General notes

–  This device may only be used in pollutant-free non-precipitating air without above-atmospheric or below-atmospheric pressure at the sensor  element. 

–  On outdoor and duct sensors, the sinter filter of the senor element protects the humidity sensor against potential dust exposure.  

In case of pollution  ⁄  contamination, this filter should be cleaned on a regular basis.

–  Dust and pollution falsify measurement results and are to be avoided. Slight pollution and dust sediments can be removed by using compressed air. 

–  Touching the humidity element is under any circumstances to be avoided, as that would result in considerable mismeasurements.

–  In case of pollution, we recommend cleaning and recalibration in the factory.

–  In any case, the sensor must not get in contact with chemicals or other cleaning agents.

–  The relative humidity of 0 ...100 % is indicated by an output signal of 0 -10 V or 4...20 mA. 

The device operating range covers 10.0 ... 99.9 % r. H. Outside of that range, mismeasurements or increased deviations may occur.

–  When several sensors (0  -10 V) are connected to one voltage supply of 24 V  AC, correct polarity must be regarded as otherwise the  alternating  voltage 

source may be short-circuited. 

–  The voltage outputs are short-circuit proof. Applying overvoltage or voltage supply to the voltage output will destroy the device.

–  If this device is operated beyond the specified range, all warranty claims are forfeited.

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and 
Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.

In addition, the following points are to be observed:
–  These instructions must be read before installation and putting in operation and all notes provided therein are to be  regarded!
–  Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors at the device (e.g. by voltage 

induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be observed.

–  This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their  control authorities, the TÜV and 

the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent perils of any kind.

–  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
–  Consequential damages caused by a fault in this device are excluded from warranty or liability.
–  These devices must be installed and commissioned by authorised specialists.
–  The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. Deviations 

from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products.

–  In case of any modifications made by the user, all warranty claims are forfeited.
–  This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow.  

Direct sun irradiation or heat  irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

–  Operating this device close to other devices that do not comply with EMC directives may influence functionality.
–  This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury,  

or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

–  Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions.
–  Modifications of these records are not permitted.
–  In case of a complaint, only complete devices returned in original packing will be accepted.

Notes on commissioning: 

This device was calibrated, adjusted and tested under standardised conditions. When operating under deviating conditions, we recommend performing an 
initial manual adjustment on-site during commissioning and subsequently at regular intervals. 

Commissioning is mandatory and may only be performed by qualified personnel!  
These instructions must be read before installation and commissioning and all notes provided therein are to be regarded!

Summary of Contents for HYGRASGARD AFF Series

Page 1: ...assivem Ausgang G Operating Instructions Mounting Installation On wall humidity and temperature sensors 1 8 2 0 calibratable with multi range switching and active passive output F Notice d instruction...

Page 2: ...TF 2 0 AFF 20 AFTF 20 1 8 Tyr2 35 50 126 90 112 20 4 M16x1 5 16 137 35 112 20 4 M16x1 5 16 211 SF K Kunststoff Sinterfilter Standard Plastic sinter filter standard Filtre fritt en mati re synth tique...

Page 3: ...0 95 r H ohne Betauung zul ssige Luftfeuchte 95 r H nicht kondensierende Luft Abweichung Feuchte AFF AFTF AFF SD AFTF SD typisch 2 0 20 80 r H bei 25 C sonst 3 0 AFF 20 AFTF 20 AFF 25 AFTF 25 typisch...

Page 4: ...0 r H 4x wie oben 0 10 V 0 10 V Pt1000 1201 7111 2005 000 AFTF U NI1000 0 100 r H 4x wie oben 0 10 V 0 10 V Ni1000 1201 7111 2009 000 AFTF U NITK 0 100 r H 4x wie oben 0 10 V 0 10 V Ni1000TK5000 1201...

Page 5: ...1 0400 101 AFTF 25 xx aktiv AFTF 25 I T YR 2 0 100 r H 35 75 C 35 35 C 0 50 C 0 80 C 4 20 mA 4 20 mA 1201 7132 1000 101 AFTF 25 I T YR 2 DISPLAY 0 100 r H 4x wie oben 4 20 mA 4 20 mA 1201 7132 1400 10...

