Operating instructions
RYM
ASKON
®
700 - BACnet
RYM
ASKON
®
700 - Modbus
PARAMETER TABLE
Setting Mode via unit screen
RYMASKON 700 Series | Parameter Table | Status: 04.04.2022 (EN)
1
PARAMETER TABLE
Setting mode via device screen
CONTROL SETTINGS
Parameter name
Description
Area
Nominal Setpoint
Nominal setpoint
0.0...95.0 °C/°F/% (default 21.0 °C)
Setpoint Limit Mode
Type of setpoint limitation
0 = Absolute (Default)
1 = Relative
Min. Setpoint Adj
Absolute: smallest adjustable lower limit
Relative: maximum permissible setpoint
downwards adaptation
0.0...95.0 °C/°F/% (default 14.0)
Max. Setpoint Adj
Absolute: highest adjustable upper limit
Relative: maximum permissible setpoint
upwards adaptation
0.0...95.0 °C/°F/% (default 30.0)
INPUTS & OUTPUTS
Parameter name
Description
Area
Sensor 1 Source
If set to hardware, input RI1 (NTC10k) is read.
If set to network, the value can be transmitted to
the unit via the bus.
0 = Hardware (RI1)
1 = Network (default)
Sensor 2 Source
If set to hardware, input RI2 (NTC10k) is read.
If set to network, the value can be transmitted to
the unit via the bus.
0 = Hardware (RI2)
1 = Network (default)
Sensor 3 Source
If set to hardware, the internal temperature
sensor is read.
If set to network, the value can be transmitted to
the unit via the bus.
0 = Hardware (internal sensor, default)
1 = Network
Digital Input Mode
Setting the function of digital input DI (status
monitoring via the bus active in all cases).
For explanations see chapter “
Voltage-free
digital input DI1”
0 = Disabled
1 = Close for ECO (default)
2 = Open for ECO
3 = Close for OFF
4 = Open for OFF
5 = DI Contact Alarm
6 = Network
7 = Close for Night
Digital Input Delay
Digital input delay
(when changing over from active to inactive)
0...7200 s (default 0 s)
Internal Sensor Cal.
Single-point calibration of internal sensor
-10.0...+10.0 °C/°F
RI1 Cal.
Calibration of sensor connected to RI1
-10.0...+10.0 °C/°F
RI2 Cal.
Calibration of sensor connected to RI2
-10.0...+10.0 °C/°F
Hum Cal.
Calibration of internal RH sensor
(devices with RH option)
-10.0...+10.0 % RH
CO2 Cal.
Calibration of CO2 sensor
(devices with CO2 option)
-500...+500 ppm
Y1 mode
Not active/settable
Y2 mode
Not active/settable
Y3 mode
Not active/settable
AO temp. scale
Not active/settable
AO CO2. Scale
Not active/settable
Fan Night Speed
Fan speed during night operation
(OFF mode)
0...6 (default 0)
AO SP Min
Not active/settable
AO SP Max
Not active/settable