S+S Regeltechnik AERASGARD RFTM- LQ-PS-CO2-Modbus Operating Instructions, Mounting & Installation Download Page 17

17

G

 

Installation and Commissioning

Automatic calibration of the  VOC measurement  (permanently active)

The regular exchange of fresh air is all that is required for the self-calibration technology in the sensor. The device detects this condition and  
performs the calibration automatically. It is sufficient to open the windows or set the air conditioning system to use outdoor air at regular intervals. 
Make sure that no harmful substances influence the ambient air during this process. Proceed as follows:

Open all windows fully or set the air conditioning system to use outdoor air 1x weekly for 15-20 minutes.  
During this time, the release of gases from volatile organic substances must be prevented as far as possible. 
Regular ventilation of the rooms and flushing of the duct with fresh air will increase the measuring accuracy of the sensor.

Every time the device is switched on, the automatic calibration cycle restarts and calculates a correction value across the operating period.  
In case of power disruptions of less than 7 days, the calculation algorithm may be supported with a manual calibration to adjust the correction value 
more quickly. 

Manual calibration of the VOC measurement

Manual calibration can be carried out independently of automatic calibration. Sufficient fresh air must be 
provided before and during the calibration procedure. Also make sure that no harmful substances influence 
the ambient air. Proceed as follows to perform manual calibration:

1.

  Preparation: Prevent the release of gases from volatile organic substances as far as possible,  

open windows and set air conditioning system to use outdoor air, remove the housing cover and  
wait 15 minutes.

2.

  Press and hold the 

“ZERO VOC”

 button until the flashing LED row changes to a steady light after  

5 seconds. Devices with a display indicate 

“AUTO 0”

 and change the countdown from 5 to 60. The 

calibration process has started. Keep the windows open or the air conditioning system set to use 
outdoor air.

3.

  After 60 seconds, the calibration is complete (status LED has gone out, the countdown is complete) 

and the device indicates or transmits the current VOC concentration.

Summary of Contents for AERASGARD RFTM- LQ-PS-CO2-Modbus

Page 1: ...midity temperature air quality VOC fine dust PM and CO2 content calibratable with Modbus connection F Notice d instruction Sonde d ambiance multifonctions resp convertisseur de mesure pour l humidit l...

Page 2: ...O2 Modbus D G F r T K 6 0 98 98 32 6 T K 6 0 98 98 32 6 34 6 RCO2 Modbus RLQ CO2 Modbus RFTM CO2 Modbus RFTM LQ CO2 Modbus RFTM CO2 Modbus P Ma zeichnung Dimensional drawing Plan cot Ma zeichnung Dime...

Page 3: ...e Langzeitstabilit t Abweichung RH typisch 2 0 20 80 r H bei 25 C sonst 3 0 Abweichung C typisch 0 2 K bei 25 C LUFTQUALIT T VOC Sensor VOC VOC Sensor Metalloxid mit automatischer Kalibrierung volatil...

Page 4: ...us Taster Potentio meter RFTM CO2 Modbus P R xx Modbus AERASGARD Rxx Modbus Raumf hler bzw Messumformer f r Feuchte Temperatur Luftqualit t VOC Feinstaub PM und CO2 Gehalt Deluxe Typ WG02 Messbereiche...

Page 5: ...und damit nicht der werksseitigen Kalibrierung entsprechen vom Kunden eingestellt werden Hierbei ist zu beachten dass die Werkskalibrierung verloren geht und die Einhaltung der technischen Daten nicht...

Page 6: ...sunterbrechung k rzer 7 Tage kann der Berechnungs algorithmus durch eine manuelle Kalibrierung unterst tzt werden um eine schnellere Anpassung des Korrekturwertes zu erreichen Manuelle Kalibrierung de...

Page 7: ...Stoppbits OFF inaktiv default OFF inaktiv OFF Die Baudrate bertragungsgeschwindigkeit wird ber Pos 1 und 2 des DIP Schalters B eingestellt Einstellbar sind 9600 Baud 19200 Baud oder 38400 Baud siehe...

Page 8: ...ich programmiert werden Somit k nnen auch beispielsweise Meldungen von der SPS angezeigt werden F r die individuelle Anzeige muss das Register 4x0001 physikalischer Anzeigewert den Wert 10 enthalten D...

Page 9: ...ameter Data Type Value Range 3x0001 CO2 Abtastung 4 s Signed 16 Bit 350 5000 350 5000 ppm 3x0002 CO2 Filterung 32 s Signed 16 Bit 350 5000 350 5000 ppm 3x0003 VOC in Abtastung 4 s Signed 16 Bit 0 1000...

Page 10: ...C Unsigned 8 Bit 0 255 ASCII Zeichen 4x0009 Dot Matrix Zeichen D Unsigned 8 Bit 0 255 ASCII Zeichen 4x0010 Dot Matrix Zeichen E Unsigned 8 Bit 0 255 ASCII Zeichen 4x0011 Dot Matrix Zeichen F Unsigned...

Page 11: ...er Exception Meldungen Unsigned 16 Bit Fehlerz hler 14 Z hler Slave Telegramme Unsigned 16 Bit Slave Telegramme 15 Z hler Telegramme ohne Antwort Unsigned 16 Bit Broadcastmeldungen Adresse 0 Function...

Page 12: ...r getrennte Segmente aufzuteilen Die Teilnehmeradresse kann von 1 bis 247 eingestellt werden F r die Busleitung ist ein Kabel mit paarverseilter Datenleitung Spannungsversorgung und Kupferabschirmgefl...

Page 13: ...nahme der Ger te darf nur durch Fachpersonal erfolgen Es gelten ausschlie lich die technischen Daten und Anschlussbedingungen der zum Ger t gelieferten Montage und Bedienungs anleitung Abweichungen zu...

Page 14: ...iation C typically 0 2 K at 25 C AIR QUALITY VOC Sensor VOC VOC sensor metal oxide with automatic calibration VOC volatile organic compounds Measuring range VOC 0 100 air quality with reference to cal...

Page 15: ...TM LQ PS CO2 Modbus RFTM LQ PS CO2 Modbus 0 100 r H 0 50 C 0 1000 g m3 5000 ppm 0 100 1501 2119 6001 500 RFTM LQ PS CO2 Modbus LCD 0 100 r H 0 50 C 0 1000 g m3 5000 ppm 0 100 1501 2119 6021 500 Note T...

Page 16: ...on site conditions which do not correspond to the function domain and thus the factory calibration Here it should be noted that the factory calibration will be lost and technical data compliance can n...

Page 17: ...perating period In case of power disruptions of less than 7 days the calculation algorithm may be supported with a manual calibration to adjust the correction value more quickly Manual calibration of...

Page 18: ...ctive ON ODD numbered OFF Inactive no parity 2 stop bits OFF Inactive default OFF Inactive OFF The baud rate speed of transmission is set at DIP switches 1 and 2 of DIP switch block B Selectable are 9...

Page 19: ...e and in the dot matrix range This means that messages such as those from the PLC can be displayed For the individual display the register 4x0001 physical value displayed must contain the value 10 The...

Page 20: ...ue Range 3x0001 CO2 Sampling 4 s Signed 16 Bit 350 5000 350 5000 ppm 3x0002 CO2 Filtering 32 s Signed 16 Bit 350 5000 350 5000 ppm 3x0003 VOC in Sampling 4 s Signed 16 Bit 0 1000 0 0 100 0 VOC 3x0004...

Page 21: ...t Matrix Character C Unsigned 8 Bit 0 255 ASCII character 4x0009 Dot Matrix Character D Unsigned 8 Bit 0 255 ASCII character 4x0010 Dot Matrix Character E Unsigned 8 Bit 0 255 ASCII character 4x0011 D...

Page 22: ...ams Unsigned 16 bit Error counter 14 Counter slave telegrams Unsigned 16 bit Slave telegrams 15 Counter telegrams without answer Unsigned 16 bit Broadcast messages address 0 Function 17 Report Slave I...

Page 23: ...ubscribers is greater the bus must be subdivided into several segments separated by repeaters The subscriber address can be set from 1 to 247 For the bus line a twisted pair cable data line power supp...

Page 24: ...mounting and operating instructions delivered together with the device are exclusively valid Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of tech...

Page 25: ...typique 2 0 20 80 h r 25 C sinon 3 0 cart C typique 0 2 K 25 C QUALIT DE L AIR COV Capteur COV capteur COV oxyde m tallique avec talonnage automatique volatile organic compounds compos s organiques vo...

Page 26: ...r 0 50 C 0 1000 g m3 5000 ppm 0 100 1501 2119 6001 500 RFTM LQ PS CO2 Modbus LCD 0 100 h r 0 50 C 0 1000 g m3 5000 ppm 0 100 1501 2119 6021 500 Remarque Ces appareils ne doivent pas tre utilis s comm...

Page 27: ...les appareils doivent tre r gl s par le client selon les conditions sur place qui ne correspondent pas au champ de d finition et l talonnage d usine Noter que dans ce cas l talonnage d usine est perd...

Page 28: ...n est calcul e pour la dur e de fonctionnement En cas de coupure de tension inf rieure 7 jours l algorithme de calcul peut tre accompagn par une l talonnage manuel afin que la valeur de correction soi...

Page 29: ...de Baud vitesse de transfert est r gl via les pos 1 et 2 de l interrupteur DIP B On peut r gler 9600 Baud 19200 Baud ou 38400 Baud voir tableau La parit est r gl e via la pos 3 de l interrupteur DIP B...

Page 30: ...14 segments que dans la zone de matrice de point Il est ainsi possible par exemple d afficher les messages de l API Pour l affichage librement programmable le registre 4x0001 valeur d affichage physi...

Page 31: ...re Param tre Data Type Value Range 3x0001 CO2 Balayage 4 s Signed 16 Bit 350 5000 350 5000 ppm 3x0002 CO2 Filtrage 32 s Signed 16 Bit 350 5000 350 5000 ppm 3x0003 COV en Balayage 4 s Signed 16 Bit 0 1...

Page 32: ...caract re C Unsigned 8 Bit 0 255 Caract res ASCII 4x0009 Matrice de points caract re D Unsigned 8 Bit 0 255 Caract res ASCII 4x0010 Matrice de points caract re E Unsigned 8 Bit 0 255 Caract res ASCII...

Page 33: ...on s 13 Compteur Messages d exception Unsigned 16 Bit Compteur d erreurs 14 Compteur T l grammes esclaves Unsigned 16 Bit T l grammes esclaves 15 Compteur T l grammes sans r ponse Unsigned 16 Bit Mess...

Page 34: ...s doit tre r parti en plusieurs segments par l interm diaire de repeaters L adresse des correspondants peut tre fix e de 1 247 Pour la ligne de bus on peut utiliser un c ble avec ligne de donn es alim...

Page 35: ...urs commises sur cet appareil L installation et la mise en service des appareils doit tre effectu e uniquement par du personnel qualifi Seules les donn es techniques et les conditions de raccordement...

Page 36: ...24 200 C VOC 1 3 CO2 1 C 2 0 20 80 25 C 3 0 C 0 2 25 C VOC VOC VOC VOC VOC 0 100 VOC low medium high VOC 20 VOC 60 0 1000 3 PM 2 5 0 3 2 5 PM 10 0 3 10 10 3 10 PM 2 5 25 3 25 PM 10 1 25 3 1 25 10 CO2...

Page 37: ...LCD 0 100 0 50 C 0 1000 3 5000 1 0 100 1501 2119 6021 500 1 2 3 4 1 2 3 4 shield shield U GND A B U GND A B mode address zero offset CO CO VOC VOC r H C 1 2 3 4 5 6 7 8 ON DIPA 1 2 3 4 5 6 ON DIPB DIP...

Page 38: ...38 r CO2 350 1 0 10 30 50 1 2 3 50 CO2 350 500 1 15 20 Modbus CO2 350 500 1 1 2 ZERO CO2 5 AUTO 0 5 600 3 4 10 350 500 1...

Page 39: ...39 r VOC 15 20 7 VOC 1 15 2 ZERO VOC 5 AUTO 0 5 60 3 60 VOC...

Page 40: ...P DIP 1 128 DIP 1 ON DIP 2 64 DIP 2 ON DIP 3 32 DIP 3 OFF DIP 4 16 DIP 4 OFF DIP 5 8 DIP 5 OFF DIP 6 4 DIP 6 OFF DIP 7 2 DIP 7 OFF DIP 8 1 DIP 8 ON 128 64 1 193 Modbus DIP 1 DIP 2 MODBUS DIP B 9600 ON...

Page 41: ...er 68 6 7 14 4x0001 10 4 0002 4 0012 4x0001 0 7 4x0005 0 A 1 B 2 C 3 D 4 DP 5 6 7 8 9 10 11 12 13 14 15 A A B C D E F G B C D 14 1 14 2 DP 14 4x0003 4x0004 0 A 1 B 2 C 3 D 4 E 5 F 6 G 7 G 8 H 9 I 10 J...

Page 42: ...8 l 109 m 110 n 111 o 112 p 113 q ASCII 114 r 115 s 116 t 117 u 118 v 119 w 120 x 121 y 122 z 123 124 125 129 132 142 148 153 154 223 ASCII 04 Read Input Register 3x0001 CO2 4 16 350 5000 350 5000 1 3...

Page 43: ...0 255 ASCII 4x0009 D 8 0 255 ASCII 4x0010 8 0 255 ASCII 4x0011 F 8 0 255 ASCII 4x0012 G 8 0 255 ASCII 4x0020 8 0 63 0 100 4x0021 CO2 16 512 511 4x0022 16 512 511 4x0023 16 512 511 4x0024 16 512 511 05...

Page 44: ...Reset Listen Only Mode 04 Listen Only Mode 10 11 16 12 CRC 16 13 16 14 16 15 16 0 17 Report Slave ID 00 8 6 01 8 AERSGARD MODBUS 17 T H V P C 18 T H V C 19 T H C 20 T H 21 T H P T H V VOC P PM C CO2...

Page 45: ...bus 32 1 247 100 Profibus Slave n MODBUS RTU Master RS 485 20 n 40 n Slave 1 Slave 2 LA LA A D1 D GND B D0 D MODBUS RTU Master Slave 1 Slave 2 5 B RBIAS RBIAS RAB RAB r AERASGARD RFTM LQ PS CO2 Modbus...

Page 46: ...46 r VOC 10 95 0 50 C VOC CO2 VOC ZVEI VDE EMV VDE VDI 0 5 g...

Page 47: ...dge at date of publication They are only meant to inform about our products and their application potential but do not imply any warranty as to certain product characteristics Since the devices are us...

Page 48: ...120 0 1 1 1 1 0 0 0 121 0 1 1 1 1 0 0 1 122 0 1 1 1 1 0 1 0 123 0 1 1 1 1 0 1 1 124 0 1 1 1 1 1 0 0 125 0 1 1 1 1 1 0 1 126 0 1 1 1 1 1 1 0 127 0 1 1 1 1 1 1 1 128 1 0 0 0 0 0 0 0 129 1 0 0 0 0 0 0 1...

Reviews: