S+S Regeltechnik PREMASGARD 121 Modbus Series Operating Instructions, Mounting & Installation Download Page 4

4

Schaltbild 

PREMASGARD

® 

121x - Modbus

Nach erfolgreicher Nullpunktkalibrierung beträgt die  

Ausgangsspannung (bei Mittelstellung des Offsetreglers)   

5 V bei O Pa Druckdifferenz!

Ausgangsspannung  0 ...10 V   

für Druckdifferenz  – ∆P ... + ∆P

1 2 3 4 5

12345678

ON

DIPA

123456

ON DIPB

Stecker für Display

Kontaktseite:

rechts

Offset-Korrektur

Druck  ± 10% EW

LED und

Taster 

Nullpunkt setzen

(auto zero)

Stecker 

Display

Offset

auto

zero

min. max.

–UB  GND

Schirmung

RS485 Modbus A RS485 Modbus B

+UB  24V A

C/DC

mode

DIP A:  Busadresse 
DIP B:  Busparameter

(Baudrate, Parity ...)
Telegramm-Anzeige.

Empfang (LED grün)

Fehler (LED rot)

1 2 3 4 5

12345678

ON

DIPA

123456

ON DIPB

Stecker für Display

Kontaktseite:

rechts

Offset-Korrektur

Druck  ± 10% EW

LED und

Taster 

Nullpunkt setzen

(auto zero)

Stecker 

Display

Offset

auto

zero

min. max.

–UB  GND

Schirmung

RS485 Modbus A RS485 Modbus B

+UB  24V A

C/DC

mode

DIP A:  Busadresse 
DIP B:  Busparameter

(Baudrate, Parity ...)
Telegramm-Anzeige.

Empfang (LED grün)

Fehler (LED rot)

Die Offseteinstellung erfolgt über ein Potentiometer auf der Leiterplatte  
mit einem Einstellbereich von ± 10 % des Gerätedruckbereiches.  
Bei Auslieferung steht das Potentiometer in Mittelstellung und ist verlackt.  
Alle Einstellungen und Justagevorgänge, die zuvor durchgeführt werden,  
sind in dieser Konfiguration durchzuführen.  
Die Offseteinstellung wird mithilfe eines Werkzeuges „Schraubendreher 
2,5“ (Klingenbreite) durchgeführt.

Automatisches Einstellen des Offsets

1.

  Zum Setzen des Nullpunktes muss das Gerät mindestens  

60 Minuten in Betrieb sein. 

2.

  Die Druckeingänge P (+) und P (–) sind mit einem Schlauch zu 

verbinden  (Druckdifferenz zwischen den Eingängen = 0 Pa). 

3.

  Zum Setzen des Nullpunktes muss der Taster 5 Sekunden  

ununter brochen betätigt werden.  

Eine LED signalisiert durch kurzes Blinken die Abgleichanforderung und 
nach Ablauf eines Countdowns wird zu dem Messwert der gemessene 
(aktuelle) Offsetwert addiert und nullspannungssicher abgespeichert. 

Der korrekte Abgleich wird durch ein Dauerleuchten von 3 Sekunden  
der LED quittiert bzw. im Display (optional) durch das Umschalten  
von  "AUTO   0"  nach  "PROG   0"  angezeigt.

Hinweis:  Durch Loslassen des Tasters während des Countdowns  
(Zähler > 0) wird das Setzen des Nullpunktes sofort abgebrochen !

Manuelles Einstellen des Offsets

Mit dem Potentiometer kann der  OFFSET ∆P abgeglichen werden.  
Der Einstellbereich beträgt ca. ± 10 % vom Druckbereich.  
Hierbei kann ein anderer Referenzpunkt, als der Nullpunkt verwendet 
werden.

PREMASGARD

®

    121x - Modbus

  |  Nullpunktkalibrierung und Konfiguration

Anzeige individuell 

programmierbar

Summary of Contents for PREMASGARD 121 Modbus Series

Page 1: ...paktform mit Modbus Anschluss G Operating Instructions Mounting Installation Pressure and differential pressure measuring transducers incl connection set compact form with Modbus connection F Notice d...

