G  

General notes

This device can be mounted in any position. The voltage output is short-circuit proof. Applying overvoltage at the voltage output will destroy this device. 
Pressure ranges are indicated on the device label. Applying measuring pressures beyond that range will cause mismeasurements and increased 
deviations or may destroy the device.

–  Attention! When leading in cables, make sure, they do not go under the board. 

This might buckle or damage hose connections! 

–  Pressure inputs are “poled“ i.e. the above-atmospheric pressure line must be connected at input P+ 

and the below-atmospheric pressure line must be connected at input P–. 

–  At an adjusting element, the output signal can be offset by ±  10 % of the final value of the measuring range. 

In this way, possible ageing or drift effects can be compensated. 

–  If this device is operated beyond the specified range, all warranty claims are forfeited.

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical 
and Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.

In additionIn addition, the following points are to be observed:

–  These instructions must be read before installation and putting in operation and all notes provided therein are to be  regarded!

–  Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors the device 

(e.g. by voltage induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to 
be observed.

–  This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their  control authorities, 

the TÜV and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to 
prevent perils of any kind.

–  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.

–  Consequential damages caused by a fault in this device are excluded from warranty or liability.

–  These devices must be installed by authorised specialists only.

–  The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively 

valid. Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous 
improvement of our products.

–  In case of any modifications made by the user, all warranty claims are forfeited.

–  This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow. Direct sun irradiation or heat 

 irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

–  Operating this device close to other devices that do not comply with EMC directives may influence functionality.

–  This device must not be used for monitoring applications, which solely serve the purpose of protecting persons against hazards or injury, 

or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

–  Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions.

–  Modifications of these records are not permitted.

–  In case of a complaint, only complete devices returned in original packing will be accepted.

These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded!

10

11

12

13

14

15

16

Summary of Contents for PREMASGARD 1160

Page 1: ...erating Instructions Mounting Installation Pressure and differential pressure measuring transducers switches monitors for volume flow rate indication series Thor II including connection set F Notice d...

Page 2: ...PREMASGARD 1160 PREMASREG 1160 D G F r Ma zeichnung PREMASGARD 1160 Dimensional drawing PREMASREG 1160 Plan cot 6000 m3 h PREMASGARD 1160 PREMASREG 1160 Anschl sse Connections Raccordements 2...

Page 3: ...ruckanschluss Stutzen aus Metall Druckart Differenzdruck Medium Luft nicht aggressive nicht brennbare Gase Genauigkeit 1 5 EW Druckbereich bei 20 C Summe von Liniarit t Hysterese 1 EW Druckbereich Tem...

Page 4: ...h PREMASGARD 1161 2170 200 0 10V PREMASREG 1161 2171 200 0 10V 1x Wechsler Zubeh r ASD 06 Anschluss Set im Lieferumfang enthalten bestehend aus 2 Anschlussnippel gerade aus ABS 2m Schlauch aus PVC wei...

Page 5: ...k Service O N Nullabgleich Funktion einstellbar DIP 6 Taster auto zero OFF Potentiometer Offset O N 1 2 3 4 LED auto zero up down select 1 2 3 4 5 6 ON DIP min max Offset Offset auto zero UB 24V AC DC...

Page 6: ...down select 1 2 3 4 5 6 ON DIP min max Offset Offset auto zero GND GND Pa V Stecker f r Display Offset Korrektur siehe Grafik ca 10 DIP Schalter Stecker Display Taster Nullpunkt setzen 1 Zeile zeigt d...

Page 7: ...ngsspannung bei Mittelstellung des Offsetreglers 5V bei OPa Druckdifferenz Ausgangsspannung 0 10V f r Druckdifferenz P P Manuelles Einstellen des Offsets Voraussetzung DIP Schalter 6 ist auf ON Schalt...

Page 8: ...cherheitsvorschriften des VDE der L nder ihrer berwachungsorgane des T V und der rtlichen EVU zu beachten Der K ufer hat die Einhaltung der Bau und Sicherungsbestimmung zu gew hrleisten und Gef hrdung...

Page 9: ...9...

Page 10: ...nd other non aggressive non combustible gases Accuracy 1 5 of pressure range end value at 20 C Sum linearity hysteresis 1 of pressure range end value Temperature drift values 0 1 of pressure range end...

Page 11: ...EMASGARD 1161 2170 200 0 10V PREMASREG 1161 2171 200 0 10V 1x Changeover contact Accessories ASD 06 connection set included in the scope of delivery consisting of 2 connection nipples straight made of...

