Installation and Commissioning

G  

Resistance characteristics of passive temperature sensors  (see last page)

In order to avoid damages  ⁄ errors, preferably shielded cables are to be used.  
Laying measuring cables parallel with current-carrying  cables must in any case be avoided. EMC directives shall be  observed! 
These instruments must be installed by authorised specialists only!

ATTENTION,  NOTE !  Testing current influences the thermometer‘s 
measuring accuracy due to intrinsic heating and therefore, should 
 never be greater than as specified below:
Sensor current, maximum 

 I 

max

Pt1000  (thin-layer)  .............................................................................. < 0.6 mA
Pt100     (thin-layer) .............................................................................. < 1.0 mA
Ni1000  (DIN),  Ni1000 TK5000  ....................................................... < 0.3 mA
NTC xx  ...................................................................................................... < 2 mW 
LM235Z ....................................................................................... 400  µ A … 5 mA
KTY 81 - 210  .............................................................................................. < 2 mA

Limiting deviation according to classes:
Tolerances at 0 °C:

Platinum sensors (Pt100, Pt1000): 
DIN EN 60751, class B  ........................................................................ ± 0.3 K
1 ⁄  3 DIN EN 60751, class B  .................................................................± 0.1 K

Nickel sensors: 
NI1000 DIN EN 43760, class B  .............................................................. ± 0.4 K
NI1000 1 ⁄  2 DIN EN 43760, class B  ..................................................... ± 0.2 K
NI1000 TK5000 ................................................................................... ± 0.4 K

Devices are to be connected under dead-voltage condition. Devices must 
only be connected to safety extra-low voltage. Consequential   damages 
caused by a fault in this device are excluded from warranty or liability. 
These devices must be installed and commissioned by authorised 

 

specialists. The technical data and connecting conditions shown on the 
device labels and in the mounting and operating instructions delivered 
 together with the device are exclusively valid. Deviations from the  
catalogue representation are not explicitly mentioned and are possible 
in terms of technical progress and continuous improvement of our  
pro ducts. In case of any modifications made by the user, all warranty 
claims are  forfeited. Operating this device close to other devices that 
do not comply with EMC directives may influence functionality. This  
device must not be used for monitoring applications, which serve the 
purpose of protecting persons against hazards or injury, or as an  
EMERGENCY STOP switch for systems or machinery, or for any other 
similar safety-relevant purposes.
Dimensions of housings or housing accessories may show slight toler-
ances on the specifications provided in these instructions. 
Modifications of these records are not permitted. 
In case of a complaint, only complete devices returned in original packing 
will be accepted.

Our “General Terms and Conditions for Business“ together with the 
“General Conditions for the Supply of Products and Services of the 
Electrical and Electronics Industry“ (ZVEI conditions) including 

 

supplementary clause “Extended Retention of Title“ apply as the  
exclusive terms and conditions“.

Notes on commissioning:

This device was calibrated, adjusted and tested under standardised 
conditions. When operating under deviating conditions, we recommend 
performing an initial manual adjustment on-site during commissioning 
and subsequently at regular intervals.

Commissioning is mandatory and may only be performed by qualified 
personnel!

Notes regarding mechanical mounting and attachment:

Mounting shall take place while observing all relevant regulations and 
standards applicable for the place of measurement (e.g. such as welding 
instructions, etc.). Particularly the following shall be regarded:
–  VDE  ⁄  VDI  directive  technical  temperature  measurements,   

measurement set - up for temperature measurements.

– The EMC directives must be adhered to. 
– It is imperative to avoid parallel laying of current-carrying lines.
– We recommend to use shielded cables with  

the shielding being attached at one side to the DDC  ⁄  PLC.

Before mounting, make sure that the existing thermometer‘s technical 
parameters comply with the actual conditions at the place of  utilization, 
in particular in respect of:
– Measuring range 
–  Permissible maximum pressure, flow velocity 
–  Installation length, tube dimensions
– Oscillations, vibrations, shocks are to be avoided (<  0.5  g)

Attention! In any case, please observe the mechanical and thermal 
load limits of protective tubes according to DIN 43763 respectively  
according to specific S+S standards!

Summary of Contents for THERMASGARD RSTF

Page 1: ...d Montageanleitung Raumstrahlungstemperaturf hler mit passivem Ausgang G Operating Instructions Mounting Installation Room radiation temperature sensors with passive output F Notice d instruction Sond...

Page 2: ...THERMASGARD RSTF D G F r Ma zeichnung Dimensional drawing Plan cot RSTF T K 6 0 85 85 27 2 40...

Page 3: ...n Ausgang siehe Tabelle passiv optional auch mit zwei Sensoren Schaltungsart 2 Leiteranschluss 4 Leiteranschluss bei Pt100 bei anderen Sensoren optional Messstrom 0 6 mA Pt1000 1 0 mA Pt100 0 3 mA Ni1...

Page 4: ...ratursensor in einem entsprechenden Geh use eingebettet wobei das Geh use verschieden aufgebaut sein kann z B mit einer externen F hlerh lse siehe Au entemperaturf hler ATF2 Bei den Geh usef hlern wir...

Page 5: ...wie anschlie end in regelm igen Abst nden vorzunehmen Eine Inbetriebnahme ist zwingend durchzuf hren und darf nur von Fachpersonal vorgenommen werden Hinweise zum mechanischen Ein und Anbau Der Einbau...

Page 6: ...W NTC xx 400 A 5 mA LM235Z Insulating resistance 100 M at 20 C 500 V DC Process connection by screws Housing plastic material ABS Housing pure white similar to RAL 9010 Semi globe black Dimensions 85...

Page 7: ...plication On housing type sensors the temperature sensor is embedded in a respective housing Different designs of housing are available e g with an external sensor sleeve see outside temperature senso...

Page 8: ...ainst hazards or injury or as an EMERGENCY STOP switch for systems or machinery or for any other similar safety relevant purposes Dimensions of housings or housing accessories may show slight toler an...

Page 9: ...apteurs Courant de mesure 0 6 mA Pt1000 1 0 mA Pt100 0 3 mA Ni1000 Ni1000 TK5000 2 0 mW NTC xx 400 A 5 mA LM235Z R sistance d isolement 100 M 20 C 500 V cc Raccord process par vis Bo tier mati re plas...

Page 10: ...n bo tier correspondant Mais il est possible que ce bo tier soit construit diff remment par ex avec une sonde chemis e externe voir sonde de temp rature ext rieure ATF2 Dans le cas des sondes sous for...

Page 11: ...s des conditions diff rentes nous recommandons un premier r glage manuel sur site lors de la mise en service et intervalles r guliers par la suite La mise en service ne doit tre effectu e que par du p...

Page 12: ...1 2 2 1 LM235Z 3 4 LM235Z 1 1 2 2 Rx 1 2 Rx 3 4 1 THERMASGARD RSTF WG03 RSTF IP30 RSTF PT100 Pt100 DIN EN 60 751 1101 40C0 1003 000 RSTF PT1000 Pt1000 DIN EN 60 751 1101 40C0 5001 000 RSTF NI1000 Ni1...

Page 13: ...EN 60 751 Pt 1000 DIN EN 60751 Ni 1000 DIN EN 43 760 TCR 6180 ppm K Ni 1000_TK5000 TCR 5000 ppm K LM235Z IC 10 K 2 73 C NTC DIN 44070 PTC KTY 0 100 C TK ATF2 FSTF RTF ATF G 10 x SS 02 r 70 C 105 C 18...

Page 14: ...Ni1000 TK5000 0 3 A NTC xx 2 LM235Z 400 A 5 A KTY 81 210 2 A 0 C Pt100 Pt1000 DIN EN 60751 0 3 K 1 3 DIN EN 60751 0 1 K NI1000 DIN EN 43760 0 4 K NI1000 1 2 DIN EN 43760 0 2 K NI1000 TK5000 0 4 K EMV...

Page 15: ...te of publication They are only meant to inform about our products and their application potential but do not imply any warranty as to certain product characteristics Since the devices are used under...

Page 16: ...57 0 3431 3607 3830 110 120 146 1 1461 1760 1625 4 3552 3817 3930 120 130 149 8 1498 1833 3676 4008 130 140 153 6 1536 1909 3802 4166 140 150 157 3 1573 1987 3929 4280 150 NTC 1 8 kOhm NTC 2 2 kOhm NT...