Page 6: ...passives Element UB GND Ausgang Temperatur 0 10V in C Ausgang Feuchte 0 10V in r H UB 24V AC DC z B Pt1000 Ni1000 LMZ235Z 1 2 3 4 5 6 passives Element UB GND optional f r Hintergrundbeleuchtung Ausgan...

Page 7: ...9 45 7 3 15 6 50 7 7 16 4 55 8 2 17 1 60 8 6 17 8 65 9 1 18 5 70 9 5 19 2 75 10 0 20 0 Temperaturtabelle MB 35 35 C C UA in V IA in mA 35 0 0 4 0 30 0 7 5 1 25 1 4 6 3 20 2 1 7 4 15 2 9 8 6 10 3 6 9...

Page 8: ...r tevariante eine Einweggleichrichtung bzw Verpolungschutzdiode integriert Diese interne Einweggleichrichtung erlaubt auch den Betrieb mit AC Versorgungs spannung bei 0 10 V Ger ten Das Ausgangssignal...

Page 9: ...Dieses Ger t ist nur f r den angegebenen Verwendungszweck zu nutzen dabei sind die entsprechenden Sicherheitsvorschriften des VDE der L nder ihrer berwachungsorgane des T V und der rtlichen EVU zu bea...

Page 10: ...n Permissible air humidity 95 r H non precipitating air Deviation humidity AFF AFTF AFF SD AFTF SD typically 2 0 20 80 r H at 25 C otherwise 3 0 AFF 20 AFTF 20 AFF 25 AFTF 25 typically 1 8 10 90 r H a...

Page 11: ...AY 0 100 r H 4 20 mA 1201 7112 0400 000 AFF U T YR 2 0 100 r H 0 10 V 1201 7111 0000 000 AFF U T YR 2 DISPLAY 0 100 r H 0 10 V 1201 7111 0400 000 AFTF xx active AFTF I T YR 2 0 100 r H 35 75 C 35 35 C...

Page 12: ...0 100 r H 0 10 V 1201 7131 0400 101 AFTF 25 xx active AFTF 25 I T YR 2 0 100 r H 35 75 C 35 35 C 0 50 C 0 80 C 4 20 mA 4 20 mA 1201 7132 1000 101 AFTF 25 I T YR 2 DISPLAY 0 100 r H 4x as above 4 20 mA...

Page 13: ...n r H 0 10V UB 24V AC DC 1 2 3 4 5 6 Passive element UB GND Output temperature in C 0 10V Output humidity in r H 0 10V UB 24V AC DC e g Pt1000 Ni1000 LMZ235Z 1 2 3 4 5 6 Passive element UB GND optiona...

Page 14: ...7 3 15 6 50 7 7 16 4 55 8 2 17 1 60 8 6 17 8 65 9 1 18 5 70 9 5 19 2 75 10 0 20 0 Temperature table MR 35 35 C C UA in V IA in mA 35 0 0 4 0 30 0 7 5 1 25 1 4 6 3 20 2 1 7 4 15 2 9 8 6 10 3 6 9 7 5 4...

Page 15: ...reverse polarity protection a one way rectifier or reverse polarity protection diode is integrated in this device variant This internal one way rectifier also allows operating 0 10 V devices on AC su...

Page 16: ...ed and EMC directives are to be observed This device shall only be used for its intended purpose Respective safety regulations issued by the VDE the states their control authorities the T V and the lo...

Page 17: ...t 0 100 h r sortie correspond 0 10 V ou 4 20 mA Plage de service humidit 0 95 h r sans condensation Humidit d air admissible 95 h r sans condensation de l air Incertitude de mesure AFF AFTF AFF SD AFT...

Page 18: ...t 0 10 V 0 10 V Pt1000 1201 7111 2005 000 AFTF U NI1000 0 100 h r 4x comme plus haut 0 10 V 0 10 V Ni1000 1201 7111 2009 000 AFTF U NITK 0 100 h r 4x comme plus haut 0 10 V 0 10 V Ni1000TK5000 1201 71...

Page 19: ...00 201 AFTF 20 xx actif AFTF 20 I T YR 2 0 100 h r 35 75 C 35 35 C 0 50 C 0 80 C 4 20 mA 4 20 mA 1201 7112 1000 201 AFTF 20 I T YR 2 DISPLAY 0 100 h r 4x comme plus haut 4 20 mA 4 20 mA 1201 7112 1400...

Page 20: ...umidity in r H 0 10V UB 24V AC DC e g Pt1000 Ni1000 LMZ235Z 1 2 3 4 5 6 Passive element UB GND optional for backlighting Output temperature in C 4 20mA Output humidity in r H 4 20mA UB 24V DC e g Pt10...

Page 21: ...7 3 15 6 50 7 7 16 4 55 8 2 17 1 60 8 6 17 8 65 9 1 18 5 70 9 5 19 2 75 10 0 20 0 Tableau de temp rature plage de mesure 35 35 C C UA en V IA en mA 35 0 0 4 0 30 0 7 5 1 25 1 4 6 3 20 2 1 7 4 15 2 9...

Page 22: ...sion de polarit c d elle comprend un redressement demi onde diode de re dressement Gr ce cette diode de redressement int gr e les appareils 0 10 V peuvent galement tre aliment s en courant alternatif...

Page 23: ...ll le avec des c bles de puissance les directives CEM sont respecter Cet appareil ne doit tre utilis que pour l usage qui est indiqu en respectant les r gles de s curit correspondantes de la VDE des L...

Page 24: ...20 I 35 35 C 35 75 C 0 50 C 0 80 C 0 10 B 4 20 AFF AFTF AFF 20 AFTF 20 AFF 25 AFTF 25 35 85 C 30 80 C AFF SD AFTF SD 35 85 C 30 70 C AFF AFTF 0 4 K 25 C AFF 20 AFTF 20 AFF 25 AFTF 25 0 2 K 25 C AFF SD...

Page 25: ...0 10 0 10 Pt1000 1201 7111 2005 000 AFTF U NI1000 0 100 4 0 10 0 10 Ni1000 1201 7111 2009 000 AFTF U NITK 0 100 4 0 10 0 10 Ni1000TK5000 1201 7111 2010 000 AFTF U LM235Z 0 100 4 0 10 0 10 LM235Z 10 K...

Page 26: ...8 Premium WG02 AFF 20 xx AFF 20 I T YR 2 0 100 4 20 A 1201 7112 0000 201 AFF 20 I T YR 2 DISPLAY 0 100 4 20 A 1201 7112 0400 201 AFF 20 U T YR 2 0 100 0 10 1201 7111 0000 201 AFF 20 U T YR 2 DISPLAY 0...

Page 27: ...Ni1000 LMZ235Z 1 2 3 4 UB GND Output temperature in C 0 10V Output humidity in r H 0 10V UB 24V AC DC 1 2 3 4 Output temperature in C 4 20mA Output humidity in r H 4 20mA UB 24V DC UB GND optional for...

Page 28: ...3 5 35 6 4 14 2 40 6 8 14 9 45 7 3 15 6 50 7 7 16 4 55 8 2 17 1 60 8 6 17 8 65 9 1 18 5 70 9 5 19 2 75 10 0 20 0 35 35 C C UA B IA A 35 0 0 4 0 30 0 7 5 1 25 1 4 6 3 20 2 1 7 4 15 2 9 8 6 10 3 6 9 7 5...

Page 29: ...e 4 20 AFTF xx U 0 10 AFTF xx I 4 20 A 2 1 2 3 4 230V AC 24VAC DC PLC PC UB 24V AC DC Output humidity in r H 0 10V Output temperature in C 0 10V UB GND 1 2 3 4 230V AC 24V DC UB 24V DC Output humidity...

Page 30: ...30 r 0 100 0 10 4 20 10 0 99 9 0 10 24 ZVEI VDE EMV...

Page 31: ...bserved We warrant the faultless quality of our products as stated in our General Terms and Conditions Sous r serve d erreurs et de modifications techniques Toutes les informations correspondent l tat...

Page 32: ...Plastic sinter filter standard Filtre fritt en mati re synth tique standard 43 3 14 8 14 8 107 72 M16x1 5 35 35 55 16 37 8 M16x1 5 39 49 4 3 64 64 43 3 14 8 14 8 107 72 M16x1 5 35 35 55 16 37 8 M16x1...

Reviews: