G
AERASGARD
®
RFTM - LQ - PS - CO2 - Modbus
|
Configuration
READOUT IN THE DISPLAY
By default, the display indicates the following measurements with the corresponding units
cyclically
and consecutively:
CO2
content in ppm,
air quality
(VOC) in %,
temperature
in °C,
relative humidity
in % r.H.,
particulate matter
(PM) in µg/m
3
The Modbus interface can be used to program an
alternative output variable
instead of the standard display:
CO2
content in ppm,
air quality
(VOC) in %,
temperature
in °C,
relative humidity
in % r.H.,
particulate matter
(PM) in µg/m
3
In this case, the first line indicates the value and indexwhile the second line indicates the corresponding unit
statically
.
The index indicates the display type, e.g. particulate matter (see the table "Function 06 Write Single Register").
Reading:
68
Index:
6
Unit:
µg/m
The Modbus interface allows the display screen to be individually configured, both in the 7 and 14 segment range
and in the dot-matrix range. This means that messages such as those from the PLC can be displayed.
For the
individual display
, the register 4x0001 (physical value displayed) must contain the value 10.
The registers 4x0002 to 4x0012 contain information about the characters and segments to be displayed.
The dot-matrix area is also programmable in the default setting (register 4x0001 contains the value 0).
In this case, the current measured value is automatically displayed in the 7-segment area.
Composition of Segment Pattern (Register 4x0005)
Bit 0 ......
Dot A
Bit 1 ......
Dot B
Bit 2 ......
Dot C
Bit 3 ......
Dot D
Bit 4 ......
Dot DP
Bit 5 ......
Percent
Bit 6 ......
- -
Bit 7 ......
- -
Bit 8 ......
- -
Bit 9 ......
- -
Bit 10 ....
- -
Bit 11 ....
- -
Bit 12 ....
- -
Bit 13 ....
- -
Bit 14 ....
- -
Bit 15 ....
- -
Dot A
Dot Matrix
A
B
C
D
E
F
G
Dot B
Dot C
Dot D
Percent
14-Segment 1
14-Segment 2
Dot DP
Composition of 14-Segment Pattern (Register 4x0003 and 4x0004)
Bit 0 ......
A
Bit 1 ......
B
Bit 2 ......
C
Bit 3 ......
D
Bit 4 ......
E
Bit 5 ......
F
Bit 6 ......
G
Bit 7 ......
G'
Bit 8 ......
H
Bit 9 ......
I
Bit 10 ....
J
Bit 11 ....
K
Bit 12 ....
L
Bit 13 ....
M
Bit 14 ....
- -
Bit 15 ....
- -
A
D
I
L
J
K
H
G
G'
F
B
E
C
M
Example for characters
Degrees Celsius (°C)
14-Segment 1:
14-Segment 2:
227 57
(Register 4x003)
(Register 4x004)