S+S Regeltechnik AERASGARD RTM-C02 Operating Instructions, Mounting & Installation Download Page 8

G  

General notes

–  This device may only be used in non-precipitating air without above-atmospheric or below-atmospheric pressure at the sensor element. 
–  The voltage output is short-circuit proof. 
–  Applying overvoltage will destroy the device.
–  In case of pollution, we recommend cleaning and recalibration in the factory. 
–  The device operating range covers 10 ... 95 % relative humidity respectively 0 ... 50 °C.  

Outside of that range, mismeasurements or increased deviations will occur. 

–  The device calibrates itself at an interval of 7 days. To ensure this function, the device needs to be supplied with  

fresh air (CO

2

 content 300  ppm ... 400  ppm) at least for 10 minutes during each 7-day period. 

–  If this device is operated beyond the specified range, all warranty claims are forfeited.

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and  Electronics 
Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.
In additionIn addition, the following points are to be observed:
–  These instructions must be read before installation and putting in operation and all notes provided therein are to be  regarded!
–  Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors the device  

(e.g. by voltage induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be observed.

–  This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their  control authorities, the TÜV and 

the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent perils of any kind.

–  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
–  Consequential damages caused by a fault in this device are excluded from warranty or liability.
–  These devices must be installed by authorised specialists only.
– The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid.   

Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our 
products.

–  In case of any modifications made by the user, all warranty claims are forfeited.
–  This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow.  

Direct sun irradiation or heat  irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

–  Operating this device close to other devices that do not comply with EMC directives may influence functionality.
–  This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury,  

or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

–  Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions.
–  Modifications of these records are not permitted.
–  In case of a complaint, only complete devices returned in original packing will be accepted.

These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded!

Connecting scheme 

Parallel operation

Connecting scheme 

Individual operation

Circuitry

Circuitry

0...10V

0V/GND

0...10V

0V/GND

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

Circuitry

0...10V

0V/GND

V

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

SUPPLY  VOLTAGE :

For operating voltage reverse polarity protection, a one-way rectifier or 
reverse polarity protection diode is integrated in this device variant. 

 

This internal one-way rectifier also allows operating 0 - 10 V devices on AC 
 supply  voltage. 

The output signal is to be tapped by a measuring instrument. Output 
 voltage is measured her against zero potential (O V) of the input voltage!

When this device is operated on 

DC supply voltage

, the operating voltage 

input UB+ is to be used for 15...36 V DC supply and UB – or GND for 
ground wire!

When several devices are supplied by one 24 V

 AC voltage supply

, it is to 

be ensured that all ”positive“ operating voltage input terminals (+) of the 
field devices are connected with each other and all ”negative“ operating 
voltage input terminals (–) (= reference potential) are connected together 
(in-phase connection of field devices). All outputs of field devices must be 
referenced to the same potential!

In case of reversed polarity at one field device, a supply voltage short- 
circuit would be caused by that device. The consequential short-circuit 
current flowing through this field device may cause damage to it. 

Therefore, pay attention to correct wiring!

Summary of Contents for AERASGARD RTM-C02

Page 1: ...Ausgang G Operating Instructions Mounting Installation Room temperature and CO2 measuring transducers self calibrating with active switching output F Notice d instruction Sonde transmetteur temp ratu...

Page 2: ...AERASGARD RTM CO2 D G F r Ma zeichnung Geh use Dimensional drawing Enclosure Plan cot bo tier Baldur2 T K 6 0 98 98 32 6...

Page 3: ...RTM CO2 2S kann der Betriebmodus per Taster gewechselt werden Automatik Manuell Stufe 1 und 2 und AUS Ausgang CO2 0 10 V Messgenauigkeit CO2 70 ppm zzgl 5 vom Messwert Druckabh ngigkeit 1 6 kPa bezog...

Page 4: ...anuelle Kalibrierung des Ausgangssignals auf 2 25 V 450 ppm Nullpunkt wird durch das Bet tigen des Tasters manuelle Kalibrierung CO2 ca 10 Sekunden dr cken gestartet Die Vorbereitung der Kalibrierung...

Page 5: ...s und der stetigen Verbesserung unserer Produkte m glich Bei Ver nderungen der Ger te durch den Anwender entfallen alle Gew hrleistungsanspr che Dieses Ger t darf nicht in der N he von W rmequellen z...

Page 6: ...nged via pushbutton Automatic Manual Step 1 and Step 2 and OFF Output CO2 0 10 V Measuring accuracy CO2 70 ppm plus 5 of measured value Pressure dependence 1 6 kPa referred to standard pressure Long t...

Page 7: ...n Afterwards continuous operation for at least 10 minutes with fresh air CO2 content 300 400 ppm must be ensured Manual calibration of the output signal to 2 25 V 450 ppm zero point is started by pres...

Page 8: ...le in terms of technical progress and continuous improvement of our products In case of any modifications made by the user all warranty claims are forfeited This device must not be installed close to...

Page 9: ...matique Plage de mesure CO2 0 2000 ppm Sur le RTM CO2 2S le mode de fonctionnement peut tre chang par un bouton poussoir Automatique manuel degr s 1 et 2 et ARR T Sortie CO2 0 10 V Incertitude de mesu...

Page 10: ...ment continu d au moins 10 minutes avec de l air frais teneur en CO2 300 400 ppm L talonnage manuel du signal de sortie 2 25 V 450 ppm point z ro est lanc avec une pression du bouton poussoir talonnag...

Page 11: ...outre de respecter les points suivants Avant de proc der toute installation et la mise en service veuillez lire attentivement la pr sente notice et toutes les consignes qui y sont pr cis es Les racco...

Page 12: ...I EN 60 730 IP 30 EN 60 529 CE EN 61326 2014 30 EU 2014 35 EU RTM CO2 RTM CO2 A RTM CO2 2S 1 2 3 4 5 6 7 8 9 UB 24V AC DC UB 24V AC DC Free Free GND Free Free Output CO2 content in ppm 0 10V Output te...

Page 13: ...4 800 1 1400 1 5 900 1 1500 1 S1 S2 5 3 4 2 1 5 3 4 2 1 CO2 350 1 1 75 10 300 400 1 2 25 450 1 CO2 10 2 25 3 5 AERASGARD RTM CO2 2 Standard WG02 CO2 2x RTM CO2 RTM CO2 0 2000 1 0 50 C 0 10 1501 61B2 1...

Page 14: ...B 15 36 UB GND 24 Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15 36V GND r 10 95 0 50 C 7 300 400 ppm 10 7 ZVE...

Page 15: ...he bottom frame slightly Pull top cover forward and hold it Pour ouvrir le bo tier placer le tournevis 2 0 au centre de l encoche pousser vers le bas et soulever l g rement le cadre inf rieur Tirer le...