Page 2: ...Y Adapter adaptateur WS 04 Wetter und Sonnenschutz optional Weather and sun protection optional Protection contre les intemp ries et le soleil en option ohne Display without display sin cran mit Disp...

Page 3: ...nes individuell programmierbaren Anzeigewertes ber die Modbusschnittstelle kann das Display sowohl im 7 Segment Bereich als auch im Dot Matrix Bereich individuell beschrieben werden BERWACHUNGSARTEN A...

Page 4: ...sind in dieser Konfiguration durchzuf hren Die Offseteinstellung wird mithilfe eines Werkzeuges Schraubendreher 2 5 Klingenbreite durchgef hrt Automatisches Einstellen des Offsets 1 Zum Setzen des Nu...

Page 5: ...Stoppbits OFF inaktiv default OFF inaktiv OFF Die Baudrate bertragungsgeschwindigkeit wird ber Pos 1 und 2 des DIP Schalters B eingestellt Einstellbar sind 9600 Baud 19200 Baud oder 38400 Baud siehe...

Page 6: ...alten Informationen ber die darzustellenden Zeichen und Segmente Der Dot Matrix Bereich ist ebenfalls in der Defaulteinstellung Register 4x0001 enth lt den Wert 0 programmierbar Im 7 Segment Bereich w...

Page 7: ...gle Register Function 16 Write Multiple Register Register Parameter Display Data Type Value Range 4x0001 physikalischer Anzeigewert Index im Display Unsigned 8 Bit 0 10 0 10 Differenzdruck in PA und h...

Page 8: ...s Reset Listen Only Mode Echo Telegramm 04 Aktivierung Listen Only Mode Keine Antwort 10 L sche Z hler Echo Telegramm 11 Z hler Bustelegramme Unsigned 16 Bit alle g ltigen Bustelegramme 12 Z hler Komm...

Page 9: ...leistungen und Haftungen bernommen Folgesch den welche durch Fehler an diesem Ger t entstehen sind von der Gew hrleistung und Haftung ausgeschlossen Montage und Inbetriebnahme der Ger te darf nur durc...

Page 10: ...individually programmable display value The Modbus interface allows the display to be individually configured in the 7 segment area and in the dot matrix area TYPES OF MONITORING A Below atmospheric p...

Page 11: ...device s pressure range Ex factory this potentiometer is in center position and is lacquer sealed All settings and adjustments that are made before must be done in this configuration Offset adjustment...

Page 12: ...ive ON ODD numbered OFF Inactive no parity 2 stop bits OFF Inactive default OFF Inaktive OFF The baud rate speed of transmission is set at DIP switches 1 and 2 of DIP switch block B Selectable are 960...

Page 13: ...t the characters and segments to be displayed The dot matrix area is also programmable in the default setting register 4x0001 contains the value 0 In this case the current measured value is automatica...

Page 14: ...e Register Register Parameter Data Type Value Range 4x0001 Physical parameter displayed Index on display Unsigned 8 Bit 0 10 0 10 Differential pressure in PA and hP 0 Default setting Freely configurab...

Page 15: ...Modbus Reset listen only mode Echo telegram 04 Activation listen only mode No answer 10 Delete counter Echo telegram 11 Counter bus telegrams Unsigned 16 Bit All valid bus telegrams 12 Counter commun...

Page 16: ...or defects and damages arising from improper use of this device Consequential damages caused by a fault in this device are excluded from warranty or liability These devices must be installed and commi...

Page 17: ...ie de texte possible sur l cran avec affichage 7 segments ou aussi affichage matrice de points via l interface Modbus MODES DE SURVEILLANCE A d pression P1 n est pas raccord ouvert c t air l atmosph r...

Page 18: ...diane et recouvert de peinture Tous les r glages et toutes les op rations d ajustage effectu s pr c demment doivent tre r alis s dans cette configuration On r alise le r glage du point z ro l aide d u...

Page 19: ...Baud vitesse de transfert est r gl via les pos 1 et 2 de l interrupteur DIP B On peut r gler 9600 Baud 19200 Baud ou 38400 Baud voir tableau La parit est r gl e via la pos 3 de l interrupteur DIP B On...

Page 20: ...ns sur les caract res et segments afficher La zone de matrice de points est galement programmable dans le r glage par d faut le registre 4x0001 contient la valeur 0 Dans la zone 7 segments la valeur d...

Page 21: ...r Registre Param tre Data Type Value Range 4x0001 Valeur d affichage physique Indice l cran Unsigned 8 bits 0 10 0 10 Pression diff rentielle in PA und hP 0 R glage par d faut Affichage librement conf...

Page 22: ...coute Seule T l gramme d cho 04 Activation Listen Only Mode mode coute seule Pas de r ponse 10 Efface compteur T l gramme d cho 11 Compteur T l grammes de bus Unsigned 16 Bit Tous les t l grammes de b...

Page 23: ...ctant les r gles de s curit correspondantes de la VDE des L nders de leurs organes de surveillance du T V et des entreprises d approvisionnement en nergie locales L acheteur doit respecter les disposi...

Page 24: ...Modbus 7 A P1 P2 B P1 P2 C P1 P2 P1 P2 PREMASGARD 121x Modbus Modbus ASD 06 2 PREMASGARD 121x Modbus 110 Pa 110 Pa 110 Pa 110 Pa 110 Pa 110 Pa 110 Pa 110 Pa 110 Pa A B C WG01 PREMASGARD 121x Modbus 1...

Page 25: ...Rec Err 1 2 3 4 5 12345678 ON DIPA 123456 ON DIPB Plug for display offset auto zero min max UB GND Shielding RS485 Modbus A RS485 Modbus B UB 24V AC DC mode Plug for display contact is on the right si...

Page 26: ...IP 1 128 DIP 1 ON DIP 2 64 DIP 2 ON DIP 3 32 DIP 3 OFF DIP 4 16 DIP 4 OFF DIP 5 8 DIP 5 OFF DIP 6 4 DIP 6 OFF DIP 7 2 DIP 7 OFF DIP 8 1 DIP 8 ON 128 64 1 193 Modbus DIP 1 DIP 2 MODBUS DIP B 9600 ON OF...

Page 27: ...001 10 4 0002 4 0012 4x0001 0 7 4x0005 0 A 1 B 2 C 3 D 4 DP 5 6 7 8 9 10 11 12 13 14 15 A A B C D E F G B C D DP 14 1 14 2 14 4x0003 4x0004 0 A 1 B 2 C 3 D 4 E 5 F 6 G 7 G 8 H 9 I 10 J 11 K 12 L 13 M...

Page 28: ...6 97 a 98 b 99 c 100 d 101 e 102 f 103 g 104 h 105 i 106 j 107 k 108 l 109 m 110 n 111 o 112 p 113 q ASCII 114 r 115 s 116 t 117 u 118 v 119 w 120 x 121 y 122 z 123 124 125 129 132 142 148 153 154 223...

Page 29: ...5000 3x0003 10 16 1000 1000 5000 5000 1000 1000 5000 5000 05 Write Single Coil 0x0001 0 0 1 ON OFF 08 Diagnostics 00 Loopback 01 Modbus Reset Listen Only Mode 04 Listen Only Mode 10 11 16 12 CRC 16 1...

Page 30: ...30 1 0 00001 0 01 1 0 001 0 000101971 1 0 01 10 1000 1 0 101971 1 1 1000 100000 100 10 1971 1 0 001 1 100 0 1 0 0101971 1 0 0980665 98 0665 9806 65 9 80665 1 P P 10 90 ZVEI VDE EMV r...

Page 31: ...n our General Terms and Conditions Sous r serve d erreurs et de modifications techniques Toutes les informations correspondent l tat de nos connaissances au moment de la publication Elles servent uniq...

Page 32: ...120 0 1 1 1 1 0 0 0 121 0 1 1 1 1 0 0 1 122 0 1 1 1 1 0 1 0 123 0 1 1 1 1 0 1 1 124 0 1 1 1 1 1 0 0 125 0 1 1 1 1 1 0 1 126 0 1 1 1 1 1 1 0 127 0 1 1 1 1 1 1 1 128 1 0 0 0 0 0 0 0 129 1 0 0 0 0 0 0 1...

Reviews: