Operating instructions 

RYM

ASKON

®

    700 - BACnet 

RYM

ASKON

®

    700 - Modbus

PARAMETER TABLE 

Setting Mode via unit screen

RYMASKON 700 Series  |  Parameter Table  |  Status:  04.04.2022  (EN)

 

 

PARAMETER TABLE  

Setting mode via device screen 

 

 

CONTROL SETTINGS 

Parameter name 

Description 

Area 

Nominal Setpoint 

 

Nominal setpoint 

0.0...95.0 °C/°F/% (default 21.0 °C) 

Setpoint Limit Mode 

 

Type of setpoint limitation 

0 = Absolute (Default) 
1 = Relative 

Min. Setpoint Adj 
 

Absolute: smallest adjustable lower limit 
Relative: maximum permissible setpoint 

downwards adaptation 

0.0...95.0 °C/°F/% (default 14.0) 

Max. Setpoint Adj 
 

Absolute: highest adjustable upper limit 
Relative: maximum permissible setpoint 

upwards adaptation 

0.0...95.0 °C/°F/% (default 30.0) 

 

 

 

INPUTS & OUTPUTS 

Parameter name 

Description 

Area 

Sensor 1 Source 
 

If set to hardware, input RI1 (NTC10k) is read.  
If set to network, the value can be transmitted to 

the unit via the bus. 

0 = Hardware (RI1) 
1 = Network (default) 

Sensor 2 Source 
 

If set to hardware, input RI2 (NTC10k) is read. 
If set to network, the value can be transmitted to 

the unit via the bus. 

0 = Hardware (RI2) 
1 = Network (default) 

Sensor 3 Source 
 

If set to hardware, the internal temperature 

sensor is read. 
If set to network, the value can be transmitted to 

the unit via the bus. 

0 = Hardware (internal sensor, default) 
1 = Network 

Digital Input Mode 
 

Setting the function of digital input DI (status 

monitoring via the bus active in all cases). 

For explanations see chapter “

Voltage-free 

digital input DI1”

 

0 = Disabled 
1 = Close for ECO (default) 
2 = Open for ECO  
3 = Close for OFF 
4 = Open for OFF 
5 = DI Contact Alarm 
6 = Network 
7 = Close for Night 

Digital Input Delay 

 

Digital input delay 

(when changing over from active to inactive) 

0...7200 s (default 0 s) 

Internal Sensor Cal. 

 

Single-point calibration of internal sensor 

-10.0...+10.0 °C/°F 

RI1 Cal. 

 

Calibration of sensor connected to RI1 

-10.0...+10.0 °C/°F 

RI2 Cal. 

 

Calibration of sensor connected to RI2 

-10.0...+10.0 °C/°F 

Hum Cal. 

 

Calibration of internal RH sensor 

(devices with RH option) 

-10.0...+10.0 % RH 

CO2 Cal. 

 

Calibration of CO2 sensor 

(devices with CO2 option) 

-500...+500 ppm 

Y1 mode 

Not active/settable 

 

Y2 mode 

Not active/settable 

 

Y3 mode 

Not active/settable 

 

AO temp. scale 

Not active/settable 

 

AO CO2. Scale 

Not active/settable 

 

Fan Night Speed 

 

Fan speed during night operation 

(OFF mode) 

0...6 (default 0) 

AO SP Min 

Not active/settable 

 

AO SP Max 

Not active/settable 

 

 

 

25

Summary of Contents for RYM7-10IB-2102-000

Page 1: ...0 www SplusS de Operating instructions RYMASKON 700 BACnet RYMASKON 700 Modbus Room control unit with colour touch screen with BACnet or Modbus connection Interface for controlling temperature fans l...

Page 2: ...g this unit close to other devices that do not comply with EMC directives may influence the functionality thereof This unit must not be used for monitoring purposes which serve the purpose of protecti...

Page 3: ...de is exited the unit performs a soft reset Alternatively the new settings can also be activated by switching the unit off and on again deacti vate and reactivate supply voltage The configuration para...

Page 4: ...conditioning 1 zone and sun protection 2 zones via touch display 2 resistance inputs NTC10K for external temperature sensors 1 relay output 7A 0 5A with CO2 as 2 point regulator potential free control...

Page 5: ...control unit Functions temperature fan light A C air conditioning 1 zone and sun protection 2 zones Communication Modbus RTU Slave address range can be configured between 1 247 or BACnet MS TP device...

Page 6: ...y output 7 A 2 point regulation Type variants Basic model Typ 710 available from stock freely configurable type variants available upon request For configuration options see number key above ACCESSORI...

Page 7: ...ensional drawing mm WIRING Connection diagram basic model WARNING Switch off the power supply before commencing the wiring work RI2 RI1 DI1 G0 B A RLY COM 7A 250V RLY OUT 0V 24V RYMASKON 710 RLY 250V...

Page 8: ...ill be dimmed to the set standby value default 5 max 20 The brightness of the touch display in standby can be adjusted in the settings display brightness If this value is configured to 0 the display i...

Page 9: ...n speed when active A C air conditioning icon for activation deactivation of the A C air conditioning control if enabled Light icon for activation deactivation of the room lighting if enabled Blind ic...

Page 10: ...he action circle the gearwheel icon for making settings appears instead of the action circle as an indication to call up the secondary screen Relative Fig 3d Display of the relative target temperature...

Page 11: ...nfiguration settings Settings Inputs Outputs Hardware and Settings Display Sensor Text the value is also shown in the small grey action circle of the display The room control units can display up to t...

Page 12: ...Selection of degrees Celsius C or degrees Fahrenheit F WARNING Changing the default setting for the temperature unit will set the defaults for all other parameters Changing the default setting for the...

Page 13: ...ig 10 Active operating mode language abbreviation not available EN Room 23 5 C A 21 0 C C F IT ES FR EN DE FAN Room 23 5 C A 21 0 C C F DIGITAL INPUT DI1 voltage free The voltage free digital input ca...

Page 14: ...speed is set or changed via the bus the unit automatically changes to Automatic Mode AUTO an A is displayed above the line bar With manual priority switching the display changes to M or only shows A i...

Page 15: ...n sequence When switching to Auto the display returns to the fan speed set via the bus 3 STEP AUTO OFF M Steps 2 4 6 M and Auto A in sequence When switching to Auto the display returns to the fan spee...

Page 16: ...tus of the switching icons can be accessed and changed via the bus The switching icons are enabled in the settings display function 1 2 NOTE Only 1 zone at a time can be switched for the Light and A C...

Page 17: ...Positions 10 steps Sliding 1 steps infinite The positions are distributed equally from 0 100 Blind configuration movement type graphical depiction Translatory movement Level Fig 7a Rotary movement Ti...

Page 18: ...input the user can cancel OFF mode by tapping the OFF icon On the other hand a networked unit which the user has switched to OFF Mode can be switched back to the normal operating mode by the bus maste...

Page 19: ...In PARTY Mode the unit activates the internal relay default and the status can be accessed via the bus Tapping the icon again aborts the mode PARTY Mode can also be activated deactivated via the bus...

Page 20: ...to change it via the screen If enabled for the user display Mode icon the mode changes when the icon is tapped The following configurations are available Deactivated default HEAT COOL switch between h...

Page 21: ...applies i e if the controller was switched to ECO via the bus or the digital input the user can cancel the mode by tapping the ECO icon NOTE The display of the ECO icon can be deactivated in the sett...

Page 22: ...0000 no PIN required AUXILIARY SCREEN ICONS TAPPING THE ICON ACTIVATES DEACTIVATES THE MODE Page 18 CLEANING MODE TAPPING THE ICON ACTIVATES THE MODE with 30 sec deactivation of switching icons and bu...

Page 23: ...can be defined to activate deactivate the locking state Lock Code default 0000 no PIN required NOTE The display lock is also retained if the unit is switched off and back on again The following confi...

Page 24: ...TE Changed communication parameters are activated when setting mode is exited the unit performs a soft reset Alternatively the new settings can also be activated by switching the unit off and on again...

Page 25: ...be transmitted to the unit via the bus 0 Hardware RI2 1 Network default Sensor 3 Source If set to hardware the internal temperature sensor is read If set to network the value can be transmitted to th...

Page 26: ...t Only 3 No Input Lock Code PIN for activation deactivation of display lock 0000 no PIN required 0000 9999 default 0000 Relay Mode Setting of the relay function NO NC linked with Party mode Boost Netw...

Page 27: ...Fan 2 Bar 3 Fan 4 Coloured Bar Fan 5 Coloured Bar Blind 1 Mode Setting of the step width for blind 1 when pressing the arrow keys on the screen 1 On Off 0 100 2 4 steps 0 25 50 75 100 3 10 steps 0 10...

Page 28: ...led no text and measurement is displayed for sensor 1 0 Disabled 1 Room 2 Floor 3 Outside 4 Zone 1 5 Zone 2 6 Zone 3 7 Bathroom 8 Sauna 9 Bedroom 10 Kitchen 11 Cooler 12 Flow 13 Hot Water 14 Tank 15 P...

Page 29: ...o 651 001 Service Pin BACnet service pin only for BACnet devices if active the controller transmits a BACnet I am notification 0 Disabled Default 1 Enabled Maintenance Code PIN for setting mode 0000 n...

Page 30: ...l statements and data herein represent our best knowledge at date of publica tion They are only meant to inform about our products and their application potential but do not imply any warranty as to c...

Reviews: