Operating instructions 

RYM

ASKON

®

    700 - BACnet 

RYM

ASKON

®

    700 - Modbus

INSTALLATION AND  
COMMISSIONING

IMPORTANT NOTES

Only the valid edition of our conditions and the valid “General Conditions for the Supply of 
Products and Services of the Electrical and Electronics Industry” (ZVEI conditions) and 
the supplementary clause “Extended Retention of Title” apply as the terms and conditions 
regulating this purchase.

The following points must also be complied with:
- These instructions must be read before installation and commissioning,  

and all of the specifications that they contain must be complied with.

-  The units must only be connected to an extra-low safety voltage in a de-energised condition.  

Use shielded cables to avoid damage to the unit and faults (e.g. resulting from voltage induction),  
avoid parallel routing with live lines, and comply with the EMC directives.

-  This unit must only be used for its intended purpose, whereby the applicable VDE safety regulations and 

all regulations issued by the regional and national regulatory authorities, TÜV and local energy providers 
must be complied with. The purchaser must ensure that the relevant building and safety regulations are 
complied with, and must avoid hazards of all kinds.

-  No warranty or liability whatsoever will be accepted for defects and damage arising from improper 

use of this unit.

-  The warranty and liability excludes consequential damage caused by a fault in this unit.
-  The units must only be installed and commissioned by qualified personnel.
-  Only the technical data and connecting conditions specified by the installation and operating instructions 

which are included in the scope of delivery of the unit apply. Deviations from the depictions contained in 
the catalogue are not additionally listed, and are possible as a result of technical progress and the 
continuous improvement of our products.

-  Any alterations made to the unit by the user will void the warranty.
-  This unit must not be installed close to sources of heat (e.g. radiators) or their heat flow. Avoid direct 

solar irradiation or heat radiation from similar sources (powerful lamps, halogen spotlights).

-  Operating this unit close to other devices that do not comply with EMC directives may influence the 

functionality thereof.

-  This unit must not be used for monitoring purposes which serve the purpose of protecting persons 

against hazards or injury, as an Emergency Stop switch on systems or machinery, or for any other 
similar safety-related purposes.

-  The housing dimensions and the dimensions of accessories may differ slightly from the specifications 

of these instructions.

-  Changes to these documents are not permitted
-  In cases of complaint, we will only accept complete units returned in their original packaging.

Commissioning is mandatory and may only be performed by qualified personnel! Please read these instruc-
tions prior to installation and commissioning, and comply with the specifications that they contain!

Mounting shall take place while observing all relevant regulations and standards applicable for the place of 
measurement (e.g. such as welding instructions, etc.). It is particularly important to comply with the 
following:

-  VDE ⁄ VDI technical temperature measurements, directives, measurement set-ups for 

temperature measurements.

-  EMC directives
-  It is imperative to avoid parallel routing of current-carrying lines
-  We recommend the use of shielded cables with the shielding attached to the DDC/PLC at one side.

Before mounting, make sure that the existing technical parameters of the measuring instrument comply 
with the actual conditions at the place of utilization, particularly with regard to:

-  the measuring range
-  the maximum permissible temperature and humidity
-  the protection type and protection class
-  oscillation, vibration and impacts must be avoided (< 0.5 g)

Devices with integrated CO2-Sensor

Devices with integrated CO2-Sensor have 

an automatic calibration of the carbon dioxide measurement – 

ABC logic.

 The Automatic Background Logic is a self-calibrating mechanism that is suitable for use in 

applications in which the CO2 concentration regularly drops to fresh air level (350 - 500 ppm).  
This should typically happen at times during which the rooms are unoccupied.  
The sensor reaches its normal accuracy after 24 hours of continuous operation in an environment which 
has been exposed to a fresh air supply of 400 ppm CO2. The deviation error remains minimal with at least 
4 cases of sensor exposure to fresh air within 21 days. The ABC logic requires continuous operating 
cycles of longer than 24 hours in order to function properly.

2

Summary of Contents for RYM7-10IB-2102-000

Page 1: ...0 www SplusS de Operating instructions RYMASKON 700 BACnet RYMASKON 700 Modbus Room control unit with colour touch screen with BACnet or Modbus connection Interface for controlling temperature fans l...

Page 2: ...g this unit close to other devices that do not comply with EMC directives may influence the functionality thereof This unit must not be used for monitoring purposes which serve the purpose of protecti...

Page 3: ...de is exited the unit performs a soft reset Alternatively the new settings can also be activated by switching the unit off and on again deacti vate and reactivate supply voltage The configuration para...

Page 4: ...conditioning 1 zone and sun protection 2 zones via touch display 2 resistance inputs NTC10K for external temperature sensors 1 relay output 7A 0 5A with CO2 as 2 point regulator potential free control...

Page 5: ...control unit Functions temperature fan light A C air conditioning 1 zone and sun protection 2 zones Communication Modbus RTU Slave address range can be configured between 1 247 or BACnet MS TP device...

Page 6: ...y output 7 A 2 point regulation Type variants Basic model Typ 710 available from stock freely configurable type variants available upon request For configuration options see number key above ACCESSORI...

Page 7: ...ensional drawing mm WIRING Connection diagram basic model WARNING Switch off the power supply before commencing the wiring work RI2 RI1 DI1 G0 B A RLY COM 7A 250V RLY OUT 0V 24V RYMASKON 710 RLY 250V...

Page 8: ...ill be dimmed to the set standby value default 5 max 20 The brightness of the touch display in standby can be adjusted in the settings display brightness If this value is configured to 0 the display i...

Page 9: ...n speed when active A C air conditioning icon for activation deactivation of the A C air conditioning control if enabled Light icon for activation deactivation of the room lighting if enabled Blind ic...

Page 10: ...he action circle the gearwheel icon for making settings appears instead of the action circle as an indication to call up the secondary screen Relative Fig 3d Display of the relative target temperature...

Page 11: ...nfiguration settings Settings Inputs Outputs Hardware and Settings Display Sensor Text the value is also shown in the small grey action circle of the display The room control units can display up to t...

Page 12: ...Selection of degrees Celsius C or degrees Fahrenheit F WARNING Changing the default setting for the temperature unit will set the defaults for all other parameters Changing the default setting for the...

Page 13: ...ig 10 Active operating mode language abbreviation not available EN Room 23 5 C A 21 0 C C F IT ES FR EN DE FAN Room 23 5 C A 21 0 C C F DIGITAL INPUT DI1 voltage free The voltage free digital input ca...

Page 14: ...speed is set or changed via the bus the unit automatically changes to Automatic Mode AUTO an A is displayed above the line bar With manual priority switching the display changes to M or only shows A i...

Page 15: ...n sequence When switching to Auto the display returns to the fan speed set via the bus 3 STEP AUTO OFF M Steps 2 4 6 M and Auto A in sequence When switching to Auto the display returns to the fan spee...

Page 16: ...tus of the switching icons can be accessed and changed via the bus The switching icons are enabled in the settings display function 1 2 NOTE Only 1 zone at a time can be switched for the Light and A C...

Page 17: ...Positions 10 steps Sliding 1 steps infinite The positions are distributed equally from 0 100 Blind configuration movement type graphical depiction Translatory movement Level Fig 7a Rotary movement Ti...

Page 18: ...input the user can cancel OFF mode by tapping the OFF icon On the other hand a networked unit which the user has switched to OFF Mode can be switched back to the normal operating mode by the bus maste...

Page 19: ...In PARTY Mode the unit activates the internal relay default and the status can be accessed via the bus Tapping the icon again aborts the mode PARTY Mode can also be activated deactivated via the bus...

Page 20: ...to change it via the screen If enabled for the user display Mode icon the mode changes when the icon is tapped The following configurations are available Deactivated default HEAT COOL switch between h...

Page 21: ...applies i e if the controller was switched to ECO via the bus or the digital input the user can cancel the mode by tapping the ECO icon NOTE The display of the ECO icon can be deactivated in the sett...

Page 22: ...0000 no PIN required AUXILIARY SCREEN ICONS TAPPING THE ICON ACTIVATES DEACTIVATES THE MODE Page 18 CLEANING MODE TAPPING THE ICON ACTIVATES THE MODE with 30 sec deactivation of switching icons and bu...

Page 23: ...can be defined to activate deactivate the locking state Lock Code default 0000 no PIN required NOTE The display lock is also retained if the unit is switched off and back on again The following confi...

Page 24: ...TE Changed communication parameters are activated when setting mode is exited the unit performs a soft reset Alternatively the new settings can also be activated by switching the unit off and on again...

Page 25: ...be transmitted to the unit via the bus 0 Hardware RI2 1 Network default Sensor 3 Source If set to hardware the internal temperature sensor is read If set to network the value can be transmitted to th...

Page 26: ...t Only 3 No Input Lock Code PIN for activation deactivation of display lock 0000 no PIN required 0000 9999 default 0000 Relay Mode Setting of the relay function NO NC linked with Party mode Boost Netw...

Page 27: ...Fan 2 Bar 3 Fan 4 Coloured Bar Fan 5 Coloured Bar Blind 1 Mode Setting of the step width for blind 1 when pressing the arrow keys on the screen 1 On Off 0 100 2 4 steps 0 25 50 75 100 3 10 steps 0 10...

Page 28: ...led no text and measurement is displayed for sensor 1 0 Disabled 1 Room 2 Floor 3 Outside 4 Zone 1 5 Zone 2 6 Zone 3 7 Bathroom 8 Sauna 9 Bedroom 10 Kitchen 11 Cooler 12 Flow 13 Hot Water 14 Tank 15 P...

Page 29: ...o 651 001 Service Pin BACnet service pin only for BACnet devices if active the controller transmits a BACnet I am notification 0 Disabled Default 1 Enabled Maintenance Code PIN for setting mode 0000 n...