Page 12: ...ice O N Zero point calibration Function selectable DIP 6 Pushbutton auto zero OFF Potentiometer Offset O N 1 2 3 4 LED auto zero up down select 1 2 3 4 5 6 ON DIP min max Offset Offset auto zero Pushb...

Page 13: ...Pa V Pushbutton Zero point settin Plug for display Offset correction see graph ca 10 DIP switches Plug for display 1st line showing actual pressure up to the measuring range limit Pa Pascal Precondit...

Page 14: ...ibration the output voltage is 5 V at 0 Pa pressure difference with the offset knob in central position Output voltage 0 10 V for pressure difference P P Manual offset adjustment Precondition DIP swit...

Page 15: ...rpose Respective safety regulations issued by the VDE the states their control authorities the T V and the local energy supply company must be observed The purchaser has to adhere to the building and...

Page 16: ...16...

Page 17: ...ibles 4 6 mm raccords de pression en m tal Type de pression pression diff rentielle Milieu air et gaz non agressifs non inflammables Pr cision 1 5 Vf de la plage de pression 20 C Somme de lin arit hys...

Page 18: ...161 2170 200 0 10V PREMASREG 1161 2171 200 0 10V 1x inverseur Accessoires ASD 06 Kit de raccordement fourni compos de 2 nipples de raccordement droits en ABS tuyau souple de 2 m en PVC mou et 4 vis t...

Page 19: ...mique OFF pression service O N ajustement du z ro Fonction r glable DIP 6 bouton poussoir auto zero OFF potentiom tre offset O N 1 2 3 4 LED auto zero up down select 1 2 3 4 5 6 ON DIP min max Offset...

Page 20: ...Zero point settin Plug for display Offset correction see graph ca 10 DIP switches Plug for display La premi re ligne affiche la pression r elle jusqu la limite de la plage de mesure Pa pascal Conditi...

Page 21: ...outon offset est en position m diane est de 5V pour une diff rence de pression de 0 Pa Tension de sortie 0 10V pour diff rence de pression P P R glage manuel du point z ro Condition pr alable l interr...

Page 22: ...lis que pour l usage qui est indiqu en respectant les r gles de s curit correspondantes de la VDE des L nders de leurs organes de surveillance du T V et des entreprises d approvisionnement en nergie l...

Page 23: ...23...

Page 24: ...20 15 36 10 1 24 2 2 24 1000 5000 0 10B 0 50 C 4 6x11 4 6 1 5 20 C 1 0 1 C 0 7 200 1 10 30 RAL 9010 108 x 72 5 x70 Thor II 0 14 1 5 M16 95 r H III EN 60730 IP65 IEC 60529 CE 2004 108 EC EN 61326 1 20...

Page 25: ...161 2171 200 0 10B 1x ASD 06 2 ABS 4 ASD 07 90 ABS DAL PREMASGARD 1160 PREMASREG 1160 6000m3 h 6000m3 h 6000m3 h A B C s l s l l 1 s 1 60 3600 1000 60 x 103 3 6 x 106 1 0 0166 1 60 16 66 1000 60 x 103...

Page 26: ...ero point setting Plug for display Offset correction see graph ca 10 DIP switches Plug display UB 24V AC DC Output volume flow rate 0 10V in Pa GND GND UB GND 1 12 11 13 2 3 4 LED auto zero up down se...

Page 27: ...4 LED auto zero up down select 1 2 3 4 5 6 ON DIP min max Offset Offset auto zero GND GND Pa V Pushbutton Zero point settin Plug for display Offset correction see graph ca 10 DIP switches Plug for di...

Page 28: ...PREMASGARD 1160 PREMASREG 1160 0 xx 4 0 0 10 0 PREMASGARD 1160 PREMASREG 1160 xx xx 5 0 0 10 DIP 6 ON ON OFF auto offset OFFSET P 10 28...

Page 29: ...r P P 10 ZVEI VDE EMV 29...

Page 30: ...30...

Page 31: ...r tro clairage Geh usedeckel um 180 drehbar Enclosure cover 180 degrees turnable Couvercle du bo tier orientable 180 180 31 Copyright by S S Regeltechnik GmbH Nachdruck auch auszugsweise nur mit Geneh...

Page 32: ...lan cot ASD 06 Anschluss Set Connection set Kit de raccordement Ma zeichnung ASD 06 Dimensional drawing Plan cot ASD 07 Anschlussnippel Connection nipple Embouts de raccordement DAL 1 Druckauslass Pre...

Reviews: