Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the 
Electrical and Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive 
terms and conditions.

In addition, the following points are to be observed:
–  These instructions must be read before installation and putting in operation and all notes provided therein are to be  regarded!
–  Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors at the device  

(e.g. by voltage induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided,  
and EMC directives are to be observed.

–  This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their  control authorities,  

the TÜV and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to 
prevent perils of any kind.

–  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
–  Consequential damages caused by a fault in this device are excluded from warranty or liability.
–  These devices must be installed and commissioned by authorised specialists.
–  The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. 

Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous 
improvement of our products.

–  In case of any modifications made by the user, all warranty claims are forfeited.
–  This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow.  

Direct sun irradiation or heat  irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

–  Operating this device close to other devices that do not comply with EMC directives may influence functionality.
–  This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury,  

or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

–  Dimensions of housings or housing accessories may show slight tolerances on the specifications provided in these instructions.
–  Modifications of these records are not permitted.
–  In case of a complaint, only complete devices returned in original packing will be accepted.

Notes on commissioning: 

This device was calibrated, adjusted and tested under standardised conditions. When operating under deviating conditions,  
we recommend performing an initial manual adjustment on-site during commissioning and subsequently at regular intervals. 

Commissioning is mandatory and may only be performed by qualified personnel!  
These instructions must be read before installation and commissioning and all notes provided therein are to be regarded!

G  

General notes

Connecting scheme 

Parallel operation

Connecting scheme 

Individual operation

Circuitry

Circuitry

0...10V

0V/GND

0...10V

0V/GND

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

Circuitry

0...10V

0V/GND

V

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

SUPPLY  VOLTAGE :

For operating voltage reverse polarity protection, a one-way rectifier or 
reverse polarity protection diode is integrated in this device variant. 

 

This internal one-way rectifier on AC  supply voltage. 

The output signal is to be tapped by a measuring instrument. The output 
signal is measured her against zero potential (O V) of the input voltage!

When this device is operated on 

DC supply voltage

, the operating voltage 

input UB+ is to be used for 15...36 V DC supply and UB – or GND for 
ground wire!

When several devices are supplied by one 24 V

 AC voltage supply

, it is to 

be ensured that all ”positive“ operating voltage input terminals (+) of the 
field devices are connected with each other and all ”negative“ operating 
voltage input terminals (–) (= reference potential) are connected together 
(in-phase connection of field devices). All outputs of field devices must be 
referenced to the same potential!

In case of reversed polarity at one field device, a supply voltage short- 
circuit would be caused by that device. The consequential short-circuit 
current flowing through this field device may cause damage to it. 

Therefore, pay attention to correct wiring!

Summary of Contents for RHEASGARD KHSSF

Page 1: ...ternal flow probe incl mounting flange with active switching output F Notice d instruction Capteur de d bit d air sur profil s chapeau pour montage en gaine contr leur de d bit d air lectronique sonde...

Page 2: ...Ma zeichnung Dimensional drawing Plan cot mm 44 45 65 25 max 155 12 20 KL 5 8 44 max 155 12 20 KL 5 8 Relay On Off 1 10 5 15 20 m s 1 2 3 4 5 6 7 8 9 10 11 12 48 33 58 90 2 36 5 Relay On Off 1 10 5 15...

Page 3: ...W24 Wechselkontakt 24 V max 5 A cos 1 Schalthysterese 2 EW Schwellwert ber Potentiometer einstellbar KHSSW W230 Wechselkontakt 230V AC max 10 A cos 1 Schalthysterese 2 EW Schwellwert ber Potentiometer...

Page 4: ...g aktiv Ausgang schaltend Art Nr KHSSF AOS KHSSF W 24 V AC DC 0 10 V 4 20 mA 1 Wechsler 1701 5118 0102 001 KHSSW KHSSW W24 24 V AC DC 1 Wechsler 1701 5113 0102 001 KHSSW W230 230V AC 1 Wechsler 1701 5...

Page 5: ...tetypen eine Anlauf berbr ckung von 60 s fest einprogrammiert Nach Zuschalten der Versorgungsspannung wird w hrend dieser Anlaufzeit eine Str mung von 20 m s bzw gr er als die eingestellte Schaltschwe...

Page 6: ...ollte nicht mehr als 100 m betragen eine Verpolung der Anschl sse kann zu Besch digungen am Ger t und oder anderen Ger ten am Leitungsstrang f hren Der Einbau hat unter Beachtung der bereinstimmung de...

Page 7: ...darf nicht f r berwachungszwecke welche dem Schutz von Personen gegen Gef hrdung oder Verletzung dienen und nicht als Not Aus Schalter an Anlagen und Maschinen oder vergleichbare sicherheitsrelevante...

Page 8: ...W230 230 V AC changeover contact max 10 A cos 1 a switching hysteresis of 2 final value threshold can be adjusted via potentiometer Data point flow velocity m s Sensor calorimetric temperature compens...

Page 9: ...A 1 changeover contact 1701 5118 0102 001 KHSSW KHSSW W24 24 V AC DC 1 changeover contact 1701 5113 0102 001 KHSSW W230 230V AC 1 changeover contact 1701 5133 0102 001 Note Changeover contact with aut...

Page 10: ...nently programmed into all unit types After the supply voltage is switched on a flow of 20 m s or greater than the set switching threshold during this start up time is assumed and the output signal is...

Page 11: ...nd BMS should not exceed 100 m Reversing the polarity of the connections can cause damage to the unit and or other units on the wiring harness Before installation make sure that the existing technical...

Page 12: ...monitoring applications which serve the purpose of protecting persons against hazards or injury or as an EMERGENCY STOP switch for systems or machinery or for any other similar safety relevant purpos...

Page 13: ...glable par potentiom tre KHSSW W24 Contact inverseur 24 V max 5 A cos 1 hyst r sis de commutation 2 Vf valeur seuil r glable par potentiom tre KHSSW W230 Contact inverseur 230 V CA max 10 A cos 1 hys...

Page 14: ...ce KHSSF AOS KHSSF W 24 V CA CC 0 10 V 4 20 mA 1 inverseur 1701 5118 0102 001 KHSSW KHSSW W24 24 V CA CC 1 inverseur 1701 5113 0102 001 KHSSW W230 230V CA 1 inverseur 1701 5133 0102 001 Remarque Conta...

Page 15: ...quelle un pontage au d marrage de 60 s est programm de mani re fixe dans tous les types d appareils Apr s la mise en marche de la tension d alimentation un d bit de 20 m s ou sup rieur au seuil de com...

Page 16: ...ble entre la sonde et la gestion technique de b timent ne doit pas d passer 100 m L inversion de la polarit des connexions peut endommager l appareil et ou d autres appareils sur le faisceau de c bles...

Page 17: ...mode de fonctionnement Cet appareil ne devra pas tre utilis des fins de surveillance qui visent la protection des personnes contre les dangers ou les blessures ni comme interrupteur d arr t d urgence...

Page 18: ...3 KHSSF W 0 10 4 20 Automatic Output Switching U I 24 5 cos 1 2 KHSSW W24 24 5 cos 1 2 KHSSW W230 230 10 cos 1 2 0 1 20 0 5 3 0 5 1 0 2 0 2 60 60 c 10 20 5 6 5 6 PC ABS UL94 V0 36 2TE 35 90 36 58 PA6...

Page 19: ...RD KHSSF RHEASREG KHSSW WG01 KHSSF AOS KHSSF W 24 0 10 4 20 1 1701 5118 0102 001 KHSSW KHSSW W24 24 1 1701 5113 0102 001 KHSSW W230 230 1 1701 5133 0102 001 AOS Automatic Output Switching DE 10 2015 0...

Page 20: ...20 r 2 4 0 1 20 60 20 10 0 1 20 5 6 5 6 KHSSF W KHSSW W24 KHSSW W230...

Page 21: ...21 r 5x d 3x d d KHSSF xx KHSSW xx VDE VDI 100 0 5 5 d 3 d DIN 43763 S S...

Page 22: ...22 ZVEI VDE EMV r 0 10 0 UB 15 36 UB GND 24 Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15 36V GND...

Page 23: ...the faultless quality of our products as stated in our General Terms and Conditions Sous r serve d erreurs et de modifications techniques Toutes les informations correspondent l tat de nos connaissanc...

Page 24: ...KHSSF W GND UB OUT Schaltbild Schematic diagram Sch ma de connexion KHSSW W230 Schaltbild Schematic diagram Sch ma de connexion KHSSW W24 1 2 3 4 5 6 7 8 9 10 11 12 Sensor GND black IN green UB red Re...

Reviews: