g3/tankradar-g3_service-manual_3143594022.webp)
22
Service Manual
G3 MaC Second edition, March 2000
Symptom
Cause
Action
WS Alarm-
Sysfail, All IO terminals Bus (1-4)
Com
No power in any
terminal on one
bus
1
Check if many green Power
LED’s on the terminals are put
out
2
Check if the power supply is
functioning
3
Check cabling
4
Replace the Power Supply
Broken circuit
between I/O Unit
and I/O Box
1
In the Saab TankRadar I/O Box,
check the communication LED
on the RS-485 PCB Refer to as-
built drawings to find right PCB
2
Look for loose cables
3
Contact a Saab Marine
Electronics’ service agent
WS Alarm-
Sysfail, IO terminal Bus (1-4) fuse
Fuse is broken on
terminal
1
In the Saab TankRadar I/O Unit,
identify the terminals where the
green power LED is put out
2
Replace fuse
Power supply is
not working
1
Check Power Supply voltage
2
Replace Power supply
3
Contact a Saab Marine
Electronics’ service agent
Faulty values or faulty feedback
from equipment connected to MaC
system
Faulty valves,
pumps, sensors
etc
1
Check the equipment connected
to the Saab TankRadar I/O Unit
Loose cables on
terminals
1
Check cables connected to the
terminals that the equipment is
connected to
Faulty terminal
1
Check terminal
2
Replace the terminal
3
Contact a Saab Marine
Electronics’ service agent
Summary of Contents for TankRadar G3
Page 1: ...SERVICE MANUAL MaC Monitoring and Control System...
Page 6: ...6 Service Manual G3 MaC Second edition March 2000...
Page 8: ...8 Service Manual G3 MaC Second edition March 2000...
Page 20: ...20 Service Manual G3 MaC Second edition March 2000...
Page 24: ...24 Service Manual G3 MaC Second edition March 2000...
Page 26: ...26 Service Manual G3 MaC Second edition March 